2021-04-12 10:15:38 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20120907 |
| ADD: 6910 S. DIXIE HWY. |
| CONT: BANDES CONSTRUCTION |
| TEL: 727-733-5558 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 FBC-BUILDING AMBULATORY SURGICAL CENTERS SECTION |
| 451.1.3. THE FLORIDA BUILDING CODE, EXISTING BUILDING |
| SECTION 101.2. SCOPE EXEMPTS STATE LICENSED FACILITIES |
| SUCH AS AMBULATORY SURGICAL CENTERS FROM COMPLIANCE |
| WITH THAT CODE. THIS MEANS THAT EVERYTHING TO BE |
| REVIEWED IS AS NEW CONSTRUCTION. |
| |
| 4TH REVIEW |
| DATE: MON. APRIL 12TH/ 2021 |
| ACTION: DENIED |
| |
| 1) PREVIOUS 3RD REVIEW. SITE PLAN. PLEASE SEE ZONING |
| COMMENTS THAT THE ZONING SITE PLAN APPROVAL HAS NOT |
| BEEN APPROVED NOR THE RIGHT-OF-WAY ABANDONMENT. |
| THE SITE PLAN SUBMITTED ON 2/17 DOES NOT SHOW THE CITY |
| DOUBLE LINE DETAIL. 2017 ACCESSIBILITY CODE SECTION |
| 502.2 VEHICLE SPACES. EACH PARKING SPACE MUST BE AT |
| LEAST 12 FEET WIDE, SHALL BE MARKED TO DEFINE THE |
| WIDTH, AND SHALL HAVE AN ADJACENT ACCESS AISLE |
| COMPLYING WITH 502.3. |
| ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR |
| OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT |
| MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485 |
| ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL |
| PAINTING. |
| |
| |
| 1A)) COMPLIED. |
| |
| 1B) 4TH REVIEW, REPEAT FROM THE 1ST ROUND OF COMMENTS. |
| THE NEW PROPOSED SHEET A1.1 VERSION 3 VERSES VERSION 4, |
| BOTH SHOW AT LEAST ONE COMMON SPACE BEFORE THE COVERED |
| ENTRY. THE COMMON PARKING SPACE IS BEING SWITCHED TO |
| EITHER SIDE OF THE COVERED ENTRY. THE 3 ACCESSIBLE |
| PARKING STALLS ARE TO BE THE CLOSEST STALLS TO THE |
| FRONT ENTRY. PLEASE REVIEW IN THE 2017 ACCESSIBILITY |
| CODE 208.3.1. LOCATION. PARKING SPACES COMPLYING WITH |
| 502 THAT SERVE A PARTICULAR BUILDING OR FACILITY SHALL |
| BE ON THE SHORTEST ACCESSIBLE ROUTE FROM PARKING TO AN |
| ENTRANCE COMPLYING WITH 206.4. ALL PLANS RELEVANT TO |
| THIS COMMENT NEED TO MATCH IN THE LAYOUT, SHEETS |
| PRELIMINARY ENGINEERING SHEET, SURVEY AND PGU-1 PAVING |
| GRADING & UTILITIES. |
| |
| PLEASE NOTE SHOW COMPLIANCE WITH THE 2017 ACCESSIBILITY |
| CODE SECTION 208.3.1 PARKING SPACES COMPLYING WITH 502 |
| THAT SERVE A PARTICULAR BUILDING OR FACILITY SHALL BE |
| LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM THE |
| PARKING TO AN ACCESSIBLE ENTRANCE COMPLYING WITH 206.4. |
| |
| 1C) 4TH REVIEW CYCLE. SHEET A1.1 SHOWS WITH REVISION # |
| 3 NEW STATEMENT THE RECONFIGURED 9X16 TYPICAL PARKING |
| STALL BOX TYPE 4 INCH WHITE LINE SEE CIVIL FOR DETAILS. |
| AGAIN IF THE CIVIL PLANS ARE NOT IN THIS SET OF PLANS |
| WE NEED TO SEE THE DETAIL ON THIS SHEET. THERE IS NO |
| MENTION OF 12 INCHES BETWEEN THE DOUBLE 4 INCH WIDE |
| LINES. THE OTHER ISSUE IS NOT SUCH AS AN ACCESSIBLE |
| PARKING CONCERN BUT IS FOUND IN THE CITY MUNI-CODE |
| UNDER 94-485(N) OFF STREET PARKING DIMENSIONS. THE |
| STALL LENGTH IS 18 FEET IN LENGTH, SMALL CARS SPACES 16 |
| FEET IN LENGTH. |
| |
| 3RD REQUEST. 1ST REQUEST. 2017 ACCESSIBILITY CODE |
| SECTION 502.2 VEHICLE SPACES. EACH PARKING SPACE MUST |
| BE AT LEAST 12 FEET WIDE, SHALL BE MARKED TO DEFINE THE |
| WIDTH, AND SHALL HAVE AN ADJACENT ACCESS AISLE |
| COMPLYING WITH 502.3. |
| ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR |
| OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT |
| MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485 |
| ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL |
| PAINTING. |
| |
| 1D) SEMI-COMPLIED. THE ACCESSIBLE PARKING SPACE JUST |
| NORTH OF THE COVERED ENTRY IS NOT THE CLOSEST PARKING |
| SPACE TO THE COVERED ENTRY. SECTION 208.3.1 PARKING |
| SPACES COMPLYING WITH 502 THAT SERVE A PARTICULAR |
| BUILDING OR FACILITY SHALL BE LOCATED ON THE SHORTEST |
| ACCESSIBLE ROUTE FROM THE PARKING TO AN ACCESSIBLE |
| ENTRANCE COMPLYING WITH 206.4. |
| 3RD REQUEST. THE ACCESSIBLE PARKING STALLS TO THE NORTH |
| DO NOT SHOW ANY WORK BEING COMPLETED. THE ACCESSIBLE 2 |
| STALLS TO THE SOUTH DO SHOW NEW ELEVATIONS THAT EXCESS |
| THE 1:48. |
| PLEASE SHOW COMPLIANCE WITH SECTION 502.4 OF THE 2017 |
| FBC-ACCESSIBILITY CODE. PARKING SPACES AND ACCESS |
| AISLES SERVING THEM SHALL COMPLY WITH 302. ACCESS |
| AISLES SHALL BE AT THE SAME LEVEL AS THE PARKING SPACES |
| THEY SERVE. CHANGES IN LEVEL ARE NOT PERMITTED. |
| EXCEPTION: SLOPES NOT STEEPER THAN 1:48 SHALL BE |
| PERMITTED. |
| |
| 1E) 4TH REVIEW. TO DATE THERE HAS BEEN NO PAPERWORK |
| FROM THE CITY SHOWING THE RIGHT OF WAY ABANDONED. |
| WORK IN PROGRESS FOR THE ABANDONMENT OF RIGHT OF WAY. |
| PLEASE SUBMIT A SURVEY WITH THE CURRENT BUILDING |
| LOCATION AND PROPOSED ADDITION. PALM BEACH COUNTY |
| PROPERTY APPRAISERS OFFICE SHOWS WHAT APPEARS TO BE A |
| RIGHT OF WAY BEHIND THE BUILDING THAT SEPARATES THE |
| REMAINDER OF THE LOT TO THE EAST OF THIS RIGHT OF WAY. |
| THE ADDITION MAY TRANSGRESS THE PROPERTY LINE. 2017 |
| FBC-B TABLE 602. PLEASE PROVIDE THE DISTANCE FROM THE |
| NEW PROPOSED ADDITION TO THIS RIGHT OF WAY. THE |
| GENERATOR AND PAD AS WELL AS THE NEW CHILLER AND |
| CONCRETE PAD MAYBE IN THE RIGHT OF WAY. |
| |
| 2) 4TH REVIEW . TO DATE THERE HAS BEEN NO PAPERWORK |
| FROM THE CITY SHOWING THE RIGHT OF WAY ABANDONED. |
| WORK IN PROGRESS FOR THE ABANDONMENT OF RIGHT OF WAY. |
| YOU MAY HAVE SUBMITTED A SURVEY TO ZONING DIVISION BUT |
| THIS IS THE BUILDING DIVISION THAT REQUEST A CURRENT |
| SURVEY TO KEEP WITH THIS PERMIT SET OF PLANS TO SHOW |
| CODE COMPLIANCE WITH THE 2017 FBC-B TABLE 602 AND TABLE |
| 705.8 THAT THE BUILDING AND OPENINGS ARE NOT |
| TRANSGRESSING THE PROPERTY LINES AND ALLOWABLE |
| OPENINGS. |
| 1ST ROUND OF COMMENTS. THE DEMOLITION PLAN STATES |
| REMOVAL OF ALL INTERIOR PARTITION WALLS. THEE SHEET |
| A3.1 THE DIMENSION PLAN IS MISSING A LOT OF INTERIOR |
| DIMENSIONS THAT WILL BE NEEDED TO KNOW WHERE TO PLACE |
| WALL LINES. SOME EXAMPLES ARE THE EAST WEST LINES OF |
| THE ENTRY VESTIBULE, CLINIC WAITING, HALL 108, MANAGERS |
| OFFICE, STAFF LOCKER ROOM, STAFF HANDICAPPED SHOWER, |
| ETC. ADDITIONAL INFORMATION REQUIRED. 107.2.1.2. |
| |
| 3) BUILDING PROVISO: THE SECONDARY (EMERGENCY) OVERFLOW |
| DRAINAGE SYSTEM IS TO BE AN INDEPENDENT SYSTEM FROM THE |
| MAIN ROOF DRAINAGE SYSTEM IN COMPLIANCE WITH THE 2017 |
| FBC-B SECTION 1503.4.1. THE INSTALLATION AND SIZING OF |
| THE SECONDARY EMERGENCY OVERFLOW OVERFLOW SHALL COMPLY |
| WITH SECTIONS 1106 & 1107 OF THE FLORIDA BUILDING CODE. |
| PLUMBING CHAPTER 11. 04/12/2021. J. W. |
| |
| 4-5) COMPLIED. |
| |
| 6) BUILDING PROVISO: THE ARCHITECTURAL AND STRUCTURAL |
| SHEETS SHOW THE INSTALLATION OF STEEL COLUMNS, BEAMS, |
| BAR JOIST AND METAL ROOF DECKING. WELDED OR BOLTED |
| CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE |
| WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF |
| FRAMING INSPECTION. |
| 2017 FBC-B 2204.1 WELDING. |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2. QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| AT 561-805-6666. |
| |
| 7A) BUILDING PROVISO/ DEFERRED SUBMITTALS: |
| PLEASE PROVIDE PRODUCT APPROVALS FOR COMPONENTS AND |
| CLADDING. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, |
| |
| 7B) BUILDING PROVISO/ DEFERRED SUBMITTALS: |
| W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 7C) ) BUILDING PROVISO/ DEFERRED SUBMITTALS: |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 7D) BUILDING PROVISO/ DEFERRED SUBMITTALS: |
| FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 8) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE |
| REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA |
| PROJECT DOX UPON NOTIFICATION BY THIS OFFICE. |
| NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL |
| FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT |
| (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT |
| FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE |
| FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN |
| BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT |
| ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO [email protected] . |
| |
| 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |