Plan Review Notes
Plan Review Notes For Permit 20120803
Permit Number 20120803
Review Stop P
Sequence Number 2
Notes
Date Text
2021-06-14 09:31:221) SHT. C.07 - PLACE A NOTE ON THE PLANS THAT SEPARATE
 PERMITS WILL BE REQUIRE FOR THE BACKFLOW PREVENTERS PER
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL.
 2) THIS BUILDING WAS DESIGNED UNDER THE FAIR HOUSING
 ACT DESIGN MANUAL-1998. INDICATE ON THE PLANS FOR EACH
 UNIT WHICH DESIGN SPECIFICATION ("A" OR "B") WAS USED
 IN THE DESIGN OF THE UNITS. WPB AMEND. TO FBC SEC.
 107.2.1.
 3) THE ADDRESS OF THE PROJECT MUST BE ON THE PLANS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A-2.1.2 - THE B1 UNITS DO NOT SHOW ANY
 LAVATORIES OR WATER CLOSETS ON THE FLOOR PLAN. THIS
 SEEMS TO APPEAR ON ALL LEVELS.CLARIFY.
 5) SHT. A-2.1.2 - THE LAUNDRY ROOM #169 SHALL COMPLY
 WITH ANSI A117.1- 1986 FOR FAIR HOUSING COMPLIANCE.THE
 WASHER AND DRYER SHALL COMPLY WITH ANSI A117.1 SEC.4.25
 FOR CONTROLS AND OPERATING MECHANISMS.THE SINK SHALL
 COMPLY WITH SEC, 4.19.2.2.
 6) PROVIDE A PLUMBING FIXTURE COUNT TABLE AND OCCUPANCY
 DESIGNATION AND OCCUPANT LOAD FOR EACH OF THE COMMON
 AREAS BASED ON THE OCCUPANCY AND OCCUPANT LOAD PER
 TABLE 403.1 OF THE FBC-PLUMBING.
 7) SHT. A-2.1.2 - THE NOTE AT THE TOP OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.1.2 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.1.2. CLARIFY.
 8) SUBMIT ENLARGED TOILET ROOM FLOOR PLANS FOR ALL THE
 COMMON AREA TOILET ROOMS SHOWING THE REQUIRED CLEAR
 FLOOR SPACES FOR ALL HANDICAPPED FIXTURES. ALSO, SHOW
 THE CLEAR INSIDE DIMENSONS (L X W) OF EACH TOILET
 ROOM.CLEARANCES FOR WATER CLOSETS SHALL COMPLY WITH
 ANSI A117.1 SEC.4.16.COMPLY WITH ANSI A117.1-1986.
 9) SHT. SHT. A-2.2.2 - THE DOORS TO TOILET ROOMS A-109
 & A-110 APPEAR TO SWING INTO THE CLEAR FLOOR SPACE FOR
 THE LAVATORIES. COMPLY WITH ANSI A117.1-1986
 SEC.4.22.2.
 10) SHT. A-2.1.1 - THE NOTE AT THE BOTTOM OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.1.1 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.1.1. CLARIFY.
 11) SHT. A-2.1.2. - SHOW THE LENGTH AND WIDTH OF ALL
 THE TOILET STALLS IN THE COMMON AREA TOILET ROOMS.
 COMPLY WITH FBC-PLUMBING SEC.405.3.1.
 12) SHT. A-2.1.2 - THE WALL SURFACE AROUND THE MOP
 SINKS SHALL COMPLY WITH FBC-BUILDING SEC. 1210.2.2.
 13) A MINIMUM OF 2 DRINKING FOUNTAINS WILL BE REQUIRED
 FOR THE FITNESS CENTER PER AND POSSIBLY OTHER AMENITY
 AREAS.FBC-PLUMBING TABLE 403.1 & SEC.410.3.
 14) SHT. A-2.1.2 - A URINAL IS REQUIRED IN THE MEN'S
 RESTROOM #151 AT THE POOL AREA PER FBC-PLUMBING
 SEC.403.6 & TABLE 403.6.
 15) SHT. A-2.1.2 - ALL SINKS LOCATED IN THE COMMON
 AREAS SHALL COMPLY WITH ANSI A117.1 SEC.4.19.2.2,
 4.19.3, 4.19.4, 4.19.5.
 16) SHT.A-2.2.1- THE NOTE AT THE BOTTOM OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.2.1 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.2.1. CLARIFY.
 17) THE DOOR IN THE C1 UNIT HALL BATH APPEARS TO SWING
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY IF THAT IS
 DESIGNED AS THE ADAPTABLE BATHROOM. COMPLY WITH FHADM
 (FAIR HOUSING ACT DESIGN MANUAL) PAGE 7.39.THIS APPLIES
 TO ALL LEVELS. CLARIFY.
 18) UNIT C1 - THE SHOWER DOOR IN THE MASTER BATH SWINGS
 INTO THE CLEAR FLOOR SPACE FOR THE SHOWER AND APPEARS
 TO PREVENT THE ACCESS TO THE CONTROLS IF THIS IS THE
 ADAPTABLE/USABLE BATHROOM. COMPLY WITH FHADM PAGE
 7.56.THIS APPLIES TO ALL LEVELS.
 19) UNIT C1 - THE HALL BATH IS MISSING THE WATER
 CLOSET, LAVATORY AND SHOWER ON THE FLOOR PLANS. THIS
 APPEARS TO OCCUR ON ALL LEVELS.CLARIFY.
 20) UNIT ST1 & ST1 MOD - THE DOORS IN THE BATHROOMS
 APPEAR TO SWING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY.COMPLY WITH FHADM PAGE 7.39.
 21) UNITS B1 & B1 MOD - IF THE MASTER BATH IS THE FHA
 COMPLIANT BATHROOM, THE LENGTH OF THE SHOWER WALL
 ADJACENT TO THE WATER CLOSET SHALL NOT EXCEED 24 INCHES
 IN LENGTH AND MUST BE AT LEAST 33 INCHES FROM THE
 OPPOSITE WALL PER THE FHADM PAGE 7.43 & 7.44.
 22) UNIT B2 - IF THE MASTER BATH IS THE FHA COMPLIANT
 BATHROOM, THE LENGTH OF THE WALLS ADJACENT TO THE WATER
 CLOSET SHALL NOT EXCEED 24 INCHES PER THE FHADM PAGE
 7.43 & 7.44.ALSO, SHOW THE CLEAR FLOOR PACE FOR THE
 WATER CLOSET PER THE FHADM PAGE 7.43.
 23) SHT. A-4.8 - THE ROOM FINISH SCHEDULE FOR THE
 COMMON AREAS IS BLANK. CLARIFY.
 24) SHT. A-2.3 - THE NAMING CONVENTION FOR THE PLAN
 NOTES THAT IT IS FOR LEVELS 3 TO 5 BUT THE PLAN STATES
 IT IS FOR LEVEL 3 ONLY. CLARIFY.
 25) SHT. A-2.3.1 - THE NOTE AT THE BOTTOM OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.3.1 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.3.1. CLARIFY.
 26) SHT.A-2.3.2 - THE NOTE AT THE TOP OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.3.2 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.3.2. CLARIFY.
 27) SHT. A-2.4.1 - THE NOTE AT THE BOTTOM OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.3.1 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.3.1. CLARIFY.
 28) SHT. A-2.4.2 - THE NOTE ON THE TOP OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.3.2 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 SHEET A2.3.2. CLARIFY.
 29) SHT. A-2.5.1- THE NOTE ON THE BOTTOM OF THE SHEET
 STATES "" REFER TO PARTIAL PLAN SHEET A-2.3.1 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.3.1. CLARIFY.
 30) SHT .A-2.5.2 - THE NOTE ON THE TOP OF THE PLAN
 REFERS TO A PARTIAL PLAN ON SHT. A-2.3.2. THERE IS NO
 PARTIAL PLAN ON A-2.3.2. CLARIFY.
 31) SHT. A-2.6.1 - THE NOTE ON THE BOTTOM OF THE PAGE
 REFERS TO PARTIAL PLAN SHEET A-2.4.1.SHT A-2.4.1 IS FOR
 LEVEL 4 AND SHT. A-2.6.1 IS FOR LEVEL 6. CLARIFY.
 32) SHT. A-2.6.2 - THE NOTE ON THE TOP OF THE PLAN
 REFERS TO A PARTIAL PLAN ON SHT. A-2.4.2. THERE IS NO
 PARTIAL PLAN ON A-2.4.2. ALSO, SHT. A-2.6.2 IS FOR
 LEVEL 6 AND SHT. A-2.4.2 IS FOR LEVEL 4.CLARIFY.
 33) SHT. A-2.7.1 - THE NOTE ON THE BOTTOM OF THE PLAN
 REFERS TO A PARTIAL PLAN ON SHT.A-2.5.1.THERE IS NO
 PARTIAL PLAN ON SHT. A-2.5.1. ALSO, SHT. A-2.5.1 IS FOR
 LEVEL 5 AND SHT. A-2.7.1 IS FOR LEVEL 7. CLARIFY.
 34) SHT. A-2.8.1 - THE NOTE ON THE BOTTOM OF THE PLAN
 REFERS TO A PARTIAL PLAN ON SHT.A-2.6.1.THERE IS NO
 PARTIAL PLAN ON SHT. A-2.6.1. ALSO, SHT. A-2.6.1 IS FOR
 LEVEL 6 AND SHT. A-2.8.1 IS FOR LEVEL 8. CLARIFY.
 35) SHT. A-2.8.2 - THE NOTE ON THE TOP OF THE PLAN
 REFERS TO A PARTIAL PLAN ON SHT. A-2.6.2. THERE IS NO
 PARTIAL PLAN ON SHT. A-2.6.2. ALSO, SHT. A-2.6.2 IS FOR
 LEVEL 6 AND SHT. A-2.8.2 IS FOR LEVEL 8. CLARIFY.
 36) SHT. A-2.9.1 - THE NOTE ON THE TOP OF THHE SHEET
 REFERS TO A PARTIAL PLANON SHT. A-2.7.2. THERRE IS NO
 PARTIAL PLAN ON A-2.7.2. ALSO, SHT. A-2.7.2 IS FOR
 LEVEL 7 AND SHT. A-2.9.1 IS FOR THE ROOF LEVEL.
 CLARIFY.
 37) SUBMIT THE INTERIOR ELEVATION DESIGNATIONS FOR THE
 DWELLING UNITS AS SHOWN ON THE FLOOR PLANS FOR THE
 UNITS ON SHEETS A-4.1, A-4.2, A-4.3 & A-4.4. SHOW THE
 HEIGHT DIMENSIONS OF THE KITCHEN AND BATHROOM CABINETS
 FROM THE FLOOR TO THE TOP OF THE COUNTER.WPB AMEND. TO
 FBC SEC. 107.2.1, FHADM PAGE 7.15 & 7.52.
 38) SHT. A-5.1 - POWDER ROOM #A-111 - SHOW THE REQUIRED
 CLEAR FLOOR SPACES FOR THE WATER CLOSET AND THE
 LAVATORY. COMPLY WITH ANSI A117.1-86 SECTIONS 4.16.2 &
 4.19.3.
 39) SHT. A-5.1- POWDER ROOM #A-111 - THE DOOR TO THE
 TOILET ROOM APPEARS TO SWING INTO THE CLEAR FLOOR SPACE
 FOR THE LAVATORY.THE DOOR TO THE TOILET ROOM CANNOT
 SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE UNLESS SUFFICIENT MANEUVERING SPACE WITHIN THE
 ROOM FOR A PERSON USING A WHEELCHAIR TO ENTER AND CLOSE
 THE DOOR, USE THE FIXTURES, REOPEN THE DOOR, AND EXIT.
 CLEARLY SHOW THIS REQUIRED MANEUVERING SPACE INSIDE THE
 TOILET ROOM.ANSI A117.1 SEC.4.22.2.
 40) SHT. A-5.1 - TOILET ROOMS # 109 & 110 - THE DOOR TO
 THE TOILET ROOM APPEARS TO SWING INTO THE CLEAR FLOOR
 SPACE FOR THE LAVATORY.THE DOOR TO THE TOILET ROOM
 CANNOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE UNLESS SUFFICIENT MANEUVERING SPACE WITHIN
 THE ROOM FOR A PERSON USING A WHEELCHAIR TO ENTER AND
 CLOSE THE DOOR, USE THE FIXTURES, REOPEN THE DOOR, AND
 EXIT. CLEARLY SHOW THIS REQUIRED MANEUVERING SPACE
 INSIDE THE TOILET ROOM. ANSI A117.1 SEC.4.22.2.
 41) SHT. A-5.1 - TOILET ROOMS #109 & 110 SHALL BE
 GENDER SPECIFIC (MALE & FEMALE) PER FBC-PLUMBING SEC.
 403.2.
 42) SHT. A-5.1 - DETAILS #1, #2, & #3 STATES THE GRAB
 BARS SHALL BE MEASURED TO THE TOP OF THE GRIPPING
 SURFACE BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE
 BOTTOM OF THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4
 AND FIGURE 29 REQUIRES THE GRAB BARS TO BE MEASURED TO
 THE CENTERLINE OF THE BAR.
 43) SHT. A-5.3 - STAFF TOILET ROOMS #170 & 111- THE
 DOOR TO THE TOILET ROOM APPEARS TO SWING INTO THE CLEAR
 FLOOR SPACE FOR THE LAVATORY.THE DOOR TO THE TOILET
 ROOM CANNOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE UNLESS SUFFICIENT MANEUVERING SPACE
 WITHIN THE ROOM FOR A PERSON USING A WHEELCHAIR TO
 ENTER AND CLOSE THE DOOR, USE THE FIXTURES, REOPEN THE
 DOOR, AND EXIT. CLEARLY SHOW THIS REQUIRED MANEUVERING
 SPACE INSIDE THE TOILET ROOM. ANSI A117.1 SEC.4.22.2.
 44) SHT. A-5.3 - DETAILS #2 & #4 STATES THE GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE BOTTOM OF
 THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 AND FIGURE
 29 REQUIRES THE GRAB BARS TO BE MEASURED TO THE
 CENTERLINE OF THE BAR.
 45) SHT. A-5.3 - DETAIL #1 - THE SINK AT THE DOG SPA
 SHALL BE A MAXIMUM OF 6-1/2 INCHES DEEP PER ANSI A117.1
 SEC. 4.19.2.2. A CLEAR FLOOR SPACE 30 INCHES BY 48
 INCHES COMPLYING WITH ANSI A117.1 SEC. 4.2.4 SHALL BE
 PROVIDED IN FRONT OF THE SINK TO ALLOW A FORWARD
 APPROACH.SHOW THE CLEAR FLOOR SPACE ON THE PLANS.
 46) A-5.3 - THE TUB IN THE DOG SPA SHALL COMPLY WITH
 ANSI A117.1 SEC. 4.20.2 FOR CLEAR FLOOR SPACE. THE
 DRYER HEIGHT SHALL COMPLY WITH ANSI A117.1 SEC.
 4.25.3.CONTROLS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST.ANSI A117.1 SEC.4.25.4.
 47) A-5.4 - DETAIL #1 - WOMEN'S RESTROOM #152 & DETAIL
 #2, WOMEN'S RESTROOM #A-119 - SHOW THE DIMENSION FROM
 THE CENTERLINE OF THE WATER CLOSET IN THE ACCESSIBLE
 TOILET STALL TO THE WALL ADJACENT TO THE WATER CLOSET.
 COMPLY WITH ANSI A117.1 SEC. 4.16, 4.17 & FIGURE 28.
 48) SHT. A-5.4 - DETAIL #1 - SHOW THE REQUIRED CLEAR
 FLOOR SPACE FOR THE WATER CLOSET IN THE ACCESSIBLE
 STALL. COMPLY WITH ANSI A117.1 SEC.4.16.2 & FIGURE 28.
 49) SHT. A-5.4 - DETAIL #1 - A URINAL IS REQUIRED IN
 THE MEN'S RESTROOM #151 PER FBC-PLUMBING TABLE 403.6.
 50) SHT. A-5.4 - DETAILS #3, 4, 5, 6, SHOW THE HEIGHT
 OF THE LAVATORY RIM AT 32 INCHES. THIS HEIGHT MAY NOT
 PROVIDE THE REQUIRED 27 INCHES UNDER THE LAVATORY FOR
 THE CLEAR FLOOR SPACE PER ANSI SEC. 4.19.3 AND ALSO THE
 CLEARANCE OF AT LEAST 29 INCHES FROM THE FLOOR TO THE
 BOTTOM OF THE APRON.REFER TO FIGURE 31 OF ANSI A117.1.
 51) SHT. A-5.4 - DETAILS #1 & #2 - BOTH DETAILS ARE
 LABELED AS "POOL ACESS/PAVILLION LEVEL 1". WHICH ONE IS
 FOR THE POOL? CLARIFY.
 52) SHT. A-5.4 - DETAILS # 3, 4, 5, 6, 7, & 8 STATES
 THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE BUT THE ELEVATION HEIGHT LINE IS SHOWN
 AT THE BOTTOM OF THE GRAB BAR. ANSI A117.1 SEC. 4.16.4
 AND FIGURE 29 REQUIRES THE GRAB BARS TO BE MEASURED TO
 THE CENTERLINE OF THE BAR.
 53) SHT. A-5.4 - SHOW THE LENGTH OF THE SIDE AND REAR
 GRAB BARS FOR THE WATER CLOSETS ON THE ELEVATION
 DETAILS.SHOW THE DISTANCES OF THE GRAB BARS FROM THE
 SIDE AND REAR WALLS PER ANSI A 117.1 SEC.4.16.4 &
 FIGURE 29.
 54) TOILET PAPER DISPENSERS SHALL COMPLY WITH ANSI
 A117.1 SEC.4.16.6 AND FIGURE 29 (B). SOAP AND PAPER
 TOWEL DISPENSERS SHALL COMPLY WITH ANSI A117.1
 SEC.4.25.
 55) SHT. A-5.5 - POWDER ROOM # A-802 - SHOW THE
 DIMENSION FROM THE CENTERLINE OF THE WATER CLOSET TO
 THE WALL ADJACENT TO THE WATER CLOSET. COMPLY WITH ANSI
 A117.1 SEC. 4.16, 4.17 & FIGURE 228.
 56) SHT. A-5.5 - POWDER ROOM #A-802 - SHOW THE REQUIRED
 CLEAR FLOOR SPACE FOR THE WATER CLOSET ON THE PLAN.
 COMPLY WITH ONE OF THE CONFIGURATIONS IN FIGURE 28 OF
 ANSI A117.1 SEC.4.16.2.
 57) SHT. A-5.5 - POWDER ROOM #A-802 - THE DOOR SWINGS
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.THE DOOR TO
 THE TOILET ROOM CANNOT SWING INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR ANY FIXTURE UNLESS SUFFICIENT MANEUVERING
 SPACE WITHIN THE ROOM FOR A PERSON USING A WHEELCHAIR
 TO ENTER AND CLOSE THE DOOR, USE THE FIXTURES, REOPEN
 THE DOOR, AND EXIT. CLEARLY SHOW THIS REQUIRED
 MANEUVERING SPACE INSIDE THE TOILET ROOM. ANSI A117.1
 SEC.4.22.2.
 58) SHT. A-5.5 - POWDER ROOM # A-803 - THE CLEAR FLOOR
 SPACES FOR THE FIXTURES ARE CONFUSING AND DO NOT MAKE
 SENSE. CLEAN THIS FLOOR PLAN UP AND CLEARLY SHOW THE
 REQUIRED CLEAR FLOOR SPACES FOR THE FIXTURES.THE CLEAR
 FLOOR SPACE FOR THE LAVATORY APPEARS TO SHOW A PARALLEL
 APPROACH WHICH IS NOT ALLOWED.A 30 INCH BY 48 INCH
 CLEAR FLOOR SPACE SHALL BE PROVIDED IN FRONT OF A
 LAVATORY TO ALLOW A FORWARD APPROACH PER ANSI A117.1
 SEC.4.19.3. COMPLY WITH ANSI A 117.1 SEC. 4.16.2,
 FIGURE 28, AND SEC. 4.19.3 & FIG. 32.
 59) SHT. A-5.5 - DETAILS #1 & #3 - STATES THE GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE BOTTOM OF
 THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 AND FIGURE
 29 REQUIRES THE GRAB BARS TO BE MEASURED TO THE
 CENTERLINE OF THE BAR.
 60) SHT. A-5.5 - .ELEVATION DETAILS - SHOW THE
 DISTANCES OF THE GRAB BARS FROM THE SIDE AND REAR WALLS
 PER ANSI A 117.1 SEC.4.16.4 & FIGURE 29.
 61) SHT. A-5.5 - DETAIL #2 - THE WALL ADJACENT TO THE
 WATER CLOSET DOES NOT SHOW THE REQUIRED GRAB BAR.
 CLARIFY.
 62) SHT. A-5.5 - SUBMIT A KEYNOTE LEGEND OR PLACE A
 NOTE ON THE PLAN REFERENCING THE SPECIFIC SHEET WHERE
 THE KEYNOTES CAN BE FOUND.
 63) SHT. A-5.5 -POWDER ROOM #A-802 - THE CLEAR FLOOR
 SPACE FOR THE LAVATORY APPEARS TO SHOW A PARALLEL
 APPROACH WHICH IS NOT ALLOWED. A 30 INCH BY 48 INCH
 CLEAR FLOOR SPACE SHALL BE PROVIDED IN FRONT OF A
 LAVATORY TO ALLOW A FORWARD APPROACH PER ANSI A117.1
 SEC.4.19.3. COMPLY WITH ANSI A 117.1 SEC. 4.16.2,
 FIGURE 28, AND SEC. 4.19.3 & FIG. 32.
 64) SHT. A-8.3 - DETAIL #2 - THE SHOWER BASE SHALL BE
 PITCHED ONE-QUARTER INCH PER FOOT TOWARD THE DRAIN PER
 FBC-PLUMBING SEC.417.5.2.
 65) SHTS. A-10.1 & A-10.2 - INDICATE ON THE PLANS FOR
 EACH UNIT WHICH DESIGN SPECIFICATION ("A" OR "B") WAS
 USED IN THE DESIGN OF THE UNITS. WPB AMEND. TO FBC SEC.
 107.2.1.
 66) SHTS. A-10.1, A-10.2, A-10.3, A-10.4 - LAVATORIES
 THAT ARE LOCATED NEXT TO WATER CLOSETS SHALL HAVE A
 MAXIMUM DEPTH OF 24 INCHES PER THE FHADM PAGE 7.43.
 67) PLACE A NOTE ON THE PLANS THAT THE COMMON AREAS
 WILL COMPLY WITH ANSI A117.1 - 1986.
 68) THERE ARE DUPLICATE SHEETS LABELED A-10.3 AND
 A-10.4. CLARIFY.
 69) SHT. A-10.3 - UNIT B2 - THE DOOR SWINGS INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY IN THE HALL BATH. A
 30 INCH BY 48 INCH CLEAR FLOOR SPACE OUTSIDE THE SWING
 OF THE DOOR AS IT IS CLOSED IS REQUIRED IN THE BATHOOM
 PER FHADM PAGE 7.39.
 70) SHT. A-10.4 - AMENITY AND LEASING ACCESSIBILITY
 DETAILS - ALL COMMON AREAS SHALL COMPLY WITH ANSI
 A117.1. REMOVE THE REFERENCES AND DETAILS FROM THE
 FBC-ACCESSIBILITY ON THIS SHEET AS THEY DO NOT APPLY.
 71) SHTS. A-10.3 & A-10.4 APPEAR TO BE THE SAME SHEET
 AND SHEETS A-10.4 & A-10.5 APPEAR TO BE THE SAME.
 CLARIFY.
 72) SHT. P-0.1 - GENERAL NOTE #1 REFERS TO
 SPECIFICATIONS. JOB SPECIFICATIONS HAVE NOT BEEN
 SUBMITTED WITH THESE PLANS. CLARIFY.
 73) SHT. P-2.0 - KEYNOTE #5 - LIST THE SPECIFIC CIVIL
 DRAWING WHERE THE CONTINUATION OF THE SANITARY SEWER
 CAN BE FOUND. WPB AMND.TO FBC SEC. 107.2.1.
 74) SHT. P-2.0 - KEYNOTE #9 - LIST THE SPECIFIC DRAWING
 WHERE THE FORCE MAIN DETAIL CAN BE REVIEWED. WPB
 AMND.TO FBC SEC. 107.2.1.
 75) SHT.P-2.1 - KEYNOTE #6 - LIST THE SPECIFIC CIVIL
 DRAWING NUMBER FOR THE CONTINUATION OF THE WATER MAIN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 76) SHT. P-2.1 - THERE ARE CIRCLES ON THE PLAN THAT
 APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND
 RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1,
 MEN'S RESTROOM #A-117, BISTRO BAR, AND MAIL
 ROOM.CLARIFY.
 77) SHT. P-2.1 APPEARS TO SHOW A RISER IN STAIR #2.
 THIS IS NOT PERMITTED PER FBC-BUILDING SEC.1023.5.
 CLARIFY.
 78) SHT. P-2.1.1 - PROVIDE MATCH LINES FOR THE PLAN AND
 LIST THE SPECIFIC CIVIL DRAWINGS FOR THE CONTINUATION
 OF THE STORM DRAINS. WPB AMEND. TO FBC SEC. 107.2.1.
 79) SHT. P-2.2 - THERE ARE CIRCLES ON THE PLAN THAT
 APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND
 RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1,
 B1- MOD, ND THE BRIDGE AREA. THERE APPEARS TO BE A
 RISER IN STAIR #2. THIS IS NOT PERMITTED PER
 FBC-BUILDING SEC.1023.5. CLARIFY.THESE ISSUES APPEAR TO
 OCCUR ON ALL LEVELS. CLARIFY.
 80) SHT. P-2.6 - IDENTIFY THE UNITS ON THE FLOOR
 PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 81) SHT. P-2.1 - SHOWS A JANITOR ROOM #167 BY STAIR #3
 AND THE SAME ROOM IS SHOWN AS STAFF TOILET ROOM #170 ON
 SHT. A-2.1. CLARIFY.
 82) SHT. P-4.1 - KEYNOTE #12 - LIST THE SPECIFIC
 BUILDING PLAN FOR THE CONTINUATION OF THE SANITARY
 LINES. WPB AMEND. TO FBC SEC. 107.2.1.
 83) SHT.P-2.1 SHOWS A 2 INCH WATER SUPPLY BRANCH TO
 MEN'S TOILET ROOM # A-117 & SHT. P-4.1 SHOWS A 1 1/2
 INCH WATER SUPPLY BRANCH. CLARIFY.
 84) SHT. P-4.2 SHOWS A FLOOR PLAN FOR UNIT C2. I COULD
 NOT FIND THIS UNIT ON ANY OF THE FLOOR PLANS. LARIFY.
 85) SHT. P-4.1 - CLEARLY IDENTIFY/ LABEL THE RESTROOMS
 ON DETAIL 1/P-4.2. NOTE: THIS DETAIL IS ON SHT. P-4.1,
 NOT P-4.2. CLARIFY.
 86) SHT. P-2.1 - THE LAYOUT OF THE PLUMBING FIXTURES
 AND NUMBER OF FIXTURE FOR THE MEN'S AND WOMEN'S TOILET
 ROOMS #151 & #152 DO NOT CORRELATE WITH THE LAYOUT AND
 NUBER OF FIXTURES ON SHT. A-2.1.
 87) SHT. P-2.1 - THE JANITOR ROOM #166 IS NOT SHOWN ON
 SHT. P-2.1. CLARIFY.
 88) SHT.P-5.1 - RISER 5/S - AIR ADMITTANCE VALVES
 CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED
 MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE
 STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A
 RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK
 VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER
 FBC-PLUMBING SEC. 918.3.1.
 89) SHT. P-5.2 - RISER 10/S - AIR ADMITTANCE VALVES
 CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED
 MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE
 STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A
 RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK
 VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER
 FBC-PLUMBING SEC. 918.3.1.
 90) SHT. P-5.2 - SANITARY AND WATER RISERS -
 IDENTIFY/LABEL EACH RISER WITH THE SPECIFIC RESTROOM
 NUMBER AND AREA. WPB AMEND. TO FBC SEC. 107.2.1.
 91) SHT. P-5.2 - RISER 11/S IS SHOWN ON THIS SHEET BUT
 I COULD NOT FIND THIS RISER ON ANY OF THE PLANS.
 CLARIFY.
 92) SHT. P-5.2 - DETAIL #2 - THE VENT BETWEEEN THE TWO
 WATER CLOSETS APPEARS TO BE A FLAT, DRY VENT. EVERY DRY
 VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE PER
 FBC-PLUMBING SEC.905.3. CLARIFY HOW THIS VENT IS
 CONNECTED TO THE HORIZONTAL DRAIN.
 93) SHT. P-8.1-SHT. P-8.1 - SUBMIT APPROVED ASSEMBLY
 DETAILS FOR THE FIRESTOP PENETRATION DETAILS.SUBMIT THE
 MANUFACTURER'S INFORMATION AND THE APPROVED LISTING
 NUMBERS. WPB AMEND. TO FBC SEC. 107.3.5.1.1.
 94) SHT. P-8.1 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE SUB-METERS. IF THE METERS WILL BE LOCATED IN A
 RETURN AIR CLOSET THEY SHALL MEET THE FLAME SPREAD
 INDEX AND SMOKE-DEVELOPED INDEX OF SEC. 602.2.1 OF THE
 FBC-MECHANICAL AND THE TEST CRITERIA OF ASTM E84 OR UL
 723.
 95) SHT. P-8.1 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC.
 107.2.1.
 96) SHT. P-8.1 - CLARIFY WHAT TYPE OF EFFLUENT WILL BE
 DISCHARGING FROM THE POOL EQUIPMENT INTO THE SANITARY
 SYSTEM. POOL WATER SHALL NOT BE DISCHARGED TO THE
 SANITARY SYSTEM PER CITY OF WEST PALM BEACH CODE OF
 ORDINANCES CHAPTER 90, ARTICLE III, SSEC.90-126 (B)(5)
 UNLESS SSPECIFICALLY AUTHORIZED BY THE CITY IN WRITING.
 97) SSHT. P-8.1 - PIPE HANGER DETAIL - PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC-PLUMBING SEC.308 AND
 TABLE 308.5.
 98) SUBMIT A COMPLETE UNDERGROUND SANITARY RISER DETAIL
 SHOWING ALL RISER CONNECTIONS, PIPE SIZES, VENTS,
 ETC.WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 99) SUBMIT A COMPLETE UNDERGROUND STORM DRAINAGE RISER
 DETAIL SHOWING ALL RISER CONNECTIONS, PIPE SIZES, GPM,
 ETC.
 100) SUBMIT A STORM DRAIN RISER SYSTEM FOR THE
 ABOVEGROUND STORM DRAIN COLLECCTION SYSTEM SHOWING
 RISER TAGS,PIPE SIZES, GPM THROUGH THE DRAINS AND
 PIPES. PROVIDE VERIFICATION THAT THE SIZING
 CALCULATIONS FOR THE SYSTEM INCLUDES 1/2 THE AREA OF
 ANY VERTICAL WALLS AND ANY DRAINAGE OF STORMWATER FROM
 UPPER ROOFS TO THE LOWER ROOF WHERE THE ROOF DRAINS ARE
 LOCATED. FBC-PLUMBING SEC.106.4.WPB AMEND. TO FBC SEC.
 107.2.1.
 101) SHT. A-7.6 - SANITATION UNIT DETAIL - A REDUCED
 PRESSURE BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED
 ON THE TRASH CHUTE WATER LINE PER FBC-PLUMBING
 608.13.2.
 102) THE WASHING MACHINE WATER SUPPLY VALVES SHALL BE
 PROVIDED WITH ACCESS WITHOUT MOVING THE UNIT. SHOW THE
 LOCATION OF THE VALVES ON THE PLANS. FBC-PLUMBING SEC.
 606.3.
 103) SUBMIT SANITARY AND WATER RISERS FOR ALL THE
 COMMON AREA PLUMBING FIXTURES AND TOILET ROOMS. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 104) THE WATER SUPPLY TO DISHWASHERS AND ICEMAKERS
 SHALL BE PROTECTED AGAINST BACKFLOW PER FBC-PLUMBING
 SEC.608..2. THE BACKFLOW DEVICE SHALL COMPLY WITH ASSE
 1024.
 105) SUBMIT A PIPING DETAIL FOR THE DOMESTIC BOOSTER
 SYSTEM AND SUBMIT WATER RISER DIAGAM FOR THE MAIN WATER
 SYSTEM IN THE BUILDING. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 106) PRESSURE REDUCING VALVES ARE REQUIRED ON THE WATER
 DISTRIBUTION SYSTEM WHERE THE WATER PRESSSURE WITHIN A
 BUILDING EXCEEDS 80 PSI STATIC.WATER PRESURE REDUCING
 VALVES SHALL CONFORM TO ASSE 1003 OR CSA B356. WATER
 PRESURE REDUCING VALVES, REGULATORS AND TRAINERS SHALL
 BE SO CONSTRUCTED AND INSTALLED AS TO PERMIT REPAIR OR
 REMOVAL OF PARTS WITHOUT BREAKING A PIPELINE OR
 REMOVING THE VALVE AND TRAINER FROM THE PIPELINE PER
 FBC SECS.604.8, 604.8.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  