2021-02-17 13:22:11 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #20121077 |
| |
| 1-ENERGY CALCULATIONS SUBMITTED: |
| A) THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR |
| OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER |
| SHALL CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH |
| THE CODE, AS PER SECTION 553.907, FLORIDA STATUTES, |
| PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| RENOVATION AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| B) PROVIDE THE NAME OF THE PERSON DOING THE |
| CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY |
| CONSERVATION. |
| |
| C)PROVIDE CORRECT AND COMPLETE INFORMATION ON TOP OF |
| FORM. CORRECT ADDRESS IS 839 4TH STREET NOT 837 4TH |
| STREET. PROVIDE OWNER'S NAME. PROVIDE BUILDER'S NAME. |
| PERMITTING OFFICE IS WEST PALM BEACH NOT PALM BEACH. |
| REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| D)ITEM #8(A) ON PAGE 1 OF 4 SPECIFIES R-5 SLAB-ON-GRADE |
| EDGE INSULATION. PLANS DON'T SPECIFY ANY SLAB EDGE |
| INSULATION. REVISE AS REQUIRED TO MATCH. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| E)ITEM #9(A) ON PAGE 1 OF 4 SPECIFIES R-4.5 EXTERIOR |
| INSULATION ON CONCRETE BLOCK. PLANS DON'T SPECIFY |
| EXTERIOR INSULATION ON THE CONCRETE BLOCK. THE |
| INSULATION IS ON THE INTERIOR SIDE. SEE PLANS AND |
| REVISE AS REQUIRED TO MATCH, INCLUDING R-VALUE |
| SPECIFIED. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| F)ITEM #10(A) ON PAGE 1 OF 4 SPECIFIES R-19 UNDER ATTIC |
| INSULATION. THIS DOESN'T MATCH PLANS. SEE PLANS AND |
| REVISE AS REQUIRED TO MATCH, INCLUDING. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| G)ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 NEEDS TO BE |
| COORDINATED WITH PLANS. PLANS ARE NOT CLEAR ON WHAT |
| ROOFING MATERIAL IS GOING TO BE INSTALLED BUT IT |
| DOESN'T SPECIFY FLAT TILE OR SLATE. COORDINATE WITH |
| ENGINEER PLANS AND REVISE AS REQUIRED TO MATCH. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| H)REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. PLANS |
| DON'T SHOW ANY 1/300 VENT RATIO. TYPICALLY, THE RATIO |
| IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL. OR |
| PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE |
| COMPLETE DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH |
| THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC. |
| R806.2. NOTE: ENGINEER OF RECORD NEEDS TO |
| REVIEW/APPROVE THEM PRIOR TO SUBMITTAL. |
| |
| I)DOOR TYPE INFORMATION SPECIFIED ON PAGE 3 OF 4 IS |
| INCORRECT. ACCORDING TO PLANS AND PRODUCT APPROVALS |
| SUBMITTED THE ENTRY DOOR AND THE BEDROOM #3 DOORS ARE |
| ALUMINUM DOORS WITH GLAZING. GLASS IN THESE DOORS NEED |
| TO BE INCLUDED ON THE GLASS CALCULATIONS AS REQUIRED BY |
| SEC. R405.5.3.1 AND SEC. R405.5.3.3 FBC-ENERGY |
| CONSERVATION. REVISE AS REQUIRED. |
| |
| J)WINDOWS INFORMATION SPECIFIED ON 3 OF 4 DOESN'T MATCH |
| PLANS. REVISE THE WINDOW AREA AND WINDOW OVERHANG DEPTH |
| AND SEPARATION TO MATCH PLANS. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| 2-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| R401.3 FBC-RESIDENTIAL. |
| SEC. 107.2.5 CITY AMENDMENTS. |
| SEC. 110.9 CITY AMENDMENTS. |
| |
| 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING |
| COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. |
| |
| 4-PLANS SUBMITTED DON'T SPECIFY WHAT IS THE ROOFING |
| MATERIAL. IS IT SHINGLES?, TILE?. IF USING SHINGLES , |
| THEN A ROOF PITCH OF 2:12 TO LESS THAN 4:12 REQUIRES |
| TWO LAYERS OF UNDERLAYMENT AS REQUIRED BY SEC. R905.2.2 |
| FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS ON PLANS FOR |
| THE TWO LAYERS OF UNDERLAYMENT. ALSO, PROVIDE |
| SPECIFICATIONS FOR THE FLAT ROOF. |
| |
| 5- SPECIFY ROOF PITCH OF THE FLAT ROOF ON THE FRONT |
| PORCH. SEE SEC. R905.9.1 OR 905.11.1 FBC RESIDENTIAL. |
| |
| 6- BEAM SCHEDULE ON SHEET S-2 ONLY SPECIFIES B-1 BEAM. |
| IT DOESN'T SPECIFY THE RAKE BEAM SHOWN ON SHEET S-4. |
| REVISE AS REQUIRED TO CLARIFY. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 7- PLANS DON'T PROVIDE SPECIFICATIONS FOR THE ROOF |
| SHEATHING. SPECIFY TYPE, THICKNESS AND ROOF SHEATHING |
| FASTENING AS REQUIRED BY SEC. R803.2.3.1 |
| FBC-RESIDENTIAL. |
| |
| 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| STEEL COLUMNS SHOWN ON THE FRONT PORCH. SPECIFY TOP AND |
| BOTTOM CONNECTORS AND FURRING DETAILS. |
| SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 9- PROVIDE DOORS AND WINDOWS STRUCTURAL BUCK DETAIL. |
| NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO |
| THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 |
| FBC-RESIDENTIAL. |
| |
| 10- REVISE THE ADDRESS INFORMATION ON ALL DRAWINGS, |
| CALCULATIONS, ENERGY CALCULATIONS, ETC. SUBMITTED TO |
| AVOID CONFLICTS/DELAYS. THERE ARE TWO STRUCTURES IN |
| THIS LOT. 839 4TH STREET IS THE ADDRESS FOR THE REAR |
| STRUCTURE. THIS PERMIT APPLICATION IS FOR THE REAR |
| STRUCTURE ONLY. 837 4TH STREET IS THE MAIN HOUSE. THIS |
| WILL FACILITATE INSPECTIONS AND RECORDS KEEPING. |
| SEC. 107.2.1.3 CITY AMENDMENTS. |
| |
| 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL): |
| |
| A)ROOF MATERIAL FOR PITCHED ROOF AS SPECIFIED ON PLANS. |
| |
| B) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| |
| 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 13-VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS |
| UPDATED TO $120,957. THE PERMIT FEE BALANCE IS |
| $2456.00. |
| |
| 14- ENGINEER TO FOLLOW UP WITH THE FLORIDA BUILDING |
| CODE TRAINING REQUIREMENT. SEE BELOW: |
| |
| FLORIDA BUILDING CODE TRAINING FOR ENGINEERS(471.0195 |
| F.S.) |
| |
| 471.0195 FLORIDA BUILDING CODE TRAINING FOR ENGINEERS. |
| ALL LICENSEES ACTIVELY PARTICIPATING IN THE DESIGN OF |
| ENGINEERING WORKS OR SYSTEMS IN CONNECTION WITH |
| BUILDINGS, STRUCTURES, OR FACILITIES AND SYSTEMS |
| COVERED BY THE FLORIDA BUILDING CODE SHALL TAKE |
| CONTINUING EDUCATION COURSES AND SUBMIT PROOF TO THE |
| BOARD, AT SUCH TIMES AND IN SUCH MANNER AS ESTABLISHED |
| BY THE BOARD BY RULE, THAT THE LICENSEE HAS COMPLETED |
| ANY SPECIALIZED OR ADVANCED COURSES ON ANY PORTION OF |
| THE FLORIDA BUILDING CODE APPLICABLE TO THE LICENSEE'S |
| AREA OF PRACTICE. THE BOARD SHALL RECORD REPORTED |
| CONTINUING EDUCATION COURSES ON A SYSTEM EASILY |
| ACCESSED BY CODE ENFORCEMENT JURISDICTIONS FOR |
| EVALUATION WHEN DETERMINING LICENSE STATUS FOR PURPOSES |
| OF PROCESSING DESIGN DOCUMENTS. LOCAL JURISDICTIONS |
| SHALL BE RESPONSIBLE FOR NOTIFYING THE BOARD WHEN |
| DESIGN DOCUMENTS ARE SUBMITTED FOR BUILDING |
| CONSTRUCTION PERMITS BY PERSONS WHO ARE NOT IN |
| COMPLIANCE WITH THIS SECTION. THE BOARD SHALL TAKE |
| APPROPRIATE ACTION AS PROVIDED BY ITS RULES WHEN SUCH |
| NONCOMPLIANCE IS DETERMINED TO EXIST. |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |