Plan Review Notes
Plan Review Notes For Permit 20120907
Permit Number 20120907
Review Stop MEDGAS
Sequence Number 1
Notes
Date Text
2021-01-20 16:00:4401/20/21 1ST MEDICAL GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. IT IS NOTED ON THE PLAN THE CONTRACTOR AND ANYONE
 INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED,
 BUT THE INSTALLERS SHALL PROVIDE PROOF FOR PERMIT ISSUE
 AND ON THE JOB SITE FOR INSPECTORS APPROVAL PER THE FAC
 61G4-15.031(1)(4A)(4B).
  
 2. PROVIDE MANUFACTURE SPECIFICATION AND INSTALLATION
 GUIDE FOR THE NEW VACUUM PUMP AND AIR COMPRESSOR PER
 THE WPB AMEND TO FBC 107.2.1.
  
 3. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR ALL MED GAS EQUIPMENT PER THE WPB AMEND TO
 FBC 107.2.1 AND NFPA 99 2015.
  
 4. THE CONTRACTOR SHALL PROVE THAT THE QUALIFIER HAS
 BEEN BEING CERTIFIED UNDER FLORIDA RULE 61G4 ? 15.031.
  
 5 THE INSTALLER SHALL PROVIDE PROOF THAT THE INDIVIDUAL
 WORKING ON THE SYSTEM HAS BEEN CERTIFIED PER FLORIDA
 RULE 61G4 ? 15.031.
  
 6. THE CONTRACTOR SHALL PROVIDE PROOF OF ALL FITTINGS
 AND COMPONENTS ARE BEING CLEANED FOR OXYGEN SERVICE PER
 THE NFPA 99 2015 SEC. 5.1.10.1.1.
  
 7. THE CONTRACTOR SHALL PROVIDE A CERTIFICATION REPORT
 SHOWING ALL OUTLETS, VALVES, SOURCE EQUIPMENT ALARMS
 PER THE NFPA 99 2015 SEC. 5.1.12.1.1 AND 5.1.12.6.
  
 8. ALL MEDICAL GAS TUBING MEETS THE ASTM B 819
 STANDARDS PER THE NFPA 99 2015 SEC. 5.1.10.1.
  
 9. THE CONTRACTOR SHALL HAVE PROOF OF RECORDS
 AVAILABLE FOR THE FOLLOWING TEST BEING COMPLETED PER
 NFPA 99 2015 SEC. 5.1.12.2.
  
 A. INITIAL PRESSURE TEST (MINIMUM OF 150 PSI) PER THE
 NFPA 99 2015 SEC. 5.1.2.2.3.4.
  
 B. INITIAL CROSS-CONNECT TEST PER THE NFPA 99 2015 SEC.
 5.1.12.2.4.
  
 C. 24 HOURS STANDING PRESSURE TEST PER THE NFPA 99 2015
 SEC. 5.1.12.2.6.7.
  
 D. PIPING AND OUTLET PURGE TEST PER THE NFPA 99 2015
 SEC. 5.1.12.2.5.
  
 E. STANDING VACUUM TEST FOR VACUUM PIPING PER THE NFPA
 99 2015 SEC. 5.1.12.2.7.
  
 11. PLEASE SPECIFY WHAT TYPE OF PIPING IS BEING USED
 FOR THE COMPRESSED AIR LINES PER THE WPB AMEND TO FBC
 107.2.1.
  
 12. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR
 THE VACUUM PUMPS AND AIR COMPRESSORS, THE
 MUFFLER/INTAKE, THE RECEIVERS, DRYERS, AFTERCOOLERS,
 ETC., PER THE WPB AMEND. TO FBC SEC. 107.2.1.
  
 13. A PRESSURE INDICATOR(S) SHALL BE LOCATED DOWNSTREAM
 OF EACH REGULATOR OR IMMEDIATELY DOWNSTREAM OF THE
 REGULATORS' ISOLATING VALVES PER THE NFPA 99 2015 SEC.
 5.1.3.5.5.1 (3).
  
 14. PLEASE SHOW THE VACUUM PUMP VENT LINE'S TERMINATION
 POINT PER THE NFPA 99 2015 SEC.5.1.3.7.6.2.
  
 15. THE VACUUM PUMPS SHALL BE PROVIDED WITH
 ANTI-VIBRATION MOUNTINGS PER THE NFPA 99 2015 SEC.
 5.1.3.7.2.
  
 16. THE PRESSURE RELIEF VALVES ON THE COMPRESSED AIR
 SYSTEM SHALL BE VENTED IN ACCORDANCE WITH NFPA 99 2015
 SEC. 5.1.3.5.6.1 (4).
  
 17. THE AREA(S) HOUSING THE VACUUM PUMP AND AIR
 COMPRESSOR SHALL BE VENTILATED. HOW IS THIS BEING DONE
 PER THE NFPA 99 2015 SECS.5.1.3.3.3.3, 5.1.3.6.3.1,
 5.1.3.7.1.1?
  
 18. CLEARLY SHOW THE TERMINATION POINTE OF THE VACUUM
 EXHAUST AND RELIEF PIPING ON THE ROOF PLAN PER THE NFPA
 99 2015 SEC. 5.1.3.7.7, 5.1.3.5.6
  
 19. PROVIDE ROOF DRAWING SHOWING DISTANCE FROM VACUUM
 EXHAUST TO AIR INTAKES PER THE WPB AMEND TO FBC
 107.2.1.
  
 20. PLEASE SHOWS VACUUM EXHAUST DISCHARGING THROUGH THE
 EXTERIOR WALL, AND IT SHALL DISCHARGE THROUGH THE ROOF
 PER THE 2017 FBC P 713.6 AND NFPA 99 2015 SEC.
 5.1.3.7.7.
  
 21. HOW TO TANK ARE SECURED PER THE WPB AMEND TO FBC
 107.2.1 AND NFPA 99 2015.
  
 22. NOTE ON THE PLAN THE NUMBER AND SIZE OF TANKS PER
 THE WPB AMEND TO FBC 107.2.1 AND NFPA 99 2015.
  
 23. A SEPARATE PERMIT IS REQUIRED FOR MED GAS PER THE
 WPB AMENDMENTS TO FBC SEC. 105.1.
  
 24. PLEASE NOTE THAT TUBING MEETS ASTM B 819 (OXY/MED,
 ACR/OXY, ACR/MED) PER THE NFPA 99 23015 SEC.
 5.1.10.1.5.
  
 25. PLEASE SUBMIT DETAILS FOR COMPRESSOR SHOWING
 COMPLIANCE WITH SECTION NFPA 99 2015 SEC. 5.3.3.5.3.
 (1) THRU (17).
  
 26. PLEASE ADD A NOTE THAT THE VACUUM SHALL RUN TO A
 SLOPE 1/4 "PER TEN FEET TOWARD THE VACUUM PUMP
  
 27. PLEASE SHOW THE LIFE SAFETY OF A MED GAS STORAGE
 SCHEDULE, AND PLEASE INCLUDE THIS ON THE MED GAS PLAN
 SHEETS PER THE WPB AMEND TO FBC 107.2.1.
  
 PLEASE NOTE THAT SOME COMMENTS MAY NOT APPLY TO THIS
 REVIEW, AND A SIMPLE N/A WILL BE SUFFICIENT ON A
 RESPONSE. WHEN RESUBMITTING PLANS, PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 NECESSARY PAGES. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION, MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 REFERENCE: NFPA 99 2015 EDITION
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / MEDICAL GAS INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved