2021-04-12 10:15:38WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120907
 ADD: 6910 S. DIXIE HWY.
 CONT: BANDES CONSTRUCTION
 TEL: 727-733-5558
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 FBC-BUILDING AMBULATORY SURGICAL CENTERS SECTION
 451.1.3. THE FLORIDA BUILDING CODE, EXISTING BUILDING
 SECTION 101.2. SCOPE EXEMPTS STATE LICENSED FACILITIES
 SUCH AS AMBULATORY SURGICAL CENTERS FROM COMPLIANCE
 WITH THAT CODE. THIS MEANS THAT EVERYTHING TO BE
 REVIEWED IS AS NEW CONSTRUCTION.
  
 4TH REVIEW
 DATE: MON. APRIL 12TH/ 2021
 ACTION: DENIED
  
 1) PREVIOUS 3RD REVIEW. SITE PLAN. PLEASE SEE ZONING
 COMMENTS THAT THE ZONING SITE PLAN APPROVAL HAS NOT
 BEEN APPROVED NOR THE RIGHT-OF-WAY ABANDONMENT.
 THE SITE PLAN SUBMITTED ON 2/17 DOES NOT SHOW THE CITY
 DOUBLE LINE DETAIL. 2017 ACCESSIBILITY CODE SECTION
 502.2 VEHICLE SPACES. EACH PARKING SPACE MUST BE AT
 LEAST 12 FEET WIDE, SHALL BE MARKED TO DEFINE THE
 WIDTH, AND SHALL HAVE AN ADJACENT ACCESS AISLE
 COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
  
 1A)) COMPLIED.
  
 1B) 4TH REVIEW, REPEAT FROM THE 1ST ROUND OF COMMENTS.
 THE NEW PROPOSED SHEET A1.1 VERSION 3 VERSES VERSION 4,
 BOTH SHOW AT LEAST ONE COMMON SPACE BEFORE THE COVERED
 ENTRY. THE COMMON PARKING SPACE IS BEING SWITCHED TO
 EITHER SIDE OF THE COVERED ENTRY. THE 3 ACCESSIBLE
 PARKING STALLS ARE TO BE THE CLOSEST STALLS TO THE
 FRONT ENTRY. PLEASE REVIEW IN THE 2017 ACCESSIBILITY
 CODE 208.3.1. LOCATION. PARKING SPACES COMPLYING WITH
 502 THAT SERVE A PARTICULAR BUILDING OR FACILITY SHALL
 BE ON THE SHORTEST ACCESSIBLE ROUTE FROM PARKING TO AN
 ENTRANCE COMPLYING WITH 206.4. ALL PLANS RELEVANT TO
 THIS COMMENT NEED TO MATCH IN THE LAYOUT, SHEETS
 PRELIMINARY ENGINEERING SHEET, SURVEY AND PGU-1 PAVING
 GRADING & UTILITIES.
  
 PLEASE NOTE SHOW COMPLIANCE WITH THE 2017 ACCESSIBILITY
 CODE SECTION 208.3.1 PARKING SPACES COMPLYING WITH 502
 THAT SERVE A PARTICULAR BUILDING OR FACILITY SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM THE
 PARKING TO AN ACCESSIBLE ENTRANCE COMPLYING WITH 206.4.
  
 1C) 4TH REVIEW CYCLE. SHEET A1.1 SHOWS WITH REVISION #
 3 NEW STATEMENT THE RECONFIGURED 9X16 TYPICAL PARKING
 STALL BOX TYPE 4 INCH WHITE LINE SEE CIVIL FOR DETAILS.
 AGAIN IF THE CIVIL PLANS ARE NOT IN THIS SET OF PLANS
 WE NEED TO SEE THE DETAIL ON THIS SHEET. THERE IS NO
 MENTION OF 12 INCHES BETWEEN THE DOUBLE 4 INCH WIDE
 LINES. THE OTHER ISSUE IS NOT SUCH AS AN ACCESSIBLE
 PARKING CONCERN BUT IS FOUND IN THE CITY MUNI-CODE
 UNDER 94-485(N) OFF STREET PARKING DIMENSIONS. THE
 STALL LENGTH IS 18 FEET IN LENGTH, SMALL CARS SPACES 16
 FEET IN LENGTH.
  
 3RD REQUEST. 1ST REQUEST. 2017 ACCESSIBILITY CODE
 SECTION 502.2 VEHICLE SPACES. EACH PARKING SPACE MUST
 BE AT LEAST 12 FEET WIDE, SHALL BE MARKED TO DEFINE THE
 WIDTH, AND SHALL HAVE AN ADJACENT ACCESS AISLE
 COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 1D) SEMI-COMPLIED. THE ACCESSIBLE PARKING SPACE JUST
 NORTH OF THE COVERED ENTRY IS NOT THE CLOSEST PARKING
 SPACE TO THE COVERED ENTRY. SECTION 208.3.1 PARKING
 SPACES COMPLYING WITH 502 THAT SERVE A PARTICULAR
 BUILDING OR FACILITY SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE FROM THE PARKING TO AN ACCESSIBLE
 ENTRANCE COMPLYING WITH 206.4.
 3RD REQUEST. THE ACCESSIBLE PARKING STALLS TO THE NORTH
 DO NOT SHOW ANY WORK BEING COMPLETED. THE ACCESSIBLE 2
 STALLS TO THE SOUTH DO SHOW NEW ELEVATIONS THAT EXCESS
 THE 1:48.
 PLEASE SHOW COMPLIANCE WITH SECTION 502.4 OF THE 2017
 FBC-ACCESSIBILITY CODE. PARKING SPACES AND ACCESS
 AISLES SERVING THEM SHALL COMPLY WITH 302. ACCESS
 AISLES SHALL BE AT THE SAME LEVEL AS THE PARKING SPACES
 THEY SERVE. CHANGES IN LEVEL ARE NOT PERMITTED.
 EXCEPTION: SLOPES NOT STEEPER THAN 1:48 SHALL BE
 PERMITTED.
  
 1E) 4TH REVIEW. TO DATE THERE HAS BEEN NO PAPERWORK
 FROM THE CITY SHOWING THE RIGHT OF WAY ABANDONED.
 WORK IN PROGRESS FOR THE ABANDONMENT OF RIGHT OF WAY.
 PLEASE SUBMIT A SURVEY WITH THE CURRENT BUILDING
 LOCATION AND PROPOSED ADDITION. PALM BEACH COUNTY
 PROPERTY APPRAISERS OFFICE SHOWS WHAT APPEARS TO BE A
 RIGHT OF WAY BEHIND THE BUILDING THAT SEPARATES THE
 REMAINDER OF THE LOT TO THE EAST OF THIS RIGHT OF WAY.
 THE ADDITION MAY TRANSGRESS THE PROPERTY LINE. 2017
 FBC-B TABLE 602. PLEASE PROVIDE THE DISTANCE FROM THE
 NEW PROPOSED ADDITION TO THIS RIGHT OF WAY. THE
 GENERATOR AND PAD AS WELL AS THE NEW CHILLER AND
 CONCRETE PAD MAYBE IN THE RIGHT OF WAY.
  
 2) 4TH REVIEW . TO DATE THERE HAS BEEN NO PAPERWORK
 FROM THE CITY SHOWING THE RIGHT OF WAY ABANDONED.
 WORK IN PROGRESS FOR THE ABANDONMENT OF RIGHT OF WAY.
 YOU MAY HAVE SUBMITTED A SURVEY TO ZONING DIVISION BUT
 THIS IS THE BUILDING DIVISION THAT REQUEST A CURRENT
 SURVEY TO KEEP WITH THIS PERMIT SET OF PLANS TO SHOW
 CODE COMPLIANCE WITH THE 2017 FBC-B TABLE 602 AND TABLE
 705.8 THAT THE BUILDING AND OPENINGS ARE NOT
 TRANSGRESSING THE PROPERTY LINES AND ALLOWABLE
 OPENINGS.
 1ST ROUND OF COMMENTS. THE DEMOLITION PLAN STATES
 REMOVAL OF ALL INTERIOR PARTITION WALLS. THEE SHEET
 A3.1 THE DIMENSION PLAN IS MISSING A LOT OF INTERIOR
 DIMENSIONS THAT WILL BE NEEDED TO KNOW WHERE TO PLACE
 WALL LINES. SOME EXAMPLES ARE THE EAST WEST LINES OF
 THE ENTRY VESTIBULE, CLINIC WAITING, HALL 108, MANAGERS
 OFFICE, STAFF LOCKER ROOM, STAFF HANDICAPPED SHOWER,
 ETC. ADDITIONAL INFORMATION REQUIRED. 107.2.1.2.
  
 3) BUILDING PROVISO: THE SECONDARY (EMERGENCY) OVERFLOW
 DRAINAGE SYSTEM IS TO BE AN INDEPENDENT SYSTEM FROM THE
 MAIN ROOF DRAINAGE SYSTEM IN COMPLIANCE WITH THE 2017
 FBC-B SECTION 1503.4.1. THE INSTALLATION AND SIZING OF
 THE SECONDARY EMERGENCY OVERFLOW OVERFLOW SHALL COMPLY
 WITH SECTIONS 1106 & 1107 OF THE FLORIDA BUILDING CODE.
 PLUMBING CHAPTER 11. 04/12/2021. J. W.
  
 4-5) COMPLIED.
  
 6) BUILDING PROVISO: THE ARCHITECTURAL AND STRUCTURAL
 SHEETS SHOW THE INSTALLATION OF STEEL COLUMNS, BEAMS,
 BAR JOIST AND METAL ROOF DECKING. WELDED OR BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING.
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 7A) BUILDING PROVISO/ DEFERRED SUBMITTALS:
 PLEASE PROVIDE PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
 (D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 7B) BUILDING PROVISO/ DEFERRED SUBMITTALS:
 W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7C) ) BUILDING PROVISO/ DEFERRED SUBMITTALS:
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7D) BUILDING PROVISO/ DEFERRED SUBMITTALS:
 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 8) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved