Plan Review Notes
Plan Review Notes For Permit 20120907
Permit Number 20120907
Review Stop B
Sequence Number 1
Notes
Date Text
2021-01-10 17:18:45WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120907
 ADD: 6910 S. DIXIE HWY.
 CONT: BANDES CONSTRUCTION
 TEL: 727-733-5558
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 FBC-BUILDING AMBULATORY SURGICAL CENTERS SECTION
 451.1.3. THE FLORIDA BUILDING CODE, EXISTING BUILDING
 SECTION 101.2,SCOPE EXEMPTS STATE LICENSED FACILITIES
 SUCH AS AMBULATORY SURGICAL CENTERS FROM COMPLIANCE
 WITH THAT CODE. THIS MEANS THAT EVERYTHING TO BE
 REVIEWED IS AS NEW CONSTRUCTION.
  
 1ST REVIEW
 DATE: SUN. JAN. 10TH/ 2021
 ACTION: DENIED
  
 1) SITE PLAN:
 1A) THE SITE PLAN STATES THAT THERE ARE 53 PARKING
 SPACES AND ONLY 2 ACCESSIBLE PARKING SPACES. PLEASE
 REVIEW THE 2017 FBC-ACCESSIBILITY CODE TABLE 208.2 51
 TO 75 PARKING SPACES REQUIRES 3 PARKING SPACES.
  
 1B) PLEASE NOTE SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE SECTION 208.3.1 PARKING SPACES
 COMPLYING WITH 502 THAT SERVE A PARTICULAR BUILDING OR
 FACILITY SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE
 ROUTE FROM THE PARKING TO AN ACCESSIBLE ENTRANCE
 COMPLYING WITH 206.4.
  
 1C) 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE
 SPACES. EACH PARKING SPACE MUST BE AT LEAST 12 FEET
 WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, AND SHALL
 HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 1D) PLEASE SHOW COMPLIANCE WITH SECTION 502.4 OF THE
 2017 FBC-ACCESSIBILITY CODE. PARKING SPACES AND ACCESS
 AISLES SERVING THEM SHALL COMPLY WITH 302. ACCESS
 AISLES SHALL BE AT THE SAME LEVEL AS THE PARKING SPACES
 THEY SERVE. CHANGES IN LEVEL ARE NOT PERMITTED.
 EXCEPTION: SLOPES NOT STEEPER THAN 1:48 SHALL BE
 PERMITTED.
  
 1D) PLEASE SUBMIT A SURVEY WITH THE CURRENT BUILDING
 LOCATION AND PROPOSED ADDITION. PALM BEACH COUNTY
 PROPERTY APPRAISERS OFFICE SHOWS WHAT APPEARS TO BE A
 RIGHT OF WAY BEHIND THE BUILDING THAT SEPARATES THE
 REMAINDER OF THE LOT TO THE EAST OF THIS RIGHT OF WAY.
 THE ADDITION MAY TRANSGRESS THE PROPERTY LINE. 2017
 FBC-B TABLE 602. PLEASE PROVIDE THE DISTANCE FROM THE
 NEW PROPOSED ADDITION TO THIS RIGHT OF WAY. THE
 GENERATOR AND PAD AS WELL AS THE NEW CHILLER AND
 CONCRETE PAD MAYBE IN THE RIGHT OF WAY.
  
 2) THE DEMOLITION PLAN STATES REMOVAL OF ALL INTERIOR
 PARTITION WALLS. THEE SHEET A3.1 THE DIMENSION PLAN IS
 MISSING A LOT OF INTERIOR DIMENSIONS THAT WILL BE
 NEEDED TO KNOW WHERE TO PLACE WALL LINES. SOME EXAMPLES
 ARE THE EAST WEST LINES OF THE ENTRY VESTIBULE, CLINIC
 WAITING, HALL 108, MANAGERS OFFICE, STAFF LOCKER ROOM,
 STAFF HANDICAPPED SHOWER, ETC. ADDITIONAL INFORMATION
 REQUIRED. 107.2.1.2.
  
 3A) SHEET A3.4 THE ROOF PLAN THAT HAS 2 SECTION LINES
 WITH NO INFORMATION PROVIDED. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3B) THE NEW FLAT ROOF DETAIL SHOWS WHAT APPEARS TO BE 4
 SETS OF ROOF DRAIN AND OVERFLOW. NO INFORMATION AS TO
 ANNUAL RAINFALL, THE ROOF SQUARE FOOTAGE EACH SET OF
 DRAINS AND OVERFLOWS ARE CAPABLE OF CARRYING, PIPE SIZE
 ETC. 2017 FBC-B 1503.4.
  
 4) SHEET Q6.1 ADA FIXTURE CLEARANCES PLEASE REVIEW GRAB
 BAR REQUIREMENTS FOR THE WATER CLOSET. 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 5) PLEASE SEE SHEET S101 THE COMPONENTS AND CLADDING
 CHART IS FUZZY AND CAN NOT BE READ. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) THE ARCHITECTURAL AND STRUCTURAL SHEETS SHOW THE
 INSTALLATION OF STEEL COLUMNS, BEAMS, BAR JOIST AND
 METAL ROOF DECKING. WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 7A) PLEASE PROVIDE PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
 (D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 7B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7D) FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 8) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  