2021-01-08 08:13:4801/08/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE THE MANUFACTURE'S SPECIFICATIONS FOR
 THE PUMP. PLEASE IDENTIFY ON THE PUMP CURVE WHICH CURVE
 KEY IS SPECIFIC TO THE PUMP BEING INSTALLED ON THIS
 POOL. THIS IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW
 FROM THE TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 -
 2013 SECS. 4.4.9, 4.4.9.1.
  
 2. SOLAR COVER REQUIRED PER 2017 FBC RE 403.10.3
 LIQUID.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN GAS HEATER AND THE FILTER PER THE WPB AMENDMENTS
 TO FBC SEC. 107.2.1.
  
 4. SUBMIT DOCUMENTATION THAT THE GAS POOL HEATER MEETS
 THE MINIMUM REQUIRED EFFICIENCY AS REQUIRED BY THE 2017
 FBC-ENERGY SEC.R403.10.4.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  