Plan Review Notes
Plan Review Notes For Permit 20120886
Permit Number 20120886
Review Stop B
Sequence Number 1
Notes
Date Text
2020-12-30 11:02:28BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE OCCUPANCY CLASSIFICATION FOR THE
 UNIT AND THE ADJACENT UNITS PER FBC CHAPTER 3
 2) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE PER FBC
 CHAPTER 6.
 3) PLEASE SHOW THE TOTAL BUILDING SQUARE FOOTING.
 4) PLEASE SHOW THE PREVIOUS OCCUPANCY CLASSIFICATION
 FOR THE UNIT.
 5) PLEASE SHOW THE CODE USED FOR THE DESIGN,
 6) DOES THE TENANT SEPARATION WALL HAVE A FIRE RATING?
 7) PLEASE SHOW THE OCCUPANT LOAD PER FBC 1004.1
 8) DRAWING HAS "ADA NOTES" ON NOTE #7 THE TOILET PAPER
 DISPENSER SHOULD BE PLACED 7 TO 9 INCHES CENTER FROM
 THE FACE OF THE TOILET PER FBC ACCESSIBILITY 604.7
 9) BUILDING APPEARS TO BE IN A FLOOD ZONE - PLEASE
 PROVIDE A OR B - (A) PLEASE PROVIDE THE BUILDING ONLY
 AS IS VALUE FROM PALM BEACH COUNTY PROPERTY APPRAISER
 OR AN INDEPENDENT APPRAISER TO DETERMINE IF THE JOB IS
 A SUBSTANTIAL IMPROVEMENT. (B) IF YOU BELIEVE THAT THE
 BUILDING IS NOT IN A FLOOD ZONE - PLEASE PROVIDE A
 SIGNED AND SEALED SURVEY SHOWING THE BUILDING FLOOD
 ZONE BASED ON THE LATEST FIRM.