Plan Review Notes
Plan Review Notes For Permit 20120803
Permit Number 20120803
Review Stop M
Sequence Number 4
Notes
Date Text
2021-09-21 07:09:104TH REVIEW FBC-2020 MECHANICAL
 PERMIT-20120803
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 THE MECHANICAL REVIEW COULD NOT BE COMPLETED AS THE
 REVISED SHEETS BELOW WERE NOT SUBMITTED.
  
 1) THE REVISED SHEET LOADED UNDER SHEET M2.1.1 IS
 ACTUALLY SHEET M2.1. PLEASE SUBMIT A REVISED SHEET
 M2.1.1.
  
 2) REVISED SHEET M7.1 HAS NOT BEEN SUBMITTED TO SHOW
 THE VENTILATION CALCULATIONS THAT WERE REQUESTED.
  
 3) REVISED SHEET M8.1 WAS NOT SUBMITTED TO SHOW THE
 DETAIL FOR THE INTAKE AIR.
  
 4) REVISED SHEETS M4.1, M4.2 WERE NOT SUBMITTED IN THIS
 CYCLE.
  
 5) THERE IS NO SHEET M4.3
  
  
 PLAN REVIEW RESULTS: DENIED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  