Plan Review Notes
Plan Review Notes For Permit 20120984
Permit Number 20120984
Review Stop E
Sequence Number 1
Notes
Date Text
2020-12-29 10:16:33CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) SCOPE OF WORK IS NOT CLEAR. APPLICATION MENTIONS
 DEMOLITION WORK, BUT ELECTRICAL DRAWINGS E-105 AND
 E-205 SEEM TO INDICATE NEW ELECTRICAL WORK IS BEING
 DONE. PLEASE CLARIFY SOW AND PROVIDE NOTES ON DRAWINGS
 SHOWING WHAT IS NEW, EXISTING TO REMAIN, EXISTING TO BE
 REMOVED. FBC 107
 2) RISER DIAGRAM AND PANEL SCHEDULES: PLEASE PROVIDE
 PANEL SCHEDULE FOR LP1 AND SHOW PANEL H ON RISER
 DIAGRAM. FBC 107
 3) ELECTRICAL SUB PERMIT IS REQUIRED FBC 107
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved