2020-12-31 12:30:08 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 20120886 |
| 12/31/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) COVER SHEET: PROVIDE A LIST OF CODES AND STANDARDS |
| USED IN THE DESIGN OF THE PROJECT- SECTION 107.2.1 WPB. |
| |
| 2) SHEETS 1 & 2: REFER TO SECTION 301.1 FBC EX: |
| ALTERATIONS TO EXISTING BUILDINGS SHALL COMPLY WITH ONE |
| OF THE METHODS LISTED IN SECTIONS 301.1.1- 301.1.3. |
| PLEASE INDICATE ON THE PLANS WHICH COMPLIANCE PATH WILL |
| BE USED. FOR THE PURPOSES OF REVIEW AT THIS POINT A |
| LEVEL II ALTERATION IS ASSUMED BASED ON SECTIONS |
| 301.1.2 AND 504.1 FBC EX. PLEASE SEE SECTION 806.1 |
| WHICH STATES ALTERATIONS SHALL COMPLY WITH THE FLORIDA |
| ACCESSIBILITY CODE. UNDER SECTION 202.3 FBC ACC, THE |
| ALTERED SPACE SHALL COMPLY WITH SECTIONS 213.2, |
| 213.3.2, & 213.3.4. IT APPEARS FROM THE DRAWINGS THAT |
| THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER CLOSET |
| (SECTIONS 213.3.2 & 604) IS NOT IN COMPLIANCE. THE |
| REQUIRED CLEAR FLOOR SPACE FOR THE WATER CLOSET IS 60 |
| INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| THE REAR WALL. |
| |
| 3) SHEET 2: PLEASE UPDATE THE REFERENCE TO THE FBC ACC- |
| 1997 SHOWN UNDER GENERAL ADA NOTES, AND PROVIDE THE |
| FOLLOWING COMPLIANCE DETAILS PER THE FBC ACC-2017: |
| |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| WATER CLOSET- SECTION 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| LAVATORY- SECTION 606.2. |
| C) TURNING SPACE DIAMETER- SECTION 304.3. |
| D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| SECTION 604.2. |
| E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| FLOOR- SECTION 604.4. |
| F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| REFLECTIVE SURFACE- SECTION 603.3 |
| G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSET- SECTION 604.5 & 609.4 |
| H) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION |
| 604.6. |
| I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| FROM THE FRONTS OF THE WATER CLOSET- SECTION 604.7. |
| K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| 606.2 |
| |
| 4) SHEET 2: THE TOILET ROOM FINISHES SHALL BE IN |
| COMPLIANCE WITH SECTION 310.3 FBC P, AND SECTION |
| 1210.2.2 FBC B. PLEASE REVIEW AND CORRECT THE NOTE |
| SPECIFYING EPOXY PAINT FINISH. |
| |
| 5) PLEASE NOTE THAT PLUMBING RISER DRAWINGS ARE |
| REQUIRED FOR ALL ALTERATIONS MADE TO THE EXISTING WATER |
| SUPPLY AND SANITARY DRAINAGE SYSTEMS- SECTION |
| 107.3.5.1.3 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |