Plan Review Notes For Permit 20120900 |
Permit Number |
20120900 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-12-22 13:12:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET -SITE PLAN - THERE IS AN INDICATION OF A | | GENRAL LOCATION OF THE PROPOSED GENERATOR; HOWEVER, | | THERE ARE NO DETAILS. | | | | PER NFPA 37, INSTALLATION AND USE OF STATIONARY | | COMBUSTION ENGINES AND GAS TURBINES | | | | 8.2.3 EXHAUST SYSTEM TERMINATION. | | 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE | | STRUCTURE | | AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF | | COMBUSTION | | WILL DISCHARGE TO A SAFE LOCATION. | | 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE | | DIRECTED TOWARD | | COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES | | CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR | | COMBUSTIBLE | | DUSTS. | | | | PLEASE PROVIDE DIMENSIONS FROM EACH PART OF THE | | BUILDING INCLUDING THE NEAEEST WINDOWS, DOORS OR VENTS | | AS WELL AS THE PROPERTY LINE. | | | | | | | | 2) SHEET - SITE PLAN - THERE ARE NO DIMENSIONS OF THE | | SIZE OF THE CMU ENCLOSURE | | | | PLEASE PROVIDE DETAILS | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|