2021-01-08 08:13:48 | 01/08/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE PROVIDE THE MANUFACTURE'S SPECIFICATIONS FOR |
| THE PUMP. PLEASE IDENTIFY ON THE PUMP CURVE WHICH CURVE |
| KEY IS SPECIFIC TO THE PUMP BEING INSTALLED ON THIS |
| POOL. THIS IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW |
| FROM THE TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - |
| 2013 SECS. 4.4.9, 4.4.9.1. |
| |
| 2. SOLAR COVER REQUIRED PER 2017 FBC RE 403.10.3 |
| LIQUID. |
| |
| 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN |
| DRAIN GAS HEATER AND THE FILTER PER THE WPB AMENDMENTS |
| TO FBC SEC. 107.2.1. |
| |
| 4. SUBMIT DOCUMENTATION THAT THE GAS POOL HEATER MEETS |
| THE MINIMUM REQUIRED EFFICIENCY AS REQUIRED BY THE 2017 |
| FBC-ENERGY SEC.R403.10.4. |
| |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |