Plan Review Notes
Plan Review Notes For Permit 20120986
Permit Number 20120986
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-21 06:58:421) PROVIDE AN ENLARGED FLOOR PLAN FOR THE NEW HANDIAP
 ACCESSIBLE TOILET ROOM # 526. SHOW THE INSIDE CLEAR
 DIMENSIONS (L X W) OF THE TOILET ROOM AND THE LENGTH
 AND WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACES FOR THE
 LAVATORY AND THE WATER CLOSET. WPB AND. TO FBC SEC.
 107.2.1.
 2) SHT. AE 101 - SHOW THE REQUIRED CLEAR FLOOR SPACE
 AND KNEE AND TOE CLEARANCES FOR THE BREAK ROOM SINK.
 SHOW THE DIMENSIONS OF THE CLEAR FLOOR SPACE. COMPLY
 WITH FBC-ACCESS. SEC. 305, 306, 606.2.
 3) SHT. AE 101 SHOWS TWO SETS OF EXAM ROOMS LABELED #5,
 6,& 7. CLARIFY.
 4) SHT. AE 502 SHOWS GRAB BARS IN A VERTICAL POSITION.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION
 PER HE FBC-ACCESS. SEC. 609.4. TTHERE IS NO EXCEPTION
 ALLOWING FOR GRAB BARS TO BE INSTALLED IN A VERTICAL
 POSITION.
 5) SHT. AE 502 - REAR WALL DETAIL. THE MAXIMUM HEIGHT
 OF THE SANITARY NAPKIN DISPOSAL OPERABLE PART SHALL BE
 LOCATED A MAXIMUM OF 48 INCHES ABOVE THE FINISH FLOOR
 PER FBC-ACCESS. SECS.308 & 309.SSHOW THIS ON THE
 DETAIL.
 6) SHT. AE 502 - TOILET FIXTURES AND ACCESSORIES DETAIL
 - THE PAPER TOWEL DISPENSER OUTLET FOR THE PAPER TOWELS
 SHALL BE LOCATED A MAXIMUM OF 48 INCHES ABOVE THE
 FINISH FLOOR. THE DETAIL SHOWS THE PAPER TOWEL OUTLET
 ABOVE THIS MAXIMUM HEIGHT. FBC -ACCESS. SECS.308 & 309.
 7) SHT. AE 502 - GENERAL SHEET NOTES #4,5, & 6 REFER TO
 THE ANSI A117.1 & THE ADA. THE GOVERNING STANDARD FOR
 HANDICAP ACCESSIBILITY IN THE STATE OF FLORIDA IS THE
 FLORIDA BUILDING CODE - ACCESSIBILITY VOLUME. EITHER
 REVISE THE NOTES TO REFLECT THE FBC OR DELETE THE
 NOTES.
 8) SHT. AE 701 - INTERIORS- ROOM FINISH SCHEDULE SHOWS
 THE WALLS IN THE TOILET ROOM # 526 AS PAINT. WALLS AND
 PARTITIONS WITHIN TWO FEET OF WATER CLOSETS SHALL HAVE
 A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OFF
 NOT LESS THAN 4 FEET ABOVE THE FLOOR,AND THE MATERIALS
 USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE PER FBC-BUILDING SEC.
 1210.2.2. EPOXY PAINT DOES NOT MEET THE INTENT OF THIS
 CODE SECTION.
 9) SUBMIT FIRESTOPPING DETAILS FOR ANY PIPE
 PENETRATIONS THROUGH RATED FLOOR AND WALL ASSEMBLIES
 PER FBC -BUILDING SECS. 714.3 & 714.4.
 10) SHT. P002 - PLUMBING SPECIFICATIONS - (C) - PIPE &
 FITTINGS (2) - DOMESTIC WATER NOTE # ( B) - PVC IS NOT
 PERMITTED INSIDE THE BUILDING OR WATER DISTRIBUTION PER
 FBC-PLUMBING SEC.605.4 AND TABLE 605.4.
 11) TEMPERED WATER IS REQUIREED AT THE LAVATORY IN THE
 ACCESSIBLE TOILET ROOM PER FBC-PLUMBING SEC.416.5. THE
 WATER- TEMPERATURE LIMITING DEVICE SHALL COMPLY WITH
 ASSE 1070OR CSA B125.33.
 12) SHUTOFF VALVES ARE REQUIRED ON THE WATER SSUPPLY
 DROPS TO THE TOILET RROOM, BREAK ROOM SINK AND THE SINK
 IN THE WORK AREA.FBC-PLUMBING SEC.606.1, 06.2..
 13) THE BRANCH VENT FOR THE PLUMBING FIXTURES APPEARS
 TO XCEED 40 FET IN DEVELOPED LENGTH. VENNTS EXCEEDING
 40 FEET IN DEVELOPED LENGTH SHALL B INCREASED BY ONE
 NOMINAL PIPE SIZE OR THE ENNTIRE DEVELOPED LENGTH OF
 THHE VVENT PIPE PER FBC-PLUMBING SEC.906.2.
 14) SHT. P101 - KEYNOTE #1 - CALLS OUT AN 1 1/2 INCH
 COLD WATER LINE BUT THERE IS NO SUCH SIZED WATER LLINE
 SHOWN ON SHT. P901.
 15) PLANS SHALL DIGITALLY SIGNED AND SEALED PER FL.
 ADMIN. CODE RULE 61G1-16.005, 61G15-23.004,
 61G15-23.005.
  