Plan Review Notes For Permit 20120984 |
Permit Number |
20120984 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-12-29 10:16:33 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | REVIEW STATUS: FAILED. | | | | 1) SCOPE OF WORK IS NOT CLEAR. APPLICATION MENTIONS | | DEMOLITION WORK, BUT ELECTRICAL DRAWINGS E-105 AND | | E-205 SEEM TO INDICATE NEW ELECTRICAL WORK IS BEING | | DONE. PLEASE CLARIFY SOW AND PROVIDE NOTES ON DRAWINGS | | SHOWING WHAT IS NEW, EXISTING TO REMAIN, EXISTING TO BE | | REMOVED. FBC 107 | | 2) RISER DIAGRAM AND PANEL SCHEDULES: PLEASE PROVIDE | | PANEL SCHEDULE FOR LP1 AND SHOW PANEL H ON RISER | | DIAGRAM. FBC 107 | | 3) ELECTRICAL SUB PERMIT IS REQUIRED FBC 107 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SINCERELY, | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|