2021-01-13 10:54:31 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-20120907 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2020 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M700: ASHRAE STD 170 VENTILATION AND AIR |
| CHANGES REQUIREMENTS |
| (AHU-1)- SOILED WORKROOM OR SOILED HOLDING, ALL AIR |
| SHOULD BE EXHAUSTED TO THE OUTDOORS. TABLE 7-1 |
| (B) MED GAS ROOM ALL AIR SHOULD BE EXHAUSTED TO THE |
| OUTDOORS. TABLE 7-1 |
| (AHU-2)- SOILED WORK ROOM ALL AIR SHOULD BE EXHAUSTED |
| TO THE OUTDOORS. TABLE 7-1. |
| |
| 2) SHEET M130: PLEASE SHOW THE OUTDOOR AIR INTAKES AND |
| EXHAUST DISCHARGES COMPLY WITH ASHRAE 170 6.3 |
| |
| 3) SHEET M111: THE EQUIPMENT AND SUPPLY ROOM APPEARS TO |
| HAVE RATED WALLS AND CEILINGS. PLEASE SHOW RATED |
| DAMPERS AT ALL OF THE PENETRATIONS OF THE RATED |
| ASSEMBLIES. FBC M 607 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |