2021-10-04 06:44:29 | 3RD REVIEW FBC-2017 PLUMBING |
| PERMIT-20120803 |
| 10/4/2021 |
| |
| CODES IN EFFECT: |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHT. C.07 - PLACE A NOTE ON THE PLANS THAT SEPARATE |
| PERMITS WILL BE REQUIRE FOR THE BACKFLOW PREVENTERS PER |
| THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL |
| MANUAL. |
| 2) THE ADDRESS OF THE PROJECT MUST BE ON THE PLANS.WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 3) SHT. A-2.1.2 - THE LAUNDRY ROOM #169 SHALL COMPLY |
| WITH ANSI A117.1- 1986 FOR FAIR HOUSING COMPLIANCE.THE |
| WASHER AND DRYER SHALL COMPLY WITH ANSI A117.1 SEC.4.25 |
| FOR CONTROLS AND OPERATING MECHANISMS.THE SINK SHALL |
| COMPLY WITH SEC, 4.19.2.2. |
| 4) PROVIDE A PLUMBING FIXTURE COUNT TABLE AND OCCUPANCY |
| DESIGNATION AND OCCUPANT LOAD FOR EACH OF THE COMMON |
| AREAS BASED ON THE OCCUPANCY AND OCCUPANT LOAD PER |
| TABLE 403.1 OF THE FBC-PLUMBING. |
| 5) SHT. A-2.1.2. - SHOW THE LENGTH AND WIDTH OF ALL THE |
| TOILET STALLS IN THE COMMON AREA TOILET ROOMS. COMPLY |
| WITH FBC-PLUMBING SEC.405.3.1. |
| 6) SHT. A-2.1.2 - A URINAL IS REQUIRED IN THE MEN'S |
| RESTROOM #151 AT THE POOL AREA PER FBC-PLUMBING |
| SEC.403.6 & TABLE 403.6. |
| 7) TOILET PAPER DISPENSERS SHALL COMPLY WITH ANSI |
| A117.1 SEC.4.16.6 AND FIGURE 29 (B). SOAP AND PAPER |
| TOWEL DISPENSERS SHALL COMPLY WITH ANSI A117.1 |
| SEC.4.25. |
| 8) SHT. A-5.5 - POWDER ROOM # A-802 - SHOW THE |
| DIMENSION FROM THE CENTERLINE OF THE WATER CLOSET TO |
| THE WALL ADJACENT TO THE WATER CLOSET. COMPLY WITH ANSI |
| A117.1 SEC. 4.16, 4.17 & FIGURE 228. |
| 9) SHT. A-5.5 - POWDER ROOM #A-802 - SHOW THE REQUIRED |
| CLEAR FLOOR SPACE FOR THE WATER CLOSET ON THE PLAN. |
| COMPLY WITH ONE OF THE CONFIGURATIONS IN FIGURE 28 OF |
| ANSI A117.1 SEC.4.16.2. |
| 10) SHT. A-5.5 - DETAILS #1 & #3 - STATES THE GRAB BARS |
| SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE |
| BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE BOTTOM OF |
| THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 AND FIGURE |
| 29 REQUIRES THE GRAB BARS TO BE MEASURED TO THE |
| CENTERLINE OF THE BAR. |
| 11) SHT. A-5.5 - .ELEVATION DETAILS - SHOW THE |
| DISTANCES OF THE GRAB BARS FROM THE SIDE AND REAR WALLS |
| PER ANSI A 117.1 SEC.4.16.4 & FIGURE 29. |
| 12) SHT. A-8.3 - DETAIL #2 - THE SHOWER BASE SHALL BE |
| PITCHED ONE-QUARTER INCH PER FOOT TOWARD THE DRAIN PER |
| FBC-PLUMBING SEC.417.5.2. |
| 13) SHTS. A-10.1 & A-10.2 - INDICATE ON THE PLANS FOR |
| EACH UNIT WHICH DESIGN SPECIFICATION ("A" OR "B") WAS |
| USED IN THE DESIGN OF THE UNITS. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 14) SHTS. A-10.1, A-10.2, A-10.3, A-10.4 - LAVATORIES |
| THAT ARE LOCATED NEXT TO WATER CLOSETS SHALL HAVE A |
| MAXIMUM DEPTH OF 24 INCHES PER THE FHADM PAGE 7.43. |
| 15) PLACE A NOTE ON THE PLANS THAT THE COMMON AREAS |
| WILL COMPLY WITH ANSI A117.1 - 1986. |
| 16) THERE ARE DUPLICATE SHEETS LABELED A-10.3 AND |
| A-10.4. CLARIFY. |
| 17) SHT. A-10.3 - UNIT B2 - THE DOOR SWINGS INTO THE |
| CLEAR FLOOR SPACE FOR THE LAVATORY IN THE HALL BATH. A |
| 30 INCH BY 48 INCH CLEAR FLOOR SPACE OUTSIDE THE SWING |
| OF THE DOOR AS IT IS CLOSED IS REQUIRED IN THE BATHOOM |
| PER FHADM PAGE 7.39. |
| 18) SHTS. A-10.3 & A-10.4 APPEAR TO BE THE SAME SHEET |
| AND SHEETS A-10.4 & A-10.5 APPEAR TO BE THE SAME. |
| CLARIFY. |
| 19) SHT. P-0.1 - GENERAL NOTE #1 REFERS TO |
| SPECIFICATIONS. JOB SPECIFICATIONS HAVE NOT BEEN |
| SUBMITTED WITH THESE PLANS. CLARIFY. |
| 20) SHT.P-2.1 - KEYNOTE #6 - LIST THE SPECIFIC CIVIL |
| DRAWING NUMBER FOR THE CONTINUATION OF THE WATER MAIN. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| 21) SHT. P-2.1 - THERE ARE CIRCLES ON THE PLAN THAT |
| APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND |
| RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1, |
| MEN'S RESTROOM #A-117, BISTRO BAR, AND MAIL |
| ROOM.CLARIFY. |
| 22) SHT. P-2.1 APPEARS TO SHOW A RISER IN STAIR #2. |
| THIS IS NOT PERMITTED PER FBC-BUILDING SEC.1023.5. |
| CLARIFY. |
| 23) SHT. P-2.1.1 - PROVIDE MATCH LINES FOR THE PLAN AND |
| LIST THE SPECIFIC CIVIL DRAWINGS FOR THE CONTINUATION |
| OF THE STORM DRAINS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 24) SHT. P-2.2 - THERE ARE CIRCLES ON THE PLAN THAT |
| APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND |
| RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1, |
| B1- MOD, ND THE BRIDGE AREA. THERE APPEARS TO BE A |
| RISER IN STAIR #2. THIS IS NOT PERMITTED PER |
| FBC-BUILDING SEC.1023.5. CLARIFY.THESE ISSUES APPEAR TO |
| OCCUR ON ALL LEVELS. CLARIFY. |
| 25) SHT. P-2.6 - IDENTIFY THE UNITS ON THE FLOOR |
| PLAN.WPB AMEND. TO FBC SEC. 107.2.1. |
| 26) SHT. P-2.1 - SHOWS A JANITOR ROOM #167 BY STAIR #3 |
| AND THE SAME ROOM IS SHOWN AS STAFF TOILET ROOM #170 ON |
| SHT. A-2.1. CLARIFY. |
| 27) SHT.P-2.1 SHOWS A 2 INCH WATER SUPPLY BRANCH TO |
| MEN'S TOILET ROOM # A-117 & SHT. P-4.1 SHOWS A 1 1/2 |
| INCH WATER SUPPLY BRANCH. CLARIFY. |
| 28) SHT. P-4.2 SHOWS A FLOOR PLAN FOR UNIT C2. I COULD |
| NOT FIND THIS UNIT ON ANY OF THE FLOOR PLANS. LARIFY. |
| 29) SHT. P-4.1 - CLEARLY IDENTIFY/ LABEL THE RESTROOMS |
| ON DETAIL 1/P-4.2. NOTE: THIS DETAIL IS ON SHT. P-4.1, |
| NOT P-4.2. CLARIFY. |
| 30) SHT.P-5.1 - RISER 5/S - AIR ADMITTANCE VALVES |
| CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED |
| MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE |
| STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A |
| RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK |
| VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER |
| FBC-PLUMBING SEC. 918.3.1. |
| 31) SHT. P-5.2 - RISER 10/S - AIR ADMITTANCE VALVES |
| CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED |
| MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE |
| STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A |
| RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK |
| VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER |
| FBC-PLUMBING SEC. 918.3.1. |
| 32) SHT. P-5.2 - SANITARY AND WATER RISERS - |
| IDENTIFY/LABEL EACH RISER WITH THE SPECIFIC RESTROOM |
| NUMBER AND AREA. WPB AMEND. TO FBC SEC. 107.2.1. |
| 33) SHT. P-8.1-SHT. P-8.1 - SUBMIT APPROVED ASSEMBLY |
| DETAILS FOR THE FIRESTOP PENETRATION DETAILS.SUBMIT THE |
| MANUFACTURER'S INFORMATION AND THE APPROVED LISTING |
| NUMBERS. WPB AMEND. TO FBC SEC. 107.3.5.1.1. |
| 34) SHT. P-8.1 - SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE SUB-METERS. IF THE METERS WILL BE LOCATED IN A |
| RETURN AIR CLOSET THEY SHALL MEET THE FLAME SPREAD |
| INDEX AND SMOKE-DEVELOPED INDEX OF SEC. 602.2.1 OF THE |
| FBC-MECHANICAL AND THE TEST CRITERIA OF ASTM E84 OR UL |
| 723. |
| 35) SHT. P-8.1 - CLARIFY WHAT TYPE OF EFFLUENT WILL BE |
| DISCHARGING FROM THE POOL EQUIPMENT INTO THE SANITARY |
| SYSTEM. POOL WATER SHALL NOT BE DISCHARGED TO THE |
| SANITARY SYSTEM PER CITY OF WEST PALM BEACH CODE OF |
| ORDINANCES CHAPTER 90, ARTICLE III, SSEC.90-126 (B)(5) |
| UNLESS SSPECIFICALLY AUTHORIZED BY THE CITY IN WRITING. |
| 36) SSHT. P-8.1 - PIPE HANGER DETAIL - PIPE SHALL BE |
| SUPPORTED IN ACCORDANCE WITH FBC-PLUMBING SEC.308 AND |
| TABLE 308.5. |
| 37) SUBMIT A COMPLETE UNDERGROUND SANITARY RISER DETAIL |
| SHOWING ALL RISER CONNECTIONS, PIPE SIZES, VENTS, |
| ETC.WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| 38) SHT. A-7.6 - SANITATION UNIT DETAIL - A REDUCED |
| PRESSURE BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED |
| ON THE TRASH CHUTE WATER LINE PER FBC-PLUMBING |
| 608.13.2. |
| 39) THE WASHING MACHINE WATER SUPPLY VALVES SHALL BE |
| PROVIDED WITH ACCESS WITHOUT MOVING THE UNIT. SHOW THE |
| LOCATION OF THE VALVES ON THE PLANS. FBC-PLUMBING SEC. |
| 606.3. |
| 40) SUBMIT SANITARY AND WATER RISERS FOR ALL THE COMMON |
| AREA PLUMBING FIXTURES AND TOILET ROOMS. WPB AMEND. TO |
| FBC SEC. 107.3.5.1.3. |
| 41) THE WATER SUPPLY TO DISHWASHERS AND ICEMAKERS SHALL |
| BE PROTECTED AGAINST BACKFLOW PER FBC-PLUMBING |
| SEC.608..2. THE BACKFLOW DEVICE SHALL COMPLY WITH ASSE |
| 1024. |
| 42) SUBMIT A PIPING DETAIL FOR THE DOMESTIC BOOSTER |
| SYSTEM AND SUBMIT WATER RISER DIAGAM FOR THE MAIN WATER |
| SYSTEM IN THE BUILDING. WPB AMEND. TO FBC SEC. |
| 107.3.5.1.3. |
| 43) PRESSURE REDUCING VALVES ARE REQUIRED ON THE WATER |
| DISTRIBUTION SYSTEM WHERE THE WATER PRESSSURE WITHIN A |
| BUILDING EXCEEDS 80 PSI STATIC.WATER PRESURE REDUCING |
| VALVES SHALL CONFORM TO ASSE 1003 OR CSA B356. WATER |
| PRESURE REDUCING VALVES, REGULATORS AND TRAINERS SHALL |
| BE SO CONSTRUCTED AND INSTALLED AS TO PERMIT REPAIR OR |
| REMOVAL OF PARTS WITHOUT BREAKING A PIPELINE OR |
| REMOVING THE VALVE AND TRAINER FROM THE PIPELINE PER |
| FBC SECS.604.8, 604.8.2. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |