Plan Review Notes
Plan Review Notes For Permit 20121077
Permit Number 20121077
Review Stop B
Sequence Number 5
Notes
Date Text
2022-12-27 16:46:34NEW SINGLE FAMILY RESIDENCE (R3) FIFTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121077
 839 4TH ST
  
 NOTE:
 ENGINEER OF RECORD TO PAY $4728.72 FEE OF FOUR TIMES
 THE AMOUNT OF THE PROPORTION OF THE PERMIT FEE
 ATTRIBUTED TO PLANS REVIEW (LAST REVIEW AND THIS ONE).
 FLORIDA STATUTE 553.80(2)(B
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
 ORIGINAL COMMENT:
 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 PREVIOUS COMMENT:
 3-ATTIC ACCESS WAS RELOCATED, BUT BASED ON THE ROOF
 FRAMING PLAN, THE LOCATION OF THE ATTIC ACCESS DOESN'T
 SEEM TO PROVIDE THE HEADROOM CLEARANCE REQUIRED BY SEC.
 R807 FBC-RESIDENTIAL. ATTIC ACCESS IS LOCATED BETWEEN
 TWO GABLE END ROOFS. ALSO, BASED ON SECTION 2 ON SHEET
 S-3, THERE IS A MASONRY WALL BETWEEN THE FRONT PART OF
 THE HOUSE AND THE REAR PART OF THE HOUSE. THEREFORE,
 THERE IS NOT ACCESS TO OTHER ROOF AREAS. EACH ROOF AREA
 NEEDS AN ATTIC ACCESS. REVISE AS REQUIRED.
  
 RESPONSE:
 ATTIC ACCESS WAS NOT REVISED ON THE ROOF FRAMING PLAN
 TO MATCH LOCATIONS SHOWN ON SHEET A-1.
 SEC. R807 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 6- BEAM SCHEDULE ON SHEET S-2 ONLY SPECIFIES B-1 BEAM.
 IT DOESN'T SPECIFY THE RAKE BEAM SHOWN ON SHEET S-4.
 REVISE AS REQUIRED TO CLARIFY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 PREVIOUS COMMENT:
 SECTION 2 ON SHEET S-3 SHOWS A MASONRY WALL BETWEEN THE
 FRONT PART OF THE HOUSE AND THE REAR PART OF THE HOUSE.
 ROOF FRAMING PLAN ON SHEET S-2 DOESN'T SPECIFY THE BEAM
 SUPPORTING THE MASONRY WALL.
 ROOF FRAMING PLAN DOESN'T SHOW HOW THE TWO REAR GABLE
 END ROOFS ARE SUPPORTED AT THE INTERSECTION OF BOTH
 ROOFS.
 FRONT PORCH WOOD BEAM SIZE AND ROOF RAFTERS SIZE
 SPECIFIED ON THE ROOF FRAMING PLAN AND WOOD BEAM
 SPECIFIED ON SECTION 2 ON SHEET S-3 DON'T MATCH.
 SECTION 2 ON SHEET S-3 SHOWS OUT LOOKERS IN THE MIDDLE
 MASONRY WALL. THE OUT LOOKERS ARE ON THE OTHER SIDE OF
 THE SECTION BY THE GABLE END AREA. REVISE/CLARIFY WALL
 SECTION AS REQUIRED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 A)ROOF FRAMING PLAN ON SHEET S2 SHOWS B-1 BEAM
 SUPPORTING THE MASONRY WALL AND RAKE BEAM RB-1.
 FOUNDATION PLAN WAS REVISED SHOWING COLUMN C1 AND
 FOOTING CF-16 IN THE MIDDLE OF THE FLOOR SLAB. ENGINEER
 TO CLARIFY WHY SPECIFYING A CONTINUOUS SPREAD FOOTING
 INSTEAD OF A CONCRETE PAD IF THE LOAD IS THE ECCENTRIC
 LOAD FROM THE COLUMN?. SEC. R301.1 FBC-RESIDENTIAL.
  
 B)FOUNDATION PLANS WAS ALSO REVISED SHOWING NEW C1
 COLUMNS ON THE PERIMETER WALL BUT THERE IS NOT COLUMN
 SUPPORTING BEAM B-1 ON THE LEFT HAND SIDE.
  
 C) SIZE OF BEAM B-1 SPECIFIED ON SECTION 2 OF SHEET S-3
 DOESN'T MATCH SIZE SPECIFIED ON THE BEAM SCHEDULE.
  
 D)NEW C1 COLUMN IS NOT SHOWN ON THE FLOOR PLAN ON SHEET
 A-1.
  
 E)BEAM SUPPORTING THE TWO GABLE END TRUSSES IS NOT
 SPECIFIED ON THE
 BEAM SCHEDULE.
  
 F)PORCH WOOD JOIST SIZE SPECIFIED ON SECTION 2 OF SHEET
 S-3 DOESN'T MATCH ROOF FRAMING PLAN.
  
  
 ORIGINAL COMMENT:
 7- PLANS DON'T PROVIDE SPECIFICATIONS FOR THE ROOF
 SHEATHING. SPECIFY TYPE, THICKNESS AND ROOF SHEATHING
 FASTENING AS REQUIRED BY SEC. R803.2.3.1
 FBC-RESIDENTIAL.
  
 PREVIOUS COMMENT:
 INFORMATION SHOWN ON THE TYPICAL WALL SECTION ON SHEET
 A-1 DOESN'T MATCH INFORMATION SHOWN ON OTHER PLANS AND
 SECTIONS. REVISE AS REQUIRED TO MATCH TO AVOID MORE
 CONFLICTS/DELAYS. ROOF SHEATHING SPECIFICATIONS DON'T
 MATCH SPECIFICATIONS SHOWN ON SHEET S-5. FOOTING SIZE
 DOESN'T MATCH FOUNDATION PLAN. ATTIC INSULATION DOESN'T
 MATCH. ETC.
 NOTE: ENGINEER TO COORDINATE ALL PLANS, SECTIONS AND
 SPECIFICATIONS TO AVOID MORE CONFLICTS AND DELAYS.
  
 RESPONSE:
 ROOF SHEATHING SPECIFICATIONS DON'T MATCH SECTION
 R803.2.3.1 FBC-RESIDENTIAL AND FIGURE R803.2.3.1
 FBC-RESIDENTIAL. NEED TO SPECIFY NAILS AT 4" O.C. ON
 ROOF ZONE #3 AND NEED TO SPECIFY RING SHANK NAILS. (OR
 PROVIDE CALCULATIONS SHOWING THAT 10D NAIL MATCHES OR
 EXCEEDS 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 FBC-RESIDENTIAL).
  
 ALSO, ROOF SHEATHING SPECIFICATIONS DON'T COMPLY WITH
 GABLE ROOF NAILING REQUIREMENTS OF FIGURE R803.2.3.1
 FBC-RESIDENTIAL. ROOF ZONE 3 IS 5 FEET NOT 48".
  
 ORIGINAL COMMENT:
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STEEL COLUMNS SHOWN ON THE FRONT PORCH. SPECIFY TOP AND
 BOTTOM CONNECTORS AND FURRING DETAILS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 PREVIOUS COMMENT:
 SECTION 2 ON SHEET S-3 SHOWS STEEL COLUMNS BELOW GRADE.
 THIS INFORMATION DOESN'T MATCH INFORMATION SHOWN ON THE
 FOUNDATION PLAN. FOUNDATION PLAN SHOWS A KNEE WALL.
 ALSO, THERE ARE NO DETAIL/SPECIFICATIONS SHOWING HOW
 THE STEEL COLUMNS AND CONNECTIONS ARE PROTECTED AGAINST
 RUST/DETERIORATION.
  
 RESPONSE:
 SECTION 2 ON SHEET S3 STILL DOESN'T MATCH FOUNDATION
 PLAN. IT DOESN'T SHOW THE KNEE WALL AND IT IS NOT CLEAR
 WHAT IS THE PURPOSE OF THE CONCRETE PEDESTAL. THE
 CONCRETE PEDESTAL IS COVERING THE STEEL COLUMN. WHY?.
 WHAT IS THE PURPOSE OF COVERING THE STEEL COLUMN WITH A
 PEDESTAL. ALSO NO SPECS FOR STEEL COLUMN, PLATE AND
 BOLTS PROTECTION FOR RUST.
  
 9-OK.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
  
 A)OK. ROOF SHINGLES FL31588-R2.
  
 PREVIOUS COMMENT:
 D)HARDIE BOARD SIDING.
 FLORIDA PRODUCT APPROVAL NUMBER UPLOADED TO PROJECTDOX
 DOESN'T MATCH FLORIDA PRODUCT APPROVAL NUMBER NAMED IN
 PROJECTDOX SUPPORTING DOCUMENTS. ONE OF THEM IS
 FL13223-R7 AND THE OTHER ONE IS FL13192.2. REVISE AS
 REQUIRED TO MATCH.
 NOTE: WHEN RESUBMITTING PLEASE UPLOAD THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND INSTALLATION
 INSTRUCTION ON THE SAME FILE. DON'T SPLIT THEM INTO TWO
 SEPARATE FILES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,