2021-06-14 09:31:22 | 1) SHT. C.07 - PLACE A NOTE ON THE PLANS THAT SEPARATE |
| PERMITS WILL BE REQUIRE FOR THE BACKFLOW PREVENTERS PER |
| THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL |
| MANUAL. |
| 2) THIS BUILDING WAS DESIGNED UNDER THE FAIR HOUSING |
| ACT DESIGN MANUAL-1998. INDICATE ON THE PLANS FOR EACH |
| UNIT WHICH DESIGN SPECIFICATION ("A" OR "B") WAS USED |
| IN THE DESIGN OF THE UNITS. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 3) THE ADDRESS OF THE PROJECT MUST BE ON THE PLANS.WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 4) SHT. A-2.1.2 - THE B1 UNITS DO NOT SHOW ANY |
| LAVATORIES OR WATER CLOSETS ON THE FLOOR PLAN. THIS |
| SEEMS TO APPEAR ON ALL LEVELS.CLARIFY. |
| 5) SHT. A-2.1.2 - THE LAUNDRY ROOM #169 SHALL COMPLY |
| WITH ANSI A117.1- 1986 FOR FAIR HOUSING COMPLIANCE.THE |
| WASHER AND DRYER SHALL COMPLY WITH ANSI A117.1 SEC.4.25 |
| FOR CONTROLS AND OPERATING MECHANISMS.THE SINK SHALL |
| COMPLY WITH SEC, 4.19.2.2. |
| 6) PROVIDE A PLUMBING FIXTURE COUNT TABLE AND OCCUPANCY |
| DESIGNATION AND OCCUPANT LOAD FOR EACH OF THE COMMON |
| AREAS BASED ON THE OCCUPANCY AND OCCUPANT LOAD PER |
| TABLE 403.1 OF THE FBC-PLUMBING. |
| 7) SHT. A-2.1.2 - THE NOTE AT THE TOP OF THE SHEET |
| STATES " REFER TO PARTIAL PLAN SHEET A-2.1.2 FOR |
| INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON |
| A-2.1.2. CLARIFY. |
| 8) SUBMIT ENLARGED TOILET ROOM FLOOR PLANS FOR ALL THE |
| COMMON AREA TOILET ROOMS SHOWING THE REQUIRED CLEAR |
| FLOOR SPACES FOR ALL HANDICAPPED FIXTURES. ALSO, SHOW |
| THE CLEAR INSIDE DIMENSONS (L X W) OF EACH TOILET |
| ROOM.CLEARANCES FOR WATER CLOSETS SHALL COMPLY WITH |
| ANSI A117.1 SEC.4.16.COMPLY WITH ANSI A117.1-1986. |
| 9) SHT. SHT. A-2.2.2 - THE DOORS TO TOILET ROOMS A-109 |
| & A-110 APPEAR TO SWING INTO THE CLEAR FLOOR SPACE FOR |
| THE LAVATORIES. COMPLY WITH ANSI A117.1-1986 |
| SEC.4.22.2. |
| 10) SHT. A-2.1.1 - THE NOTE AT THE BOTTOM OF THE SHEET |
| STATES " REFER TO PARTIAL PLAN SHEET A-2.1.1 FOR |
| INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON |
| A-2.1.1. CLARIFY. |
| 11) SHT. A-2.1.2. - SHOW THE LENGTH AND WIDTH OF ALL |
| THE TOILET STALLS IN THE COMMON AREA TOILET ROOMS. |
| COMPLY WITH FBC-PLUMBING SEC.405.3.1. |
| 12) SHT. A-2.1.2 - THE WALL SURFACE AROUND THE MOP |
| SINKS SHALL COMPLY WITH FBC-BUILDING SEC. 1210.2.2. |
| 13) A MINIMUM OF 2 DRINKING FOUNTAINS WILL BE REQUIRED |
| FOR THE FITNESS CENTER PER AND POSSIBLY OTHER AMENITY |
| AREAS.FBC-PLUMBING TABLE 403.1 & SEC.410.3. |
| 14) SHT. A-2.1.2 - A URINAL IS REQUIRED IN THE MEN'S |
| RESTROOM #151 AT THE POOL AREA PER FBC-PLUMBING |
| SEC.403.6 & TABLE 403.6. |
| 15) SHT. A-2.1.2 - ALL SINKS LOCATED IN THE COMMON |
| AREAS SHALL COMPLY WITH ANSI A117.1 SEC.4.19.2.2, |
| 4.19.3, 4.19.4, 4.19.5. |
| 16) SHT.A-2.2.1- THE NOTE AT THE BOTTOM OF THE SHEET |
| STATES " REFER TO PARTIAL PLAN SHEET A-2.2.1 FOR |
| INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON |
| A-2.2.1. CLARIFY. |
| 17) THE DOOR IN THE C1 UNIT HALL BATH APPEARS TO SWING |
| INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY IF THAT IS |
| DESIGNED AS THE ADAPTABLE BATHROOM. COMPLY WITH FHADM |
| (FAIR HOUSING ACT DESIGN MANUAL) PAGE 7.39.THIS APPLIES |
| TO ALL LEVELS. CLARIFY. |
| 18) UNIT C1 - THE SHOWER DOOR IN THE MASTER BATH SWINGS |
| INTO THE CLEAR FLOOR SPACE FOR THE SHOWER AND APPEARS |
| TO PREVENT THE ACCESS TO THE CONTROLS IF THIS IS THE |
| ADAPTABLE/USABLE BATHROOM. COMPLY WITH FHADM PAGE |
| 7.56.THIS APPLIES TO ALL LEVELS. |
| 19) UNIT C1 - THE HALL BATH IS MISSING THE WATER |
| CLOSET, LAVATORY AND SHOWER ON THE FLOOR PLANS. THIS |
| APPEARS TO OCCUR ON ALL LEVELS.CLARIFY. |
| 20) UNIT ST1 & ST1 MOD - THE DOORS IN THE BATHROOMS |
| APPEAR TO SWING INTO THE CLEAR FLOOR SPACE FOR THE |
| LAVATORY.COMPLY WITH FHADM PAGE 7.39. |
| 21) UNITS B1 & B1 MOD - IF THE MASTER BATH IS THE FHA |
| COMPLIANT BATHROOM, THE LENGTH OF THE SHOWER WALL |
| ADJACENT TO THE WATER CLOSET SHALL NOT EXCEED 24 INCHES |
| IN LENGTH AND MUST BE AT LEAST 33 INCHES FROM THE |
| OPPOSITE WALL PER THE FHADM PAGE 7.43 & 7.44. |
| 22) UNIT B2 - IF THE MASTER BATH IS THE FHA COMPLIANT |
| BATHROOM, THE LENGTH OF THE WALLS ADJACENT TO THE WATER |
| CLOSET SHALL NOT EXCEED 24 INCHES PER THE FHADM PAGE |
| 7.43 & 7.44.ALSO, SHOW THE CLEAR FLOOR PACE FOR THE |
| WATER CLOSET PER THE FHADM PAGE 7.43. |
| 23) SHT. A-4.8 - THE ROOM FINISH SCHEDULE FOR THE |
| COMMON AREAS IS BLANK. CLARIFY. |
| 24) SHT. A-2.3 - THE NAMING CONVENTION FOR THE PLAN |
| NOTES THAT IT IS FOR LEVELS 3 TO 5 BUT THE PLAN STATES |
| IT IS FOR LEVEL 3 ONLY. CLARIFY. |
| 25) SHT. A-2.3.1 - THE NOTE AT THE BOTTOM OF THE SHEET |
| STATES " REFER TO PARTIAL PLAN SHEET A-2.3.1 FOR |
| INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON |
| A-2.3.1. CLARIFY. |
| 26) SHT.A-2.3.2 - THE NOTE AT THE TOP OF THE SHEET |
| STATES " REFER TO PARTIAL PLAN SHEET A-2.3.2 FOR |
| INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON |
| A-2.3.2. CLARIFY. |
| 27) SHT. A-2.4.1 - THE NOTE AT THE BOTTOM OF THE SHEET |
| STATES " REFER TO PARTIAL PLAN SHEET A-2.3.1 FOR |
| INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON |
| A-2.3.1. CLARIFY. |
| 28) SHT. A-2.4.2 - THE NOTE ON THE TOP OF THE SHEET |
| STATES " REFER TO PARTIAL PLAN SHEET A-2.3.2 FOR |
| INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON |
| SHEET A2.3.2. CLARIFY. |
| 29) SHT. A-2.5.1- THE NOTE ON THE BOTTOM OF THE SHEET |
| STATES "" REFER TO PARTIAL PLAN SHEET A-2.3.1 FOR |
| INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON |
| A-2.3.1. CLARIFY. |
| 30) SHT .A-2.5.2 - THE NOTE ON THE TOP OF THE PLAN |
| REFERS TO A PARTIAL PLAN ON SHT. A-2.3.2. THERE IS NO |
| PARTIAL PLAN ON A-2.3.2. CLARIFY. |
| 31) SHT. A-2.6.1 - THE NOTE ON THE BOTTOM OF THE PAGE |
| REFERS TO PARTIAL PLAN SHEET A-2.4.1.SHT A-2.4.1 IS FOR |
| LEVEL 4 AND SHT. A-2.6.1 IS FOR LEVEL 6. CLARIFY. |
| 32) SHT. A-2.6.2 - THE NOTE ON THE TOP OF THE PLAN |
| REFERS TO A PARTIAL PLAN ON SHT. A-2.4.2. THERE IS NO |
| PARTIAL PLAN ON A-2.4.2. ALSO, SHT. A-2.6.2 IS FOR |
| LEVEL 6 AND SHT. A-2.4.2 IS FOR LEVEL 4.CLARIFY. |
| 33) SHT. A-2.7.1 - THE NOTE ON THE BOTTOM OF THE PLAN |
| REFERS TO A PARTIAL PLAN ON SHT.A-2.5.1.THERE IS NO |
| PARTIAL PLAN ON SHT. A-2.5.1. ALSO, SHT. A-2.5.1 IS FOR |
| LEVEL 5 AND SHT. A-2.7.1 IS FOR LEVEL 7. CLARIFY. |
| 34) SHT. A-2.8.1 - THE NOTE ON THE BOTTOM OF THE PLAN |
| REFERS TO A PARTIAL PLAN ON SHT.A-2.6.1.THERE IS NO |
| PARTIAL PLAN ON SHT. A-2.6.1. ALSO, SHT. A-2.6.1 IS FOR |
| LEVEL 6 AND SHT. A-2.8.1 IS FOR LEVEL 8. CLARIFY. |
| 35) SHT. A-2.8.2 - THE NOTE ON THE TOP OF THE PLAN |
| REFERS TO A PARTIAL PLAN ON SHT. A-2.6.2. THERE IS NO |
| PARTIAL PLAN ON SHT. A-2.6.2. ALSO, SHT. A-2.6.2 IS FOR |
| LEVEL 6 AND SHT. A-2.8.2 IS FOR LEVEL 8. CLARIFY. |
| 36) SHT. A-2.9.1 - THE NOTE ON THE TOP OF THHE SHEET |
| REFERS TO A PARTIAL PLANON SHT. A-2.7.2. THERRE IS NO |
| PARTIAL PLAN ON A-2.7.2. ALSO, SHT. A-2.7.2 IS FOR |
| LEVEL 7 AND SHT. A-2.9.1 IS FOR THE ROOF LEVEL. |
| CLARIFY. |
| 37) SUBMIT THE INTERIOR ELEVATION DESIGNATIONS FOR THE |
| DWELLING UNITS AS SHOWN ON THE FLOOR PLANS FOR THE |
| UNITS ON SHEETS A-4.1, A-4.2, A-4.3 & A-4.4. SHOW THE |
| HEIGHT DIMENSIONS OF THE KITCHEN AND BATHROOM CABINETS |
| FROM THE FLOOR TO THE TOP OF THE COUNTER.WPB AMEND. TO |
| FBC SEC. 107.2.1, FHADM PAGE 7.15 & 7.52. |
| 38) SHT. A-5.1 - POWDER ROOM #A-111 - SHOW THE REQUIRED |
| CLEAR FLOOR SPACES FOR THE WATER CLOSET AND THE |
| LAVATORY. COMPLY WITH ANSI A117.1-86 SECTIONS 4.16.2 & |
| 4.19.3. |
| 39) SHT. A-5.1- POWDER ROOM #A-111 - THE DOOR TO THE |
| TOILET ROOM APPEARS TO SWING INTO THE CLEAR FLOOR SPACE |
| FOR THE LAVATORY.THE DOOR TO THE TOILET ROOM CANNOT |
| SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY |
| FIXTURE UNLESS SUFFICIENT MANEUVERING SPACE WITHIN THE |
| ROOM FOR A PERSON USING A WHEELCHAIR TO ENTER AND CLOSE |
| THE DOOR, USE THE FIXTURES, REOPEN THE DOOR, AND EXIT. |
| CLEARLY SHOW THIS REQUIRED MANEUVERING SPACE INSIDE THE |
| TOILET ROOM.ANSI A117.1 SEC.4.22.2. |
| 40) SHT. A-5.1 - TOILET ROOMS # 109 & 110 - THE DOOR TO |
| THE TOILET ROOM APPEARS TO SWING INTO THE CLEAR FLOOR |
| SPACE FOR THE LAVATORY.THE DOOR TO THE TOILET ROOM |
| CANNOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR |
| ANY FIXTURE UNLESS SUFFICIENT MANEUVERING SPACE WITHIN |
| THE ROOM FOR A PERSON USING A WHEELCHAIR TO ENTER AND |
| CLOSE THE DOOR, USE THE FIXTURES, REOPEN THE DOOR, AND |
| EXIT. CLEARLY SHOW THIS REQUIRED MANEUVERING SPACE |
| INSIDE THE TOILET ROOM. ANSI A117.1 SEC.4.22.2. |
| 41) SHT. A-5.1 - TOILET ROOMS #109 & 110 SHALL BE |
| GENDER SPECIFIC (MALE & FEMALE) PER FBC-PLUMBING SEC. |
| 403.2. |
| 42) SHT. A-5.1 - DETAILS #1, #2, & #3 STATES THE GRAB |
| BARS SHALL BE MEASURED TO THE TOP OF THE GRIPPING |
| SURFACE BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE |
| BOTTOM OF THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 |
| AND FIGURE 29 REQUIRES THE GRAB BARS TO BE MEASURED TO |
| THE CENTERLINE OF THE BAR. |
| 43) SHT. A-5.3 - STAFF TOILET ROOMS #170 & 111- THE |
| DOOR TO THE TOILET ROOM APPEARS TO SWING INTO THE CLEAR |
| FLOOR SPACE FOR THE LAVATORY.THE DOOR TO THE TOILET |
| ROOM CANNOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED |
| FOR ANY FIXTURE UNLESS SUFFICIENT MANEUVERING SPACE |
| WITHIN THE ROOM FOR A PERSON USING A WHEELCHAIR TO |
| ENTER AND CLOSE THE DOOR, USE THE FIXTURES, REOPEN THE |
| DOOR, AND EXIT. CLEARLY SHOW THIS REQUIRED MANEUVERING |
| SPACE INSIDE THE TOILET ROOM. ANSI A117.1 SEC.4.22.2. |
| 44) SHT. A-5.3 - DETAILS #2 & #4 STATES THE GRAB BARS |
| SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE |
| BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE BOTTOM OF |
| THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 AND FIGURE |
| 29 REQUIRES THE GRAB BARS TO BE MEASURED TO THE |
| CENTERLINE OF THE BAR. |
| 45) SHT. A-5.3 - DETAIL #1 - THE SINK AT THE DOG SPA |
| SHALL BE A MAXIMUM OF 6-1/2 INCHES DEEP PER ANSI A117.1 |
| SEC. 4.19.2.2. A CLEAR FLOOR SPACE 30 INCHES BY 48 |
| INCHES COMPLYING WITH ANSI A117.1 SEC. 4.2.4 SHALL BE |
| PROVIDED IN FRONT OF THE SINK TO ALLOW A FORWARD |
| APPROACH.SHOW THE CLEAR FLOOR SPACE ON THE PLANS. |
| 46) A-5.3 - THE TUB IN THE DOG SPA SHALL COMPLY WITH |
| ANSI A117.1 SEC. 4.20.2 FOR CLEAR FLOOR SPACE. THE |
| DRYER HEIGHT SHALL COMPLY WITH ANSI A117.1 SEC. |
| 4.25.3.CONTROLS SHALL BE OPERABLE WITH ONE HAND AND |
| SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING |
| OF THE WRIST.ANSI A117.1 SEC.4.25.4. |
| 47) A-5.4 - DETAIL #1 - WOMEN'S RESTROOM #152 & DETAIL |
| #2, WOMEN'S RESTROOM #A-119 - SHOW THE DIMENSION FROM |
| THE CENTERLINE OF THE WATER CLOSET IN THE ACCESSIBLE |
| TOILET STALL TO THE WALL ADJACENT TO THE WATER CLOSET. |
| COMPLY WITH ANSI A117.1 SEC. 4.16, 4.17 & FIGURE 28. |
| 48) SHT. A-5.4 - DETAIL #1 - SHOW THE REQUIRED CLEAR |
| FLOOR SPACE FOR THE WATER CLOSET IN THE ACCESSIBLE |
| STALL. COMPLY WITH ANSI A117.1 SEC.4.16.2 & FIGURE 28. |
| 49) SHT. A-5.4 - DETAIL #1 - A URINAL IS REQUIRED IN |
| THE MEN'S RESTROOM #151 PER FBC-PLUMBING TABLE 403.6. |
| 50) SHT. A-5.4 - DETAILS #3, 4, 5, 6, SHOW THE HEIGHT |
| OF THE LAVATORY RIM AT 32 INCHES. THIS HEIGHT MAY NOT |
| PROVIDE THE REQUIRED 27 INCHES UNDER THE LAVATORY FOR |
| THE CLEAR FLOOR SPACE PER ANSI SEC. 4.19.3 AND ALSO THE |
| CLEARANCE OF AT LEAST 29 INCHES FROM THE FLOOR TO THE |
| BOTTOM OF THE APRON.REFER TO FIGURE 31 OF ANSI A117.1. |
| 51) SHT. A-5.4 - DETAILS #1 & #2 - BOTH DETAILS ARE |
| LABELED AS "POOL ACESS/PAVILLION LEVEL 1". WHICH ONE IS |
| FOR THE POOL? CLARIFY. |
| 52) SHT. A-5.4 - DETAILS # 3, 4, 5, 6, 7, & 8 STATES |
| THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| GRIPPING SURFACE BUT THE ELEVATION HEIGHT LINE IS SHOWN |
| AT THE BOTTOM OF THE GRAB BAR. ANSI A117.1 SEC. 4.16.4 |
| AND FIGURE 29 REQUIRES THE GRAB BARS TO BE MEASURED TO |
| THE CENTERLINE OF THE BAR. |
| 53) SHT. A-5.4 - SHOW THE LENGTH OF THE SIDE AND REAR |
| GRAB BARS FOR THE WATER CLOSETS ON THE ELEVATION |
| DETAILS.SHOW THE DISTANCES OF THE GRAB BARS FROM THE |
| SIDE AND REAR WALLS PER ANSI A 117.1 SEC.4.16.4 & |
| FIGURE 29. |
| 54) TOILET PAPER DISPENSERS SHALL COMPLY WITH ANSI |
| A117.1 SEC.4.16.6 AND FIGURE 29 (B). SOAP AND PAPER |
| TOWEL DISPENSERS SHALL COMPLY WITH ANSI A117.1 |
| SEC.4.25. |
| 55) SHT. A-5.5 - POWDER ROOM # A-802 - SHOW THE |
| DIMENSION FROM THE CENTERLINE OF THE WATER CLOSET TO |
| THE WALL ADJACENT TO THE WATER CLOSET. COMPLY WITH ANSI |
| A117.1 SEC. 4.16, 4.17 & FIGURE 228. |
| 56) SHT. A-5.5 - POWDER ROOM #A-802 - SHOW THE REQUIRED |
| CLEAR FLOOR SPACE FOR THE WATER CLOSET ON THE PLAN. |
| COMPLY WITH ONE OF THE CONFIGURATIONS IN FIGURE 28 OF |
| ANSI A117.1 SEC.4.16.2. |
| 57) SHT. A-5.5 - POWDER ROOM #A-802 - THE DOOR SWINGS |
| INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.THE DOOR TO |
| THE TOILET ROOM CANNOT SWING INTO THE CLEAR FLOOR SPACE |
| REQUIRED FOR ANY FIXTURE UNLESS SUFFICIENT MANEUVERING |
| SPACE WITHIN THE ROOM FOR A PERSON USING A WHEELCHAIR |
| TO ENTER AND CLOSE THE DOOR, USE THE FIXTURES, REOPEN |
| THE DOOR, AND EXIT. CLEARLY SHOW THIS REQUIRED |
| MANEUVERING SPACE INSIDE THE TOILET ROOM. ANSI A117.1 |
| SEC.4.22.2. |
| 58) SHT. A-5.5 - POWDER ROOM # A-803 - THE CLEAR FLOOR |
| SPACES FOR THE FIXTURES ARE CONFUSING AND DO NOT MAKE |
| SENSE. CLEAN THIS FLOOR PLAN UP AND CLEARLY SHOW THE |
| REQUIRED CLEAR FLOOR SPACES FOR THE FIXTURES.THE CLEAR |
| FLOOR SPACE FOR THE LAVATORY APPEARS TO SHOW A PARALLEL |
| APPROACH WHICH IS NOT ALLOWED.A 30 INCH BY 48 INCH |
| CLEAR FLOOR SPACE SHALL BE PROVIDED IN FRONT OF A |
| LAVATORY TO ALLOW A FORWARD APPROACH PER ANSI A117.1 |
| SEC.4.19.3. COMPLY WITH ANSI A 117.1 SEC. 4.16.2, |
| FIGURE 28, AND SEC. 4.19.3 & FIG. 32. |
| 59) SHT. A-5.5 - DETAILS #1 & #3 - STATES THE GRAB BARS |
| SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE |
| BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE BOTTOM OF |
| THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 AND FIGURE |
| 29 REQUIRES THE GRAB BARS TO BE MEASURED TO THE |
| CENTERLINE OF THE BAR. |
| 60) SHT. A-5.5 - .ELEVATION DETAILS - SHOW THE |
| DISTANCES OF THE GRAB BARS FROM THE SIDE AND REAR WALLS |
| PER ANSI A 117.1 SEC.4.16.4 & FIGURE 29. |
| 61) SHT. A-5.5 - DETAIL #2 - THE WALL ADJACENT TO THE |
| WATER CLOSET DOES NOT SHOW THE REQUIRED GRAB BAR. |
| CLARIFY. |
| 62) SHT. A-5.5 - SUBMIT A KEYNOTE LEGEND OR PLACE A |
| NOTE ON THE PLAN REFERENCING THE SPECIFIC SHEET WHERE |
| THE KEYNOTES CAN BE FOUND. |
| 63) SHT. A-5.5 -POWDER ROOM #A-802 - THE CLEAR FLOOR |
| SPACE FOR THE LAVATORY APPEARS TO SHOW A PARALLEL |
| APPROACH WHICH IS NOT ALLOWED. A 30 INCH BY 48 INCH |
| CLEAR FLOOR SPACE SHALL BE PROVIDED IN FRONT OF A |
| LAVATORY TO ALLOW A FORWARD APPROACH PER ANSI A117.1 |
| SEC.4.19.3. COMPLY WITH ANSI A 117.1 SEC. 4.16.2, |
| FIGURE 28, AND SEC. 4.19.3 & FIG. 32. |
| 64) SHT. A-8.3 - DETAIL #2 - THE SHOWER BASE SHALL BE |
| PITCHED ONE-QUARTER INCH PER FOOT TOWARD THE DRAIN PER |
| FBC-PLUMBING SEC.417.5.2. |
| 65) SHTS. A-10.1 & A-10.2 - INDICATE ON THE PLANS FOR |
| EACH UNIT WHICH DESIGN SPECIFICATION ("A" OR "B") WAS |
| USED IN THE DESIGN OF THE UNITS. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 66) SHTS. A-10.1, A-10.2, A-10.3, A-10.4 - LAVATORIES |
| THAT ARE LOCATED NEXT TO WATER CLOSETS SHALL HAVE A |
| MAXIMUM DEPTH OF 24 INCHES PER THE FHADM PAGE 7.43. |
| 67) PLACE A NOTE ON THE PLANS THAT THE COMMON AREAS |
| WILL COMPLY WITH ANSI A117.1 - 1986. |
| 68) THERE ARE DUPLICATE SHEETS LABELED A-10.3 AND |
| A-10.4. CLARIFY. |
| 69) SHT. A-10.3 - UNIT B2 - THE DOOR SWINGS INTO THE |
| CLEAR FLOOR SPACE FOR THE LAVATORY IN THE HALL BATH. A |
| 30 INCH BY 48 INCH CLEAR FLOOR SPACE OUTSIDE THE SWING |
| OF THE DOOR AS IT IS CLOSED IS REQUIRED IN THE BATHOOM |
| PER FHADM PAGE 7.39. |
| 70) SHT. A-10.4 - AMENITY AND LEASING ACCESSIBILITY |
| DETAILS - ALL COMMON AREAS SHALL COMPLY WITH ANSI |
| A117.1. REMOVE THE REFERENCES AND DETAILS FROM THE |
| FBC-ACCESSIBILITY ON THIS SHEET AS THEY DO NOT APPLY. |
| 71) SHTS. A-10.3 & A-10.4 APPEAR TO BE THE SAME SHEET |
| AND SHEETS A-10.4 & A-10.5 APPEAR TO BE THE SAME. |
| CLARIFY. |
| 72) SHT. P-0.1 - GENERAL NOTE #1 REFERS TO |
| SPECIFICATIONS. JOB SPECIFICATIONS HAVE NOT BEEN |
| SUBMITTED WITH THESE PLANS. CLARIFY. |
| 73) SHT. P-2.0 - KEYNOTE #5 - LIST THE SPECIFIC CIVIL |
| DRAWING WHERE THE CONTINUATION OF THE SANITARY SEWER |
| CAN BE FOUND. WPB AMND.TO FBC SEC. 107.2.1. |
| 74) SHT. P-2.0 - KEYNOTE #9 - LIST THE SPECIFIC DRAWING |
| WHERE THE FORCE MAIN DETAIL CAN BE REVIEWED. WPB |
| AMND.TO FBC SEC. 107.2.1. |
| 75) SHT.P-2.1 - KEYNOTE #6 - LIST THE SPECIFIC CIVIL |
| DRAWING NUMBER FOR THE CONTINUATION OF THE WATER MAIN. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| 76) SHT. P-2.1 - THERE ARE CIRCLES ON THE PLAN THAT |
| APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND |
| RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1, |
| MEN'S RESTROOM #A-117, BISTRO BAR, AND MAIL |
| ROOM.CLARIFY. |
| 77) SHT. P-2.1 APPEARS TO SHOW A RISER IN STAIR #2. |
| THIS IS NOT PERMITTED PER FBC-BUILDING SEC.1023.5. |
| CLARIFY. |
| 78) SHT. P-2.1.1 - PROVIDE MATCH LINES FOR THE PLAN AND |
| LIST THE SPECIFIC CIVIL DRAWINGS FOR THE CONTINUATION |
| OF THE STORM DRAINS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 79) SHT. P-2.2 - THERE ARE CIRCLES ON THE PLAN THAT |
| APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND |
| RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1, |
| B1- MOD, ND THE BRIDGE AREA. THERE APPEARS TO BE A |
| RISER IN STAIR #2. THIS IS NOT PERMITTED PER |
| FBC-BUILDING SEC.1023.5. CLARIFY.THESE ISSUES APPEAR TO |
| OCCUR ON ALL LEVELS. CLARIFY. |
| 80) SHT. P-2.6 - IDENTIFY THE UNITS ON THE FLOOR |
| PLAN.WPB AMEND. TO FBC SEC. 107.2.1. |
| 81) SHT. P-2.1 - SHOWS A JANITOR ROOM #167 BY STAIR #3 |
| AND THE SAME ROOM IS SHOWN AS STAFF TOILET ROOM #170 ON |
| SHT. A-2.1. CLARIFY. |
| 82) SHT. P-4.1 - KEYNOTE #12 - LIST THE SPECIFIC |
| BUILDING PLAN FOR THE CONTINUATION OF THE SANITARY |
| LINES. WPB AMEND. TO FBC SEC. 107.2.1. |
| 83) SHT.P-2.1 SHOWS A 2 INCH WATER SUPPLY BRANCH TO |
| MEN'S TOILET ROOM # A-117 & SHT. P-4.1 SHOWS A 1 1/2 |
| INCH WATER SUPPLY BRANCH. CLARIFY. |
| 84) SHT. P-4.2 SHOWS A FLOOR PLAN FOR UNIT C2. I COULD |
| NOT FIND THIS UNIT ON ANY OF THE FLOOR PLANS. LARIFY. |
| 85) SHT. P-4.1 - CLEARLY IDENTIFY/ LABEL THE RESTROOMS |
| ON DETAIL 1/P-4.2. NOTE: THIS DETAIL IS ON SHT. P-4.1, |
| NOT P-4.2. CLARIFY. |
| 86) SHT. P-2.1 - THE LAYOUT OF THE PLUMBING FIXTURES |
| AND NUMBER OF FIXTURE FOR THE MEN'S AND WOMEN'S TOILET |
| ROOMS #151 & #152 DO NOT CORRELATE WITH THE LAYOUT AND |
| NUBER OF FIXTURES ON SHT. A-2.1. |
| 87) SHT. P-2.1 - THE JANITOR ROOM #166 IS NOT SHOWN ON |
| SHT. P-2.1. CLARIFY. |
| 88) SHT.P-5.1 - RISER 5/S - AIR ADMITTANCE VALVES |
| CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED |
| MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE |
| STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A |
| RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK |
| VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER |
| FBC-PLUMBING SEC. 918.3.1. |
| 89) SHT. P-5.2 - RISER 10/S - AIR ADMITTANCE VALVES |
| CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED |
| MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE |
| STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A |
| RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK |
| VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER |
| FBC-PLUMBING SEC. 918.3.1. |
| 90) SHT. P-5.2 - SANITARY AND WATER RISERS - |
| IDENTIFY/LABEL EACH RISER WITH THE SPECIFIC RESTROOM |
| NUMBER AND AREA. WPB AMEND. TO FBC SEC. 107.2.1. |
| 91) SHT. P-5.2 - RISER 11/S IS SHOWN ON THIS SHEET BUT |
| I COULD NOT FIND THIS RISER ON ANY OF THE PLANS. |
| CLARIFY. |
| 92) SHT. P-5.2 - DETAIL #2 - THE VENT BETWEEEN THE TWO |
| WATER CLOSETS APPEARS TO BE A FLAT, DRY VENT. EVERY DRY |
| VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT |
| ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE PER |
| FBC-PLUMBING SEC.905.3. CLARIFY HOW THIS VENT IS |
| CONNECTED TO THE HORIZONTAL DRAIN. |
| 93) SHT. P-8.1-SHT. P-8.1 - SUBMIT APPROVED ASSEMBLY |
| DETAILS FOR THE FIRESTOP PENETRATION DETAILS.SUBMIT THE |
| MANUFACTURER'S INFORMATION AND THE APPROVED LISTING |
| NUMBERS. WPB AMEND. TO FBC SEC. 107.3.5.1.1. |
| 94) SHT. P-8.1 - SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE SUB-METERS. IF THE METERS WILL BE LOCATED IN A |
| RETURN AIR CLOSET THEY SHALL MEET THE FLAME SPREAD |
| INDEX AND SMOKE-DEVELOPED INDEX OF SEC. 602.2.1 OF THE |
| FBC-MECHANICAL AND THE TEST CRITERIA OF ASTM E84 OR UL |
| 723. |
| 95) SHT. P-8.1 - SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 96) SHT. P-8.1 - CLARIFY WHAT TYPE OF EFFLUENT WILL BE |
| DISCHARGING FROM THE POOL EQUIPMENT INTO THE SANITARY |
| SYSTEM. POOL WATER SHALL NOT BE DISCHARGED TO THE |
| SANITARY SYSTEM PER CITY OF WEST PALM BEACH CODE OF |
| ORDINANCES CHAPTER 90, ARTICLE III, SSEC.90-126 (B)(5) |
| UNLESS SSPECIFICALLY AUTHORIZED BY THE CITY IN WRITING. |
| 97) SSHT. P-8.1 - PIPE HANGER DETAIL - PIPE SHALL BE |
| SUPPORTED IN ACCORDANCE WITH FBC-PLUMBING SEC.308 AND |
| TABLE 308.5. |
| 98) SUBMIT A COMPLETE UNDERGROUND SANITARY RISER DETAIL |
| SHOWING ALL RISER CONNECTIONS, PIPE SIZES, VENTS, |
| ETC.WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| 99) SUBMIT A COMPLETE UNDERGROUND STORM DRAINAGE RISER |
| DETAIL SHOWING ALL RISER CONNECTIONS, PIPE SIZES, GPM, |
| ETC. |
| 100) SUBMIT A STORM DRAIN RISER SYSTEM FOR THE |
| ABOVEGROUND STORM DRAIN COLLECCTION SYSTEM SHOWING |
| RISER TAGS,PIPE SIZES, GPM THROUGH THE DRAINS AND |
| PIPES. PROVIDE VERIFICATION THAT THE SIZING |
| CALCULATIONS FOR THE SYSTEM INCLUDES 1/2 THE AREA OF |
| ANY VERTICAL WALLS AND ANY DRAINAGE OF STORMWATER FROM |
| UPPER ROOFS TO THE LOWER ROOF WHERE THE ROOF DRAINS ARE |
| LOCATED. FBC-PLUMBING SEC.106.4.WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 101) SHT. A-7.6 - SANITATION UNIT DETAIL - A REDUCED |
| PRESSURE BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED |
| ON THE TRASH CHUTE WATER LINE PER FBC-PLUMBING |
| 608.13.2. |
| 102) THE WASHING MACHINE WATER SUPPLY VALVES SHALL BE |
| PROVIDED WITH ACCESS WITHOUT MOVING THE UNIT. SHOW THE |
| LOCATION OF THE VALVES ON THE PLANS. FBC-PLUMBING SEC. |
| 606.3. |
| 103) SUBMIT SANITARY AND WATER RISERS FOR ALL THE |
| COMMON AREA PLUMBING FIXTURES AND TOILET ROOMS. WPB |
| AMEND. TO FBC SEC. 107.3.5.1.3. |
| 104) THE WATER SUPPLY TO DISHWASHERS AND ICEMAKERS |
| SHALL BE PROTECTED AGAINST BACKFLOW PER FBC-PLUMBING |
| SEC.608..2. THE BACKFLOW DEVICE SHALL COMPLY WITH ASSE |
| 1024. |
| 105) SUBMIT A PIPING DETAIL FOR THE DOMESTIC BOOSTER |
| SYSTEM AND SUBMIT WATER RISER DIAGAM FOR THE MAIN WATER |
| SYSTEM IN THE BUILDING. WPB AMEND. TO FBC SEC. |
| 107.3.5.1.3. |
| 106) PRESSURE REDUCING VALVES ARE REQUIRED ON THE WATER |
| DISTRIBUTION SYSTEM WHERE THE WATER PRESSSURE WITHIN A |
| BUILDING EXCEEDS 80 PSI STATIC.WATER PRESURE REDUCING |
| VALVES SHALL CONFORM TO ASSE 1003 OR CSA B356. WATER |
| PRESURE REDUCING VALVES, REGULATORS AND TRAINERS SHALL |
| BE SO CONSTRUCTED AND INSTALLED AS TO PERMIT REPAIR OR |
| REMOVAL OF PARTS WITHOUT BREAKING A PIPELINE OR |
| REMOVING THE VALVE AND TRAINER FROM THE PIPELINE PER |
| FBC SECS.604.8, 604.8.2. |
| |