2021-01-14 16:22:32 | CODES IN EFFECT |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| REVIEW STATUS: FAILED. |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1) E600 ? ELECTRICAL RISER DIAGRAM: RISER SHOWS A |
| 277/480 VOLTS TRANSFORMER, BUT PANELS ARE 120/208 |
| VOLTS. PLEASE CORRECT FOR CONSISTENCY. |
| 2) PLEASE PROVIDE LOAD CALCULATIONS FOR: |
| - MAIN SERVICE AND SUBPANELS |
| - EMERGENCY GENERATOR. |
| 3) PLEASE PROVIDE DRAWING DETAILS/SPECS/NOTES TO SHOW |
| SPECIFIC COMPLIANCE WITH: |
| - WIRING METHOD TO BE USED IN PATIENT CARE AREAS. NEC |
| 517.13(A), 517.13(B) |
| - GROUND FAULT PROTECTION. NEC 517.17 |
| - ANESTHETIZING LOCATIONS: MEDICAL GAS ROOM, OPERATING |
| ROOMS, PROCEDURE ROOM, PREOP, ANESTHESIA WORKROOM MUST |
| COMPLY WITH NEC 517 PART IV AND NEC 501 (CLASS I). |
| 4) DIGITAL SIGNATURE (ELECTRICAL DRAWINGS): DIGITAL |
| CERTIFICATE FOR MR. PHILIP GARRETT IS NO LONGER VALID |
| (EXPIRED ON 1/2/2021). SEE SIGNATURE COMMENTS TOO. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| ENRIQUE QUINONEZ |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |
| |