2021-09-30 12:32:02 | NEW 8 STORY APT AND 6 STORY PARKING GARAGE |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE SHOW THE ROOM "USE" FOR THE ROOMS MARKED |
| G105, G104, G102, 167 ON THE FLOOR PLAN. |
| |
| 2) PLEASE REVISE THE LIFE SAFETY PLANS - TO MATCH THE |
| REVISED FLOOR PLANS PROVIDED. |
| |
| 3) BUILDING IS NOT CONSIDERED A HIGHRISE - UNIT MARKED |
| ST-1 AND ST-1 MOD - THE SLEEPING ROOM REQUIRES AN |
| EMERGENCY EXIT. FBC 1030.1 |
| |
| 4) CAR CHARGING STATIONS FOR THE PARKING ARE SHOWN ON |
| THE ELECTRICAL DRAWINGS BUT NOT ON THE ARCHITECTURAL |
| FLOOR PLAN. ELECTRIC VEHICLE CHARGING STATIONS ARE |
| BEING INSTALLED - PLEASE SHOW THAT AT LEAST 1 OF THE |
| CHARGING STATIONS IS A MARKED ACCESSIBLE PARKING SPACE, |
| ACCESS AISLE, SIGNAGE ETC. ALLOWING ACCESS TO THE |
| CHARGER - PER FBC 502 |
| |
| 5) ARCHITECT NEEDS TO SPECIFY HOW THE WALLS BETWEEN |
| UNITS AND SERVICE OR CORRIDOR AREA MEET THE |
| REQUIREMENTS OF FBC 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN |
| TESTED IN ACCORDANCE WITH ASTM E90. PENETRATIONS OR |
| OPENINGS IN CONSTRUCTION ASSEMBLIES FOR PIPING; |
| ELECTRICAL DEVICES; RECESSED CABINETS; BATHTUBS; |
| SOFFITS; OR HEATING, VENTILATING OR EXHAUST DUCTS SHALL |
| BE SEALED, LINED, INSULATED OR OTHERWISE TREATED TO |
| MAINTAIN THE REQUIRED RATINGS. |
| |
| 6) THE ONLY CALCULATIONS FOR THE OPEN GARAGE |
| VENTILATION PROVIDE ARE FOR THE 1ST FLOOR - THE |
| PERCENTAGES ARE NOT SHOWN. PLEASE PROVIDE THE |
| CALCULATIONS FOR THE OPEN GARAGE PER FBC 406.5.2 FOR |
| NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF THE |
| STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS ON |
| TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN |
| EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20 |
| PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER. |
| THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE |
| PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40 |
| PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS |
| SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY |
| DISTRIBUTED OPENINGS. |
| |
| 7) DRAWING A-4.8 - THE FINISH SCHEDULE NEEDS TO SHOW |
| THE COMMON RESTROOM WALL FINISH TO COMPLY WITH (DRYWALL |
| IS NOT CONSIDERED A HARD SURFACE) 1210.2.2 WALLS AND |
| PARTITIONS. |
| WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| MOISTURE. |
| |
| 8) DRAWING A-4.8 CANNOT HAVE A WOOD BASEBOARD IN THE |
| COMMON RESTROOMS - FBC 1210.2.1 FLOORS AND WALL BASES. |
| IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND |
| SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH |
| FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE |
| WALLS NOT LESS THAN 4 INCHES (102 MM). |
| |
| |
| |
| |
| |
| |
| |