2021-02-17 13:50:01 | CODES IN EFFECT |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| |
| ELECTRICAL REVIEW STATUS: FAILED, SAME COMMENTS AS |
| REVIEW #1. |
| |
| 1) DRAWINGS SHOW THREE A/C UNITS, BUT PANEL SCHEDULE |
| ONLY SHOWS ONE UNIT. PLEASE CLARIFY AND CORRECT. FBC |
| 107 |
| 2) AHU SPECS INDICATE A10KW HEATER, BUT LOAD |
| CALCULATIONS AND PANEL SCHEDULE SHOW AN 8.6 KW LOAD. |
| PLEASE CLARIFY AND CORRECT. FBC 107 |
| 3) PLEASE INDICATE CIRCUIT NUMBERS FOR ALL A/C |
| EQUIPMENT ON POWER PLANS AND MATCH THEM TO PANEL |
| SCHEDULE. FBC 107 |
| 4) REVISION #3 INCLUDES THREE PIECES OF EQUIPMENT (H#1, |
| H#2, AND H#3). PLEASE CLARIFY WHAT THEY ARE AND INCLUDE |
| THEM ON YOUR SYMBOLS OR NOTES. IF PART OF THE A/C |
| UNITS, PLEASE INDICATE CIRCUITS FEEDING THEM AND |
| INCLUDE ON PANEL SCHEDULE. FBC 107 |
| 5) A GFI, WP RECEPTABLE BE REQUIRED ON BACK OF UNIT. |
| NEC 210.52 |
| 6) PLEASE SEE SIGNATURE COMMENTS |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |