Plan Review Notes
Plan Review Notes For Permit 20120907
Permit Number 20120907
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-20 13:58:2501/20/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET S300, IT SHOWS A SLAB TRENCH DETAIL FOR THE
 REPAIR, AND IT SHALL ALSO INCLUDE TERMITE TREATMENT OF
 THE SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE
 ONSITE FOR A FINAL INSPECTION PER THE 2017
 FBC-RESIDENTIAL SECTION R318.1.1.
  
 2. ON SHEET A3.0, THE SERVICE SINK (MOP SINK)
 SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE
 IN ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2
 AND 2017 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS
 SHEET.
  
 3. ON SHEET A3.0:
 A. PLEASE LABEL ALL ROOMS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. IN THE SOILED WORKSTATION, IT SHOWS A RADIUS WHICH
 IS NOT REQUIRED, PLEASE REMOVE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. IN THE RESTROOM, THE DOOR SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE
 PER THE 2017 FBC-ACC SEC. 603.2.3. PLEASE SHOW THE 30"
 X 48" AND 60" TRUING RADIUS THE EXCEPTION 2 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. PLEASE SHOW CLEAR FLOOR SPACE IN FRONT OF A SHOWER
 OF 36" X 48" PER THE 2017 FBC ACC. SEC. 608.2.1.
  
 E. THE SINKS IN THE EXAM ROOM SHALL HAVE AT LEAST 5%
 AND NOT FEWER THAN ONE OF ACCESSIBILITY PER THE 2017
 FBC ACC. SEC. 212.3. PLEASE SHOW THE SINKS FORWARD
 APPROACH PER THE 606.2 CLEAR FLOOR SPACE AND A DETAIL
 OF THE SINK ON DETAIL PAGE A 6.1 PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 ON SHEET A6.1;
 A. FOR DETAIL 2 OF THE SHOWER, PLEASE SHOW THE
 DIMENSION ON THE SIDE VIEW AND LOCATION OF THE GRAB
 BARS AND THE CONTROL VALVE PER THE 2017 FBC SEC.
 608.5.1 AND 608.3.1.
  
 B. PLEASE PROVIDE DETAIL FOR THE BACKING OF THE SHOWER
 GRAB BARS AND SEAT PER THE 2017 FBC ACC. SEC. 610.4.
  
 C. THE GRAB BARS ON THE FLAT TOILET DETAIL NEED THE TO
 BE MEASURED FROM CENTERLINE TO CENTERLINE PER THE 207
 FBC AA. SEC. 604.5.2.
  
 D. ON ADA FIXTURE CLEARANCE, NOTE #1 AND #3 ARE NOT
 SHOWN IN BOTH DETAILS PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. ON SHEET 6.2. IN DETAILS 6 AND 7, THE UL HOURLY
 RATING IS MISSING. PLEASE DEFINE THE FIREWALL HOUR
 RATING PER THE 2017 FBC 714.3.
  
 5. ON SHEET 10.1, PLEASE PROVIDE DETAIL CORRESPONDING
 WITH A COMMENT 2.E ON THE EXAM ROOM FOR THE CABINET
 HEIGHT OF 34? AS PER THE 2017 FBC ACC SEC. 606.3.
  
 6. ON SHEET M803, DETAIL MD 6411, A BACKFLOW DEVICE IS
 PRESENT, AND IT WILL REQUIRE A SEPARATE PERMIT AS AN
 ISOLATION DEVICE WITH THE CERTIFICATION OF A LICENSED
 CONTRACTOR. ALL BACKFLOWS THAT ARE ISOLATION MAY BE
 COMBINED IN THAT PERMIT, NOT INCLUDING THE CONTAINMENT
 BACKFLOW, FIRE DUAL CHECK VALVE, IRRIGATION, AND WATER
 SERVICE, WHICH NEED TO BE CERTIFIED BY THE CITY OF WEST
 PALM BEACH UTILITIES DEPARTMENT. PLEASE MAKE A NOTE IF
 POSSIBLE. PLEASE PROVIDE SEPARATE DRAINS FOR EACH
 DEVICE UNLESS DOCUMENTATION IS PROVIDED THAT THE DRAINS
 CAN BE COMBINED PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. ON SHEET M804, ON DETAIL MD-0902, A BACKFLOW DEVICE
 IS NOT SPECIFIED OR DOES NOT SHOW A DRAIN. PLEASE DO
 THE SAME FOR THE COMMENT ABOVE AND PROVIDE THE MAKE AND
 MODEL PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. ON SHEET P000, FOR GENERAL PLUMBING NOTES ITEM 10,
 THE HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010.
  
 9. ON SHEET P100, THERE IS A SANITARY FITTING THAT IS
 NOT IN THE FLOW DIRECTION THAT PICKS UP THE MOP SINK ON
 ONE SIDE AND TWO SINKS ON THE OTHER SIDE, IN THE PRE-OP
 RECOVERY AREA. PLEASE CHANGE PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. NOTE: PLEASE CORRECT ON ISOMETRIC PAGE P600
 AS WELL. THANKS.
  
 10. ON SHEET P510;
 A. THE CLINICAL SINK/BIDET WATER TEMPERATURE SHALL BE
 LIMITED TO A MAXIMUM TEMPERATURE OF 110 F (43 C) BY A
 WATER TEMPERATURE LIMITING DEVICE CONFORMING TO ASSE
 1070 OR CSA B125.3 PER THE 2017 FBC P408.3 BIDET WATER
 TEMPERATURE.
  
 B. M-2 AND M-2, EACH WATER STERILIZER FILLED WITH WATER
 THROUGH DIRECTLY CONNECTED PIPING SHALL BE EQUIPPED
 WITH AN APPROVED LEAKAGE DIVERTER OR BLEED LINE ON THE
 WATER SUPPLY CONTROL VALVE TO INDICATE AND CONDUCT ANY
 LEAKAGE OF UNSTERILE WATER AWAY FROM THE STERILE ZONE
 PER THE 2017 FBC P 609.8 VALVE LEAKAGE DIVERTER.
  
 C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2017 FBC BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 11. ON SHEET P600;
 A. PLEASE LABEL ALL THE CLEAN-OUT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. ME-3, ME-2, AND ME-1 COVER HOW THE P-TRAPS ARE
 INSTALLED IN THE ISOMETRIC. FOR CLARITY, PLEASE OUTLINE
 THE BOXES IN A DASHED FORMAT SO THE P-TRAP CAN BE SEEN
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. PLEASE SHOW LINES TO TRAP PRIMERS ON ALL FLOOR
 DRAINS THAT REQUIRE THEM PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. ON THE GENERAL NOTE C, IT REFERS TO P0.1, AND THERE
 IS NO SUCH PAGE. PLEASE CLARIFY THE PAGE NUMBER PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 12. ON SHEET P 601, PLEASE THE INSULATION DETAIL FOR
 THE HOT WATER RECIRCULATING SYSTEM PER THE 2017 ENERGY
 CODE FBC CE 404.4.
  
 13. ON SHEET P801 AND P802, THERE ARE SEVERAL DETAILS
 WITH PD-000 IN MULTIPLE USE; PLEASE RELABEL THE DETAIL
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 14. ON SHEET P801;
 A. THE SINGLE TRAP PRIMER DETAIL HAS A VALVE ON THE
 RUN. THE TRAP PRIMER NEEDS TO BE ON AN ISOLATION VALVE
 FOR MAINTENANCE PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. THE ICE MAKER AND COFFEE MAKER REQUIRES AN INLINE
 VACUUM BREAKER THAT COMPLIES WITH THE ASSE 1024
 NON-CARBONATED.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR