2021-02-19 14:36:25 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20120907 |
| ADD: 6910 S. DIXIE HWY. |
| CONT: BANDES CONSTRUCTION |
| TEL: 727-733-5558 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 FBC-BUILDING AMBULATORY SURGICAL CENTERS SECTION |
| 451.1.3. THE FLORIDA BUILDING CODE, EXISTING BUILDING |
| SECTION 101.2. SCOPE EXEMPTS STATE LICENSED FACILITIES |
| SUCH AS AMBULATORY SURGICAL CENTERS FROM COMPLIANCE |
| WITH THAT CODE. THIS MEANS THAT EVERYTHING TO BE |
| REVIEWED IS AS NEW CONSTRUCTION. |
| |
| 2ND REVIEW |
| DATE: FRI. FEB. 19TH/ 2021 |
| ACTION: DENIED |
| |
| 1) SITE PLAN: |
| |
| 1A) & 1B) COMPLIED. |
| |
| 1C) 2ND REQUEST. THE RESPONSE INDICATES SEE CIVIL PLANS |
| FOR DETAILS. THE CIVIL PLANS WERE NOT INCLUDED IN THIS |
| SUBMISSION NOR WAS A PERMIT NUMBER PROVIDED FOR THE |
| CIVIL PLANS. |
| 1ST REQUEST. 2017 ACCESSIBILITY CODE SECTION 502.2 |
| VEHICLE SPACES. EACH PARKING SPACE MUST BE AT LEAST 12 |
| FEET WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, AND |
| SHALL HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH |
| 502.3. |
| ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR |
| OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT |
| MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485 |
| ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL |
| PAINTING. |
| |
| 1D) 2ND REQUEST. THE RESPONSE INDICATES SEE CIVIL PLANS |
| FOR DETAILS. THE CIVIL PLANS WERE NOT INCLUDED IN THIS |
| SUBMISSION NOR WAS A PERMIT NUMBER PROVIDED FOR THE |
| CIVIL PLANS. |
| 1ST REQUEST. PLEASE SHOW COMPLIANCE WITH SECTION 502.4 |
| OF THE 2017 FBC-ACCESSIBILITY CODE. PARKING SPACES AND |
| ACCESS AISLES SERVING THEM SHALL COMPLY WITH 302. |
| ACCESS AISLES SHALL BE AT THE SAME LEVEL AS THE PARKING |
| SPACES THEY SERVE. CHANGES IN LEVEL ARE NOT PERMITTED. |
| EXCEPTION: SLOPES NOT STEEPER THAN 1:48 SHALL BE |
| PERMITTED. |
| |
| 1D) PLEASE SUBMIT A SURVEY WITH THE CURRENT BUILDING |
| LOCATION AND PROPOSED ADDITION. PALM BEACH COUNTY |
| PROPERTY APPRAISERS OFFICE SHOWS WHAT APPEARS TO BE A |
| RIGHT OF WAY BEHIND THE BUILDING THAT SEPARATES THE |
| REMAINDER OF THE LOT TO THE EAST OF THIS RIGHT OF WAY. |
| THE ADDITION MAY TRANSGRESS THE PROPERTY LINE. 2017 |
| FBC-B TABLE 602. PLEASE PROVIDE THE DISTANCE FROM THE |
| NEW PROPOSED ADDITION TO THIS RIGHT OF WAY. THE |
| GENERATOR AND PAD AS WELL AS THE NEW CHILLER AND |
| CONCRETE PAD MAYBE IN THE RIGHT OF WAY. |
| |
| 2) 2ND REQUEST. YOU MAY HAVE SUBMITTED A SURVEY TO |
| ZONING DIVISION BUT THIS IS THE BUILDING DIVISION THAT |
| REQUEST A CURRENT SURVEY TO KEEP WITH THIS PERMIT SET |
| OF PLANS TO SHOW CODE COMPLIANCE WITH THE 2017 FBC-B |
| TABLE 602 AND TABLE 705.8 THAT THE BUILDING AND |
| OPENINGS ARE NOT TRANSGRESSING THE PROPERTY LINES AND |
| ALLOWABLE OPENINGS. |
| 1ST ROUND OF COMMENTS. THE DEMOLITION PLAN STATES |
| REMOVAL OF ALL INTERIOR PARTITION WALLS. THEE SHEET |
| A3.1 THE DIMENSION PLAN IS MISSING A LOT OF INTERIOR |
| DIMENSIONS THAT WILL BE NEEDED TO KNOW WHERE TO PLACE |
| WALL LINES. SOME EXAMPLES ARE THE EAST WEST LINES OF |
| THE ENTRY VESTIBULE, CLINIC WAITING, HALL 108, MANAGERS |
| OFFICE, STAFF LOCKER ROOM, STAFF HANDICAPPED SHOWER, |
| ETC. ADDITIONAL INFORMATION REQUIRED. 107.2.1.2. |
| |
| 3A) 2ND REQUEST. THE RESPONSE LETTER INDICATES THAT |
| SHEET A3.4 HAS BEEN REVISED. THE PLANS DO NOT SHOW A |
| VERSION 2 OF THE PLANS AND THE DATE FOR PLANS SHEET |
| A3.4 STILL SHOWS AN UPLOAD DATE OF 12/18/2020 OR BEFORE |
| THE 1ST REVIEW TOOK PLACE. |
| |
| 1ST ROUND OF COMMENTS. SHEET A3.4 THE ROOF PLAN THAT |
| HAS 2 SECTION LINES WITH NO INFORMATION PROVIDED. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3B) ) 2ND REQUEST. THE RESPONSE LETTER INDICATES THAT |
| SHEET A3.4 HAS BEEN REVISED. THE PLANS DO NOT SHOW A |
| VERSION 2 OF THE PLANS AND THE DATE FOR PLANS SHEET |
| A3.4 STILL SHOWS AN UPLOAD DATE OF 12/18/2020 OR BEFORE |
| THE 1ST REVIEW TOOK PLACE. |
| |
| 1ST ROUND OF COMMENTS. THE NEW FLAT ROOF DETAIL SHOWS |
| WHAT APPEARS TO BE 4 SETS OF ROOF DRAIN AND OVERFLOW. |
| NO INFORMATION AS TO ANNUAL RAINFALL, THE ROOF SQUARE |
| FOOTAGE EACH SET OF DRAINS AND OVERFLOWS ARE CAPABLE OF |
| CARRYING, PIPE SIZE ETC. 2017 FBC-B 1503.4. |
| |
| 4-5) COMPLIED. |
| |
| 6) BUILDING PROVISO: THE ARCHITECTURAL AND STRUCTURAL |
| SHEETS SHOW THE INSTALLATION OF STEEL COLUMNS, BEAMS, |
| BAR JOIST AND METAL ROOF DECKING. WELDED OR BOLTED |
| CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE |
| WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF |
| FRAMING INSPECTION. |
| 2017 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2. QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| AT 561-805-6666. |
| |
| 7A) BUILDING PROVISO/ DEFERRED SUBMITTALS: |
| PLEASE PROVIDE PRODUCT APPROVALS FOR COMPONENTS AND |
| CLADDING. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, |
| |
| 7B) BUILDING PROVISO/ DEFERRED SUBMITTALS: |
| W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 7C) ) BUILDING PROVISO/ DEFERRED SUBMITTALS: |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 7D) BUILDING PROVISO/ DEFERRED SUBMITTALS: |
| FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 8) 2ND REQUEST. IMPACT FEES - DIGITAL SUBMITTALS: PLANS |
| WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY |
| VIA PROJECT DOX UPON NOTIFICATION BY THIS OFFICE. |
| NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL |
| FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT |
| (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT |
| FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE |
| FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN |
| BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT |
| ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO [email protected] . |
| |
| 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |