2021-01-20 12:20:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 OUTLETS IN EXAM ROOM TO BE WIRED PER 517.13
  
 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL
 EQUIPMENT IN PATIENT CARE SPACES. WIRING IN PATIENT
 CARE SPACES SHALL COMPLY WITH 517.13(A) AND (B). (A)
 WIRING METHODS. ALL BRANCH CIRCUITS SERVING PATIENT
 CARE SPACES SHALL BE PROVIDED WITH AN EFFECTIVE
 GROUND-FAULT CURRENT PATH BY INSTALLATION IN A METAL
 RACEWAY SYSTEM OR A CABLE HAVING A METALLIC ARMOR OR
 SHEATH ASSEMBLY. THE METAL RACEWAY SYSTEM, METALLIC
 CABLE ARMOR, OR SHEATH ASSEMBLY SHALL ITSELF QUALIFY AS
 AN EQUIPMENT GROUNDING CONDUCTOR IN ACCORDANCE WITH
 250.118. (B) INSULATED EQUIPMENT GROUNDING CONDUCTORS
 AND INSULATED EQUIPMENT BONDING JUMPERS. (1) GENERAL.
 THE FOLLOWING SHALL BE DIRECTLY CONNECTED TO AN
 INSULATED COPPER EQUIPMENT GROUNDING CONDUCTOR THAT IS
 CLEARLY IDENTIFIED ALONG ITS ENTIRE LENGTH BY GREEN
 INSULATION AND INSTALLED WITH THE BRANCH CIRCUIT
 CONDUCTORS IN THE WIRING METHODS AS PROVIDED IN
 517.13(A): (1) THE GROUNDING TERMINALS OF ALL
 RECEPTACLES OTHER THAN ISOLATED GROUND RECEPTACLES (2)
 METAL OUTLET BOXES, METAL DEVICE BOXES, OR METAL
 ENCLOSURES (3) ALL NON?CURRENT-CARRYING CONDUCTIVE
 SURFACES OF FIXED ELECTRICAL EQUIPMENT LIKELY TO BECOME
 ENERGIZED THAT ARE SUBJECT TO PERSONAL CONTACT,
 OPERATING AT OVER 100 VOLTS