2021-10-04 06:44:293RD REVIEW FBC-2017 PLUMBING
 PERMIT-20120803
 10/4/2021
  
 CODES IN EFFECT:
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHT. C.07 - PLACE A NOTE ON THE PLANS THAT SEPARATE
 PERMITS WILL BE REQUIRE FOR THE BACKFLOW PREVENTERS PER
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL.
 2) THE ADDRESS OF THE PROJECT MUST BE ON THE PLANS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) SHT. A-2.1.2 - THE LAUNDRY ROOM #169 SHALL COMPLY
 WITH ANSI A117.1- 1986 FOR FAIR HOUSING COMPLIANCE.THE
 WASHER AND DRYER SHALL COMPLY WITH ANSI A117.1 SEC.4.25
 FOR CONTROLS AND OPERATING MECHANISMS.THE SINK SHALL
 COMPLY WITH SEC, 4.19.2.2.
 4) PROVIDE A PLUMBING FIXTURE COUNT TABLE AND OCCUPANCY
 DESIGNATION AND OCCUPANT LOAD FOR EACH OF THE COMMON
 AREAS BASED ON THE OCCUPANCY AND OCCUPANT LOAD PER
 TABLE 403.1 OF THE FBC-PLUMBING.
 5) SHT. A-2.1.2. - SHOW THE LENGTH AND WIDTH OF ALL THE
 TOILET STALLS IN THE COMMON AREA TOILET ROOMS. COMPLY
 WITH FBC-PLUMBING SEC.405.3.1.
 6) SHT. A-2.1.2 - A URINAL IS REQUIRED IN THE MEN'S
 RESTROOM #151 AT THE POOL AREA PER FBC-PLUMBING
 SEC.403.6 & TABLE 403.6.
 7) TOILET PAPER DISPENSERS SHALL COMPLY WITH ANSI
 A117.1 SEC.4.16.6 AND FIGURE 29 (B). SOAP AND PAPER
 TOWEL DISPENSERS SHALL COMPLY WITH ANSI A117.1
 SEC.4.25.
 8) SHT. A-5.5 - POWDER ROOM # A-802 - SHOW THE
 DIMENSION FROM THE CENTERLINE OF THE WATER CLOSET TO
 THE WALL ADJACENT TO THE WATER CLOSET. COMPLY WITH ANSI
 A117.1 SEC. 4.16, 4.17 & FIGURE 228.
 9) SHT. A-5.5 - POWDER ROOM #A-802 - SHOW THE REQUIRED
 CLEAR FLOOR SPACE FOR THE WATER CLOSET ON THE PLAN.
 COMPLY WITH ONE OF THE CONFIGURATIONS IN FIGURE 28 OF
 ANSI A117.1 SEC.4.16.2.
 10) SHT. A-5.5 - DETAILS #1 & #3 - STATES THE GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE BOTTOM OF
 THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 AND FIGURE
 29 REQUIRES THE GRAB BARS TO BE MEASURED TO THE
 CENTERLINE OF THE BAR.
 11) SHT. A-5.5 - .ELEVATION DETAILS - SHOW THE
 DISTANCES OF THE GRAB BARS FROM THE SIDE AND REAR WALLS
 PER ANSI A 117.1 SEC.4.16.4 & FIGURE 29.
 12) SHT. A-8.3 - DETAIL #2 - THE SHOWER BASE SHALL BE
 PITCHED ONE-QUARTER INCH PER FOOT TOWARD THE DRAIN PER
 FBC-PLUMBING SEC.417.5.2.
 13) SHTS. A-10.1 & A-10.2 - INDICATE ON THE PLANS FOR
 EACH UNIT WHICH DESIGN SPECIFICATION ("A" OR "B") WAS
 USED IN THE DESIGN OF THE UNITS. WPB AMEND. TO FBC SEC.
 107.2.1.
 14) SHTS. A-10.1, A-10.2, A-10.3, A-10.4 - LAVATORIES
 THAT ARE LOCATED NEXT TO WATER CLOSETS SHALL HAVE A
 MAXIMUM DEPTH OF 24 INCHES PER THE FHADM PAGE 7.43.
 15) PLACE A NOTE ON THE PLANS THAT THE COMMON AREAS
 WILL COMPLY WITH ANSI A117.1 - 1986.
 16) THERE ARE DUPLICATE SHEETS LABELED A-10.3 AND
 A-10.4. CLARIFY.
 17) SHT. A-10.3 - UNIT B2 - THE DOOR SWINGS INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY IN THE HALL BATH. A
 30 INCH BY 48 INCH CLEAR FLOOR SPACE OUTSIDE THE SWING
 OF THE DOOR AS IT IS CLOSED IS REQUIRED IN THE BATHOOM
 PER FHADM PAGE 7.39.
 18) SHTS. A-10.3 & A-10.4 APPEAR TO BE THE SAME SHEET
 AND SHEETS A-10.4 & A-10.5 APPEAR TO BE THE SAME.
 CLARIFY.
 19) SHT. P-0.1 - GENERAL NOTE #1 REFERS TO
 SPECIFICATIONS. JOB SPECIFICATIONS HAVE NOT BEEN
 SUBMITTED WITH THESE PLANS. CLARIFY.
 20) SHT.P-2.1 - KEYNOTE #6 - LIST THE SPECIFIC CIVIL
 DRAWING NUMBER FOR THE CONTINUATION OF THE WATER MAIN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 21) SHT. P-2.1 - THERE ARE CIRCLES ON THE PLAN THAT
 APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND
 RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1,
 MEN'S RESTROOM #A-117, BISTRO BAR, AND MAIL
 ROOM.CLARIFY.
 22) SHT. P-2.1 APPEARS TO SHOW A RISER IN STAIR #2.
 THIS IS NOT PERMITTED PER FBC-BUILDING SEC.1023.5.
 CLARIFY.
 23) SHT. P-2.1.1 - PROVIDE MATCH LINES FOR THE PLAN AND
 LIST THE SPECIFIC CIVIL DRAWINGS FOR THE CONTINUATION
 OF THE STORM DRAINS. WPB AMEND. TO FBC SEC. 107.2.1.
 24) SHT. P-2.2 - THERE ARE CIRCLES ON THE PLAN THAT
 APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND
 RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1,
 B1- MOD, ND THE BRIDGE AREA. THERE APPEARS TO BE A
 RISER IN STAIR #2. THIS IS NOT PERMITTED PER
 FBC-BUILDING SEC.1023.5. CLARIFY.THESE ISSUES APPEAR TO
 OCCUR ON ALL LEVELS. CLARIFY.
 25) SHT. P-2.6 - IDENTIFY THE UNITS ON THE FLOOR
 PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 26) SHT. P-2.1 - SHOWS A JANITOR ROOM #167 BY STAIR #3
 AND THE SAME ROOM IS SHOWN AS STAFF TOILET ROOM #170 ON
 SHT. A-2.1. CLARIFY.
 27) SHT.P-2.1 SHOWS A 2 INCH WATER SUPPLY BRANCH TO
 MEN'S TOILET ROOM # A-117 & SHT. P-4.1 SHOWS A 1 1/2
 INCH WATER SUPPLY BRANCH. CLARIFY.
 28) SHT. P-4.2 SHOWS A FLOOR PLAN FOR UNIT C2. I COULD
 NOT FIND THIS UNIT ON ANY OF THE FLOOR PLANS. LARIFY.
 29) SHT. P-4.1 - CLEARLY IDENTIFY/ LABEL THE RESTROOMS
 ON DETAIL 1/P-4.2. NOTE: THIS DETAIL IS ON SHT. P-4.1,
 NOT P-4.2. CLARIFY.
 30) SHT.P-5.1 - RISER 5/S - AIR ADMITTANCE VALVES
 CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED
 MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE
 STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A
 RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK
 VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER
 FBC-PLUMBING SEC. 918.3.1.
 31) SHT. P-5.2 - RISER 10/S - AIR ADMITTANCE VALVES
 CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED
 MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE
 STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A
 RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK
 VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER
 FBC-PLUMBING SEC. 918.3.1.
 32) SHT. P-5.2 - SANITARY AND WATER RISERS -
 IDENTIFY/LABEL EACH RISER WITH THE SPECIFIC RESTROOM
 NUMBER AND AREA. WPB AMEND. TO FBC SEC. 107.2.1.
 33) SHT. P-8.1-SHT. P-8.1 - SUBMIT APPROVED ASSEMBLY
 DETAILS FOR THE FIRESTOP PENETRATION DETAILS.SUBMIT THE
 MANUFACTURER'S INFORMATION AND THE APPROVED LISTING
 NUMBERS. WPB AMEND. TO FBC SEC. 107.3.5.1.1.
 34) SHT. P-8.1 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE SUB-METERS. IF THE METERS WILL BE LOCATED IN A
 RETURN AIR CLOSET THEY SHALL MEET THE FLAME SPREAD
 INDEX AND SMOKE-DEVELOPED INDEX OF SEC. 602.2.1 OF THE
 FBC-MECHANICAL AND THE TEST CRITERIA OF ASTM E84 OR UL
 723.
 35) SHT. P-8.1 - CLARIFY WHAT TYPE OF EFFLUENT WILL BE
 DISCHARGING FROM THE POOL EQUIPMENT INTO THE SANITARY
 SYSTEM. POOL WATER SHALL NOT BE DISCHARGED TO THE
 SANITARY SYSTEM PER CITY OF WEST PALM BEACH CODE OF
 ORDINANCES CHAPTER 90, ARTICLE III, SSEC.90-126 (B)(5)
 UNLESS SSPECIFICALLY AUTHORIZED BY THE CITY IN WRITING.
 36) SSHT. P-8.1 - PIPE HANGER DETAIL - PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC-PLUMBING SEC.308 AND
 TABLE 308.5.
 37) SUBMIT A COMPLETE UNDERGROUND SANITARY RISER DETAIL
 SHOWING ALL RISER CONNECTIONS, PIPE SIZES, VENTS,
 ETC.WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 38) SHT. A-7.6 - SANITATION UNIT DETAIL - A REDUCED
 PRESSURE BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED
 ON THE TRASH CHUTE WATER LINE PER FBC-PLUMBING
 608.13.2.
 39) THE WASHING MACHINE WATER SUPPLY VALVES SHALL BE
 PROVIDED WITH ACCESS WITHOUT MOVING THE UNIT. SHOW THE
 LOCATION OF THE VALVES ON THE PLANS. FBC-PLUMBING SEC.
 606.3.
 40) SUBMIT SANITARY AND WATER RISERS FOR ALL THE COMMON
 AREA PLUMBING FIXTURES AND TOILET ROOMS. WPB AMEND. TO
 FBC SEC. 107.3.5.1.3.
 41) THE WATER SUPPLY TO DISHWASHERS AND ICEMAKERS SHALL
 BE PROTECTED AGAINST BACKFLOW PER FBC-PLUMBING
 SEC.608..2. THE BACKFLOW DEVICE SHALL COMPLY WITH ASSE
 1024.
 42) SUBMIT A PIPING DETAIL FOR THE DOMESTIC BOOSTER
 SYSTEM AND SUBMIT WATER RISER DIAGAM FOR THE MAIN WATER
 SYSTEM IN THE BUILDING. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 43) PRESSURE REDUCING VALVES ARE REQUIRED ON THE WATER
 DISTRIBUTION SYSTEM WHERE THE WATER PRESSSURE WITHIN A
 BUILDING EXCEEDS 80 PSI STATIC.WATER PRESURE REDUCING
 VALVES SHALL CONFORM TO ASSE 1003 OR CSA B356. WATER
 PRESURE REDUCING VALVES, REGULATORS AND TRAINERS SHALL
 BE SO CONSTRUCTED AND INSTALLED AS TO PERMIT REPAIR OR
 REMOVAL OF PARTS WITHOUT BREAKING A PIPELINE OR
 REMOVING THE VALVE AND TRAINER FROM THE PIPELINE PER
 FBC SECS.604.8, 604.8.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW