2021-11-30 14:07:265TH REVIEW FBC-2020 MECHANICAL
 PERMIT-20120803
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M7.1: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON THE OCCUPANCY CLASSIFICATIONS
 FROM 2020FBC M TABLE 403.3.1.1 AND CODE SECTION
 403.3.1.1. THE VENTILATION CALCULATIONS SEEM TO BE A
 MIX BETWEEN FBC M TABLE 403.3.1.1 AND ASHRAE 62.1-2013.
 PLEASE REMOVE ALL PARTS NOT ASSOCIATED WITH FBC M
 403.3.1.1 AS YOU CANNOT MIX BOTH CALCULATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  