2021-06-14 14:58:27COMMERCIAL ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 REPAIRS - PLEASE SHOW THE CORRECT MEASUREMENTS, HEIGHTS
 ETC. TO AVOID INCORRECT PLACEMENT IN THE FIELD - -
 1) PLEASE SHOW THE DOOR WIDTH TO COMPLY WITH FBC
 404.2.3
 2) GRAB BAR HEIGHT SHOULD BE SHOWN AT 36" MAX TO THE
 TOP OF THE GRIPPING SURFACE - FBC 609.4 POSITION OF
 GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
 3) MIRROR MAX HEIGHT SHOULD BE SHOWN TO THE REFLECTIVE
 SURFACE FBC 603.3MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.