Plan Review Notes
Plan Review Notes For Permit 20121077
Permit Number 20121077
Review Stop B
Sequence Number 4
Notes
Date Text
2022-07-12 16:52:59NEW SINGLE FAMILY RESIDENCE (R3) FOURTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121077
  
  
 NOTE:
 ENGINEER OF RECORD TO PAY $2364.36 FEE OF FOUR TIMES
 THE AMOUNT OF THE PROPORTION OF THE PERMIT FEE
 ATTRIBUTED TO PLANS REVIEW.
 FLORIDA STATUTE 553.80(2)(B
  
  
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
  
 ORIGINAL COMMENT:
 2-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 A)DRAINAGE PLAN SHOWS A 6 INCH SWALE IMMEDIATELY
 ADJACENT TO THE EXISTING RESIDENCE #837. THE PROPOSED
 SWALE AFFECTS THE FOUNDATION. ENGINEER OF RECORD TO
 PROVIDE DETAILS SPECIFICATIONS SHOWING HOW PROTECTING
 THE FOOTING AS REQUIRED BY SEC. R401.3 BC-RESIDENTIAL.
  
 B)DRAINAGE PLAN SHOWS A PERMANENT TRENCH AND SILT FENCE
 TO CONTAIN THE SURFACE DRAINAGE. NEED TO APPLY FOR A
 SEPARATE FENCE PERMIT FOR ZONING APPROVAL. SEC. 105.1
 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 RESPONSE:
 ATTIC ACCESS WAS RELOCATED, BUT BASED ON THE ROOF
 FRAMING PLAN, THE LOCATION OF THE ATTIC ACCESS DOESN'T
 SEEM TO PROVIDE PROVIDE THE HEADROOM CLEARANCE REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL. ATTIC ACCESS IS LOCATED
 BETWEEN TWO GABLE END ROOFS. ALSO, BASED ON SECTION 2
 ON SHEET S-3, THERE IS A MASONRY WALL BETWEEN THE FRONT
 PART OF THE HOUSE AND THE REAR PART OF THE HOUSE.
 THEREFORE, THERE IS NOT ACCESS TO OTHER ROOF AREAS.
 EACH ROOF AREA NEEDS AN ATTIC ACCESS. REVISE AS
 REQUIRED.
  
 ORIGINAL COMMENT:
 6- BEAM SCHEDULE ON SHEET S-2 ONLY SPECIFIES B-1 BEAM.
 IT DOESN'T SPECIFY THE RAKE BEAM SHOWN ON SHEET S-4.
 REVISE AS REQUIRED TO CLARIFY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 SECTION 2 ON SHEET S-3 SHOWS A MASONRY WALL BETWEEN THE
 FRONT PART OF THE HOUSE AND THE REAR PART OF THE HOUSE.
 ROOF FRAMING PLAN ON SHEET S-2 DOESN'T SPECIFY THE BEAM
 SUPPORTING THE MASONRY WALL.
 ROOF FRAMING PLAN DOESN'T SHOW HOW THE TWO REAR GABLE
 END ROOFS ARE SUPPORTED AT THE INTERSECTION OF BOTH
 ROOFS.
 FRONT PORCH WOOD BEAM SIZE AND ROOF RAFTERS SIZE
 SPECIFIED ON THE ROOF FRAMING PLAN AND WOOD BEAM
 SPECIFIED ON SECTION 2 ON SHEET S-3 DON'T MATCH.
 SECTION 2 ON SHEET S-3 SHOWS OUTLOOKERS IN THE MIDDLE
 MASONRY WALL. THE OUTLOOKERS ARE ON THE OTHER SIDE OF
 THE SECTION BY THE GABLE END AREA. REVISE/CLARIFY WALL
 SECTION AS REQUIRED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 7- PLANS DON'T PROVIDE SPECIFICATIONS FOR THE ROOF
 SHEATHING. SPECIFY TYPE, THICKNESS AND ROOF SHEATHING
 FASTENING AS REQUIRED BY SEC. R803.2.3.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 INFORMATION SHOWN ON THE TYPICAL WALL SECTION ON SHEET
 A-1 DOESN'T MATCH INFORMATION SHOWN ON OTHER PLANS AND
 SECTIONS. REVISE AS REQUIRED TO MATCH TO AVOID MORE
 CONFLICTS/DELAYS. ROOF SHEATHING SPECIFICATIONS DON'T
 MATCH SPECIFICATIONS SHOWN ON SHEET S-5. FOOTING SIZE
 DOESN'T MATCH FOUNDATION PLAN. ATTIC INSULATION DOESN'T
 MATCH. ETC.
 NOTE: ENGINEER TO COORDINATE ALL PLANS, SECTIONS AND
 SPECIFICATIONS TO AVOID MORE CONFLICTS AND DELAYS.
  
 ORIGINAL COMMENT:
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STEEL COLUMNS SHOWN ON THE FRONT PORCH. SPECIFY TOP AND
 BOTTOM CONNECTORS AND FURRING DETAILS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 SECTION 2 ON SHEET S-3 SHOWS STEEL COLUMNS BELOW GRADE.
 THIS INFORMATION DOESN'T MATCH INFORMATION SHOWN ON THE
 FOUNDATION PLAN. FOUNDATION PLAN SHOWS A KNEE WALL.
 ALSO, THERE ARE NO DETAIL/SPECIFICATIONS SHOWING HOW
 THE STEEL COLUMNS AND CONNECTIONS ARE PROTECTED AGAINST
 RUST/DETERIORATION.
  
 ORIGINAL COMMENT:
 9- PROVIDE DOORS AND WINDOWS STRUCTURAL BUCK DETAIL.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 BUCK DETAIL ON SHEET A1 DOESN'T PROVIDE THE STRUCTURAL
 BUCK SPECIFICATIONS AS REQUESTED AND DOESN'T SEEM TO
 APPLY TO THIS JOB.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 A)OK. ROOF SHINGLES FL31588-R2.
  
 ORIGINAL COMMENT:
 D)HARDIEBOARD SIDING. INFORMATION SUBMITTED IS NOT A
 PRODUCT APPROVAL. NEED MIAMI DADE NOA OR COMPLETE
 FLORIDA PRODUCT APPROVAL.
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL NUMBER UPLOADED TO PROJECTDOX
 DOESN'T MATCH FLORIDA PRODUCT APPROVAL NUMBER NAMED IN
 PROJECTDOX SUPPORTING DOCUMENTS. ONE OF THEM IS
 FL13223-R7 AND THE OTHER ONE IS FL13192.2. REVISE AS
 REQUIRED TO MATCH.
 NOTE: WHEN RESUBMITTING PLEASE UPLOAD THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND INSTALLATION
 INSTRUCTION ON THE SAME FILE. DON'T SPLIT THEM INTO TWO
 SEPARATE FILES.
  
 ORIGINAL COMMENT:
 E) SINGLE HUNG WINDOWS. NEW COMMENT BASED ON REVISED
 PLANS. PROVIDE PRODUCT APPROVAL FOR SINGLE HUNG WINDOW
 SIZE SPECIFIED ON PLANS FO WINDOW A. NEW 72"W X 52"H
 SINGLE HUNG WINDOW.
  
 RESPONSE:
 REPEAT COMMENT. NOA SUBMITTED DOESN'T COVER 72" WIDE
 WINDOW. NEED TO PROVIDE PRODUCT APPROVAL THAT COVERS
 THIS WINDOW SIZE AS SPECIFIED ON PLANS.
  
 F) PROVIDE PRODUCT APPROVAL FOR SHINGLES UNDERLAYMENT
 SPECIFIED ON TYPICAL WALL SECTION ON SHEET A-1.
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 14- PROVIDE COMPLETE WALL SECTION FROM FOUNDATION
 THROUGH ROOF AS REQUIRED BY SEC. 107.5.3 CITY
 AMENDMENTS.
  
 RESPONSE:
 REVISE NEW TYPICAL WALL SECTION ON SHEET A1:
 A) FOOTING SIZE DOESN'T MATCH SIZE SPECIFIED ON THE
 FOUNDATION PLAN. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 C)ROOF SHEATHING NAILING SPECIFICATIONS ARE NOT CLEAR.
 NOTE: SEE SECTION R803.2.3.1 FBC-RESIDENTIAL AND FIGURE
 R803.2.3.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 ROOD SHEATHING SPECIFICATIONS ON TYPICAL WALL SECTION
 AND SPECIFICATIONS ON SHEET S-5 DON'T MATCH. REVISE AS
 REQUIRED TO MATCH. NOTE: SEE SECTION R803.2.3.1
 FBC-RESIDENTIAL AND FIGURE R803.2.3.1 FBC-RESIDENTIAL.
  
 D) ROOF INSULATION ON TYPICAL WALL SECTION AND
 SPECIFICATIONS ON SHEET S-3 DON'T MATCH. REVISE AS
 REQUIRED TO MATCH.
  
  
 ORIGINAL COMMENT:
 17- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE FRONT AND BACK GUARDRAILS SHOWING
 COMPLIANCE WITH SEC. R312.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. DESIGN INFORMATION NEEDS
 TO BE SHOWN ON PLANS BY THE DESIGNER OF RECORD. PRODUCT
 APPROVALS OR SHOP DRAWINGS ARE DEFERRED SUBMITTALS JUST
 TO CONFIRM THE DESIGN INTENT OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]