Date |
Text |
2021-01-20 16:00:44 | 01/20/21 1ST MEDICAL GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. IT IS NOTED ON THE PLAN THE CONTRACTOR AND ANYONE |
| INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED, |
| BUT THE INSTALLERS SHALL PROVIDE PROOF FOR PERMIT ISSUE |
| AND ON THE JOB SITE FOR INSPECTORS APPROVAL PER THE FAC |
| 61G4-15.031(1)(4A)(4B). |
| |
| 2. PROVIDE MANUFACTURE SPECIFICATION AND INSTALLATION |
| GUIDE FOR THE NEW VACUUM PUMP AND AIR COMPRESSOR PER |
| THE WPB AMEND TO FBC 107.2.1. |
| |
| 3. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION |
| GUIDES FOR ALL MED GAS EQUIPMENT PER THE WPB AMEND TO |
| FBC 107.2.1 AND NFPA 99 2015. |
| |
| 4. THE CONTRACTOR SHALL PROVE THAT THE QUALIFIER HAS |
| BEEN BEING CERTIFIED UNDER FLORIDA RULE 61G4 ? 15.031. |
| |
| 5 THE INSTALLER SHALL PROVIDE PROOF THAT THE INDIVIDUAL |
| WORKING ON THE SYSTEM HAS BEEN CERTIFIED PER FLORIDA |
| RULE 61G4 ? 15.031. |
| |
| 6. THE CONTRACTOR SHALL PROVIDE PROOF OF ALL FITTINGS |
| AND COMPONENTS ARE BEING CLEANED FOR OXYGEN SERVICE PER |
| THE NFPA 99 2015 SEC. 5.1.10.1.1. |
| |
| 7. THE CONTRACTOR SHALL PROVIDE A CERTIFICATION REPORT |
| SHOWING ALL OUTLETS, VALVES, SOURCE EQUIPMENT ALARMS |
| PER THE NFPA 99 2015 SEC. 5.1.12.1.1 AND 5.1.12.6. |
| |
| 8. ALL MEDICAL GAS TUBING MEETS THE ASTM B 819 |
| STANDARDS PER THE NFPA 99 2015 SEC. 5.1.10.1. |
| |
| 9. THE CONTRACTOR SHALL HAVE PROOF OF RECORDS |
| AVAILABLE FOR THE FOLLOWING TEST BEING COMPLETED PER |
| NFPA 99 2015 SEC. 5.1.12.2. |
| |
| A. INITIAL PRESSURE TEST (MINIMUM OF 150 PSI) PER THE |
| NFPA 99 2015 SEC. 5.1.2.2.3.4. |
| |
| B. INITIAL CROSS-CONNECT TEST PER THE NFPA 99 2015 SEC. |
| 5.1.12.2.4. |
| |
| C. 24 HOURS STANDING PRESSURE TEST PER THE NFPA 99 2015 |
| SEC. 5.1.12.2.6.7. |
| |
| D. PIPING AND OUTLET PURGE TEST PER THE NFPA 99 2015 |
| SEC. 5.1.12.2.5. |
| |
| E. STANDING VACUUM TEST FOR VACUUM PIPING PER THE NFPA |
| 99 2015 SEC. 5.1.12.2.7. |
| |
| 11. PLEASE SPECIFY WHAT TYPE OF PIPING IS BEING USED |
| FOR THE COMPRESSED AIR LINES PER THE WPB AMEND TO FBC |
| 107.2.1. |
| |
| 12. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR |
| THE VACUUM PUMPS AND AIR COMPRESSORS, THE |
| MUFFLER/INTAKE, THE RECEIVERS, DRYERS, AFTERCOOLERS, |
| ETC., PER THE WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 13. A PRESSURE INDICATOR(S) SHALL BE LOCATED DOWNSTREAM |
| OF EACH REGULATOR OR IMMEDIATELY DOWNSTREAM OF THE |
| REGULATORS' ISOLATING VALVES PER THE NFPA 99 2015 SEC. |
| 5.1.3.5.5.1 (3). |
| |
| 14. PLEASE SHOW THE VACUUM PUMP VENT LINE'S TERMINATION |
| POINT PER THE NFPA 99 2015 SEC.5.1.3.7.6.2. |
| |
| 15. THE VACUUM PUMPS SHALL BE PROVIDED WITH |
| ANTI-VIBRATION MOUNTINGS PER THE NFPA 99 2015 SEC. |
| 5.1.3.7.2. |
| |
| 16. THE PRESSURE RELIEF VALVES ON THE COMPRESSED AIR |
| SYSTEM SHALL BE VENTED IN ACCORDANCE WITH NFPA 99 2015 |
| SEC. 5.1.3.5.6.1 (4). |
| |
| 17. THE AREA(S) HOUSING THE VACUUM PUMP AND AIR |
| COMPRESSOR SHALL BE VENTILATED. HOW IS THIS BEING DONE |
| PER THE NFPA 99 2015 SECS.5.1.3.3.3.3, 5.1.3.6.3.1, |
| 5.1.3.7.1.1? |
| |
| 18. CLEARLY SHOW THE TERMINATION POINTE OF THE VACUUM |
| EXHAUST AND RELIEF PIPING ON THE ROOF PLAN PER THE NFPA |
| 99 2015 SEC. 5.1.3.7.7, 5.1.3.5.6 |
| |
| 19. PROVIDE ROOF DRAWING SHOWING DISTANCE FROM VACUUM |
| EXHAUST TO AIR INTAKES PER THE WPB AMEND TO FBC |
| 107.2.1. |
| |
| 20. PLEASE SHOWS VACUUM EXHAUST DISCHARGING THROUGH THE |
| EXTERIOR WALL, AND IT SHALL DISCHARGE THROUGH THE ROOF |
| PER THE 2017 FBC P 713.6 AND NFPA 99 2015 SEC. |
| 5.1.3.7.7. |
| |
| 21. HOW TO TANK ARE SECURED PER THE WPB AMEND TO FBC |
| 107.2.1 AND NFPA 99 2015. |
| |
| 22. NOTE ON THE PLAN THE NUMBER AND SIZE OF TANKS PER |
| THE WPB AMEND TO FBC 107.2.1 AND NFPA 99 2015. |
| |
| 23. A SEPARATE PERMIT IS REQUIRED FOR MED GAS PER THE |
| WPB AMENDMENTS TO FBC SEC. 105.1. |
| |
| 24. PLEASE NOTE THAT TUBING MEETS ASTM B 819 (OXY/MED, |
| ACR/OXY, ACR/MED) PER THE NFPA 99 23015 SEC. |
| 5.1.10.1.5. |
| |
| 25. PLEASE SUBMIT DETAILS FOR COMPRESSOR SHOWING |
| COMPLIANCE WITH SECTION NFPA 99 2015 SEC. 5.3.3.5.3. |
| (1) THRU (17). |
| |
| 26. PLEASE ADD A NOTE THAT THE VACUUM SHALL RUN TO A |
| SLOPE 1/4 "PER TEN FEET TOWARD THE VACUUM PUMP |
| |
| 27. PLEASE SHOW THE LIFE SAFETY OF A MED GAS STORAGE |
| SCHEDULE, AND PLEASE INCLUDE THIS ON THE MED GAS PLAN |
| SHEETS PER THE WPB AMEND TO FBC 107.2.1. |
| |
| PLEASE NOTE THAT SOME COMMENTS MAY NOT APPLY TO THIS |
| REVIEW, AND A SIMPLE N/A WILL BE SUFFICIENT ON A |
| RESPONSE. WHEN RESUBMITTING PLANS, PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY |
| NECESSARY PAGES. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION, MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| REFERENCE: NFPA 99 2015 EDITION |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / MEDICAL GAS INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |