2021-02-17 13:22:11NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121077
  
 1-ENERGY CALCULATIONS SUBMITTED:
 A) THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR
 OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER
 SHALL CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH
 THE CODE, AS PER SECTION 553.907, FLORIDA STATUTES,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 C)PROVIDE CORRECT AND COMPLETE INFORMATION ON TOP OF
 FORM. CORRECT ADDRESS IS 839 4TH STREET NOT 837 4TH
 STREET. PROVIDE OWNER'S NAME. PROVIDE BUILDER'S NAME.
 PERMITTING OFFICE IS WEST PALM BEACH NOT PALM BEACH.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 D)ITEM #8(A) ON PAGE 1 OF 4 SPECIFIES R-5 SLAB-ON-GRADE
 EDGE INSULATION. PLANS DON'T SPECIFY ANY SLAB EDGE
 INSULATION. REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)ITEM #9(A) ON PAGE 1 OF 4 SPECIFIES R-4.5 EXTERIOR
 INSULATION ON CONCRETE BLOCK. PLANS DON'T SPECIFY
 EXTERIOR INSULATION ON THE CONCRETE BLOCK. THE
 INSULATION IS ON THE INTERIOR SIDE. SEE PLANS AND
 REVISE AS REQUIRED TO MATCH, INCLUDING R-VALUE
 SPECIFIED.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 F)ITEM #10(A) ON PAGE 1 OF 4 SPECIFIES R-19 UNDER ATTIC
 INSULATION. THIS DOESN'T MATCH PLANS. SEE PLANS AND
 REVISE AS REQUIRED TO MATCH, INCLUDING.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 G)ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 NEEDS TO BE
 COORDINATED WITH PLANS. PLANS ARE NOT CLEAR ON WHAT
 ROOFING MATERIAL IS GOING TO BE INSTALLED BUT IT
 DOESN'T SPECIFY FLAT TILE OR SLATE. COORDINATE WITH
 ENGINEER PLANS AND REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 H)REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. PLANS
 DON'T SHOW ANY 1/300 VENT RATIO. TYPICALLY, THE RATIO
 IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL. OR
 PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. NOTE: ENGINEER OF RECORD NEEDS TO
 REVIEW/APPROVE THEM PRIOR TO SUBMITTAL.
  
 I)DOOR TYPE INFORMATION SPECIFIED ON PAGE 3 OF 4 IS
 INCORRECT. ACCORDING TO PLANS AND PRODUCT APPROVALS
 SUBMITTED THE ENTRY DOOR AND THE BEDROOM #3 DOORS ARE
 ALUMINUM DOORS WITH GLAZING. GLASS IN THESE DOORS NEED
 TO BE INCLUDED ON THE GLASS CALCULATIONS AS REQUIRED BY
 SEC. R405.5.3.1 AND SEC. R405.5.3.3 FBC-ENERGY
 CONSERVATION. REVISE AS REQUIRED.
  
 J)WINDOWS INFORMATION SPECIFIED ON 3 OF 4 DOESN'T MATCH
 PLANS. REVISE THE WINDOW AREA AND WINDOW OVERHANG DEPTH
 AND SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 2-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 4-PLANS SUBMITTED DON'T SPECIFY WHAT IS THE ROOFING
 MATERIAL. IS IT SHINGLES?, TILE?. IF USING SHINGLES ,
 THEN A ROOF PITCH OF 2:12 TO LESS THAN 4:12 REQUIRES
 TWO LAYERS OF UNDERLAYMENT AS REQUIRED BY SEC. R905.2.2
 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS ON PLANS FOR
 THE TWO LAYERS OF UNDERLAYMENT. ALSO, PROVIDE
 SPECIFICATIONS FOR THE FLAT ROOF.
  
 5- SPECIFY ROOF PITCH OF THE FLAT ROOF ON THE FRONT
 PORCH. SEE SEC. R905.9.1 OR 905.11.1 FBC RESIDENTIAL.
  
 6- BEAM SCHEDULE ON SHEET S-2 ONLY SPECIFIES B-1 BEAM.
 IT DOESN'T SPECIFY THE RAKE BEAM SHOWN ON SHEET S-4.
 REVISE AS REQUIRED TO CLARIFY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 7- PLANS DON'T PROVIDE SPECIFICATIONS FOR THE ROOF
 SHEATHING. SPECIFY TYPE, THICKNESS AND ROOF SHEATHING
 FASTENING AS REQUIRED BY SEC. R803.2.3.1
 FBC-RESIDENTIAL.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STEEL COLUMNS SHOWN ON THE FRONT PORCH. SPECIFY TOP AND
 BOTTOM CONNECTORS AND FURRING DETAILS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 9- PROVIDE DOORS AND WINDOWS STRUCTURAL BUCK DETAIL.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 10- REVISE THE ADDRESS INFORMATION ON ALL DRAWINGS,
 CALCULATIONS, ENERGY CALCULATIONS, ETC. SUBMITTED TO
 AVOID CONFLICTS/DELAYS. THERE ARE TWO STRUCTURES IN
 THIS LOT. 839 4TH STREET IS THE ADDRESS FOR THE REAR
 STRUCTURE. THIS PERMIT APPLICATION IS FOR THE REAR
 STRUCTURE ONLY. 837 4TH STREET IS THE MAIN HOUSE. THIS
 WILL FACILITATE INSPECTIONS AND RECORDS KEEPING.
 SEC. 107.2.1.3 CITY AMENDMENTS.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF MATERIAL FOR PITCHED ROOF AS SPECIFIED ON PLANS.
  
 B) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 13-VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS
 UPDATED TO $120,957. THE PERMIT FEE BALANCE IS
 $2456.00.
  
 14- ENGINEER TO FOLLOW UP WITH THE FLORIDA BUILDING
 CODE TRAINING REQUIREMENT. SEE BELOW:
  
 FLORIDA BUILDING CODE TRAINING FOR ENGINEERS(471.0195
 F.S.)
  
 471.0195 FLORIDA BUILDING CODE TRAINING FOR ENGINEERS.
 ALL LICENSEES ACTIVELY PARTICIPATING IN THE DESIGN OF
 ENGINEERING WORKS OR SYSTEMS IN CONNECTION WITH
 BUILDINGS, STRUCTURES, OR FACILITIES AND SYSTEMS
 COVERED BY THE FLORIDA BUILDING CODE SHALL TAKE
 CONTINUING EDUCATION COURSES AND SUBMIT PROOF TO THE
 BOARD, AT SUCH TIMES AND IN SUCH MANNER AS ESTABLISHED
 BY THE BOARD BY RULE, THAT THE LICENSEE HAS COMPLETED
 ANY SPECIALIZED OR ADVANCED COURSES ON ANY PORTION OF
 THE FLORIDA BUILDING CODE APPLICABLE TO THE LICENSEE'S
 AREA OF PRACTICE. THE BOARD SHALL RECORD REPORTED
 CONTINUING EDUCATION COURSES ON A SYSTEM EASILY
 ACCESSED BY CODE ENFORCEMENT JURISDICTIONS FOR
 EVALUATION WHEN DETERMINING LICENSE STATUS FOR PURPOSES
 OF PROCESSING DESIGN DOCUMENTS. LOCAL JURISDICTIONS
 SHALL BE RESPONSIBLE FOR NOTIFYING THE BOARD WHEN
 DESIGN DOCUMENTS ARE SUBMITTED FOR BUILDING
 CONSTRUCTION PERMITS BY PERSONS WHO ARE NOT IN
 COMPLIANCE WITH THIS SECTION. THE BOARD SHALL TAKE
 APPROPRIATE ACTION AS PROVIDED BY ITS RULES WHEN SUCH
 NONCOMPLIANCE IS DETERMINED TO EXIST.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  