2023-03-03 14:09:16 | NEW SINGLE FAMILY RESIDENCE(R3)SIXTH BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #20121077 |
| 839 4TH ST |
| |
| ****NOTE: |
| ACCORDING TO THE DEPARTMENT OF BUSINESS & PROFESSIONAL |
| REGULATION, THE CONTRACTOR'S LICENSE IS SUSPENDED. |
| CONTRACTOR TO UPDATE LICENSE STATUS WITH DBPR PRIOR TO |
| OBTAINING THE PERMIT. |
| |
| |
| NOTE: |
| ENGINEER OF RECORD TO PAY $4728.72 FEE OF FOUR TIMES |
| THE AMOUNT OF THE PROPORTION OF THE PERMIT FEE |
| ATTRIBUTED TO PLANS REVIEW (LAST REVIEW AND THIS ONE). |
| FLORIDA STATUTE 553.80(2)(B |
| |
| NOTE: |
| ARCHITECTS-ENGINEERS |
| FLORIDA STATUTE 553.80(2)(B): |
| ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN |
| PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT |
| NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE |
| FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| REVIEW |
| |
| ORIGINAL COMMENT: |
| 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING |
| COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. |
| |
| PREVIOUS COMMENT: |
| 3-ATTIC ACCESS WAS RELOCATED, BUT BASED ON THE ROOF |
| FRAMING PLAN, THE LOCATION OF THE ATTIC ACCESS DOESN'T |
| SEEM TO PROVIDE THE HEADROOM CLEARANCE REQUIRED BY SEC. |
| R807 FBC-RESIDENTIAL. ATTIC ACCESS IS LOCATED BETWEEN |
| TWO GABLE END ROOFS. ALSO, BASED ON SECTION 2 ON SHEET |
| S-3, THERE IS A MASONRY WALL BETWEEN THE FRONT PART OF |
| THE HOUSE AND THE REAR PART OF THE HOUSE. THEREFORE, |
| THERE IS NOT ACCESS TO OTHER ROOF AREAS. EACH ROOF AREA |
| NEEDS AN ATTIC ACCESS. REVISE AS REQUIRED. |
| |
| PREVIOUS COMMENT: |
| 3- ATTIC ACCESS WAS NOT REVISED ON THE ROOF FRAMING |
| PLAN TO MATCH LOCATIONS SHOWN ON SHEET A-1. |
| SEC. R807 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| A)ROOF FRAMING PLAN ON SHEET S2 SHOWS ATTIC ACCESS BY |
| THE KITCHEN AREA BEING BLOCKED BY THE TRUSS GIRDER |
| ABOVE. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| B)BEDROOM #3 ATTIC ACCESS LOCATION SHOWN ON SHEET A1 |
| DOESN'T MATCH LOCATION AND ORIENTATION SHOWN ON THE |
| ROOF FRAMING PLAN ON SHEET S2. REVISE TO MATCH. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 6-SECTION 2 ON SHEET S-3 SHOWS A MASONRY WALL BETWEEN |
| THE FRONT PART OF THE HOUSE AND THE REAR PART OF THE |
| HOUSE. ROOF FRAMING PLAN ON SHEET S-2 DOESN'T SPECIFY |
| THE BEAM SUPPORTING THE MASONRY WALL. |
| ROOF FRAMING PLAN DOESN'T SHOW HOW THE TWO REAR GABLE |
| END ROOFS ARE SUPPORTED AT THE INTERSECTION OF BOTH |
| ROOFS. |
| FRONT PORCH WOOD BEAM SIZE AND ROOF RAFTERS SIZE |
| SPECIFIED ON THE ROOF FRAMING PLAN AND WOOD BEAM |
| SPECIFIED ON SECTION 2 ON SHEET S-3 DON'T MATCH. |
| SECTION 2 ON SHEET S-3 SHOWS OUT LOOKERS IN THE MIDDLE |
| MASONRY WALL. THE OUT LOOKERS ARE ON THE OTHER SIDE OF |
| THE SECTION BY THE GABLE END AREA. REVISE/CLARIFY WALL |
| SECTION AS REQUIRED. |
| SEC. R301.1 FBC-RESIDENTIAL. |
| |
| PREVIOUS COMMENT: |
| D)NEW C1 COLUMN IS NOT SHOWN ON THE FLOOR PLAN ON SHEET |
| A-1. |
| |
| RESPONSE: |
| PROPOSED FLOOR PLAN ON SHEET A1 SHOWS NEW COLUMN C1 |
| BLOCKING THE HALLWAY LEADING TO BEDROOM #2 AND BEDROOM |
| #3. REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| PREVIOUS COMMENT: |
| E)BEAM SUPPORTING THE TWO GABLE END TRUSSES IS NOT |
| SPECIFIED ON THE |
| BEAM SCHEDULE. |
| |
| RESPONSE: |
| REPEAT COMMENT. ROOF FRAMING PLAN DOESN'T SPECIFY THIS |
| BEAM. SEE SECTION-1 ON SHEET S3. THE BEAM IN QUESTION |
| IS THE CENTER BEAM SUPPORTING THE TWO GABLE END |
| TRUSSES. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| A)OK. ROOF SHINGLES FL31588-R2. |
| |
| PREVIOUS COMMENT: |
| D)HARDIE BOARD SIDING. |
| FLORIDA PRODUCT APPROVAL NUMBER UPLOADED TO PROJECTDOX |
| DOESN'T MATCH FLORIDA PRODUCT APPROVAL NUMBER NAMED IN |
| PROJECTDOX SUPPORTING DOCUMENTS. ONE OF THEM IS |
| FL13223-R7 AND THE OTHER ONE IS FL13192.2. REVISE AS |
| REQUIRED TO MATCH. |
| NOTE: WHEN RESUBMITTING PLEASE UPLOAD THE FLORIDA |
| PRODUCT APPROVAL COVER PAGE AND INSTALLATION |
| INSTRUCTION ON THE SAME FILE. DON'T SPLIT THEM INTO TWO |
| SEPARATE FILES. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| NEW COMMENT: |
| 12- ENGINEER'S SELF CERTIFIED DIGITAL SIGNATURE |
| 1- REVISED DRAWINGS A1, S1, S2, S3 AND S5 HAVE |
| ENGINEER'S SELF-CERTIFIED SIGNATURE. BOARD OF |
| ENGINEER'S DON'T ALLOW SELF-CERTIFICATION. A THIRD |
| PARTY CERTIFICATION IS REQUIRED. |
| FAC 61G15-23.004. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |