Plan Review Notes
Plan Review Notes For Permit 20120803
Permit Number 20120803
Review Stop P
Sequence Number 1
Notes
Date Text
2021-03-04 18:48:131ST REVIEW FBC-2017 PLUMBING
 PERMIT-20120803
 3/15/2021
  
 CODES IN EFFECT:
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- THIS BUILDING WAS DESIGNED UNDER THE REQUIREMENTS OF
 THE FAIR HOUSING ACT. INDICATE ON THE PLAN IN EACH UNIT
 WHICH DESIGN SPECIFICATION ("A" OR "B" OF THE ACT) WAS
 USED IN THE DESIGN OF THE UNITS.
  
 2- THE WASHING MACHINE VALVES SHALL BE ACCESSIBLE
 WITHOUT MOVING THE UNIT PER THE 2017 FBC SEC. P 606.3
  
 3- THE ADDRESS OF THE PROJECT MUST BE ON THE PLANS. WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4- NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7. PER FBCACC SEC. 211.2 & FBC-PLUMBING SEC.
 410.3.
  
 5- ON PAGE A2.1.2 RR A-110 & RR A-109 WHERE PLUMBING
 FIXTURES ARE REQUIRED, SEPARATE FACILITIES SHALL BE
 PROVIDED FOR EACH SEX. PER FBC P 403.2
  
 6- ON PAGE A2.1.2 B1 UNITS DO NOT SHOW THE LAVATORIES
 OR THE WATER CLOSETS ON THE FLOOR PLAN
  
 7- ON PAGE A2.1.2 ASSE 1022 BACKFLOWS ARE REQUIRED FOR
 THE BISTRO BAR ICE MAKER AND DISHWASHER
  
 8- AN OUTSIDE SHOWER IS REQUIRED FOR THE POOL AREA
  
 9- PLEASE PROVIDE A DETAIL OF WHAT WILL BE INSTALLED IN
 THE DOG SPA
  
 10- REDUCED PRESSURE PRINCIPAL BACKFLOW PREVENTER IS
 REQUIRED FOR THE TRASH CHUTE WATER LINE THAT COMPLIES
 WITH FBCP 608.13.2
  
 11- ON PLAN PAGE A4.3 UNIT B1- PLEASE CLARIFY
 TUB/SHOWER? INDICATED IN THE SHOWER
  
 12- ON PLAN PAGE A4.9 DETAIL 7 & 8 UNIT B2 IS NOT A
 BATHROOM
  
 13- ON PLAN A5.1 IN THE WOMENS RESTROOM A-119 CLEAR
 FLOOR SPACE SHALL NOT IMPEDE ON THE WATER CLOSET 5'
 CLEAR FLOOR SPACE
  
 14- ON PLAN A5.1 BOH ROOM A-120 . PROVIDE ELEVATION ON
 THE CABINETRY AND SINK LOCATION
  
 15- ON PLAN A5.1 POWDER ROOM A-111 RESTROOMS INDICATE
 THE CLEAR FLOOR SPACE FOR THE LAVATORY
  
 16- ON PLAN A5.4 DETAIL NUMBER 2. PLEASE INDICATE THE
 INTERIOR DIMENTIONS OF THE ACCESSIBLE RESTOOMS & IN THE
 WOMENS RESTROOM A-119 CLEAR FLOOR SPACE SHALL NOT
 IMPEDE ON THE WATER CLOSET 5' CLEAR FLOOR SPACE
  
 17- PROVIDE SPECIFICATIONS ON THE ROOF DRAINS THAT WILL
 BE INSTALLED
  
 18- ON PAGE 256-P5.1 AAV'S ARE NOT ALLOWED TO BE
 INSTALLED ON THE 1ST- 4TH FLOORS PER FBCP 918.3.1 WHERE
 THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL
 BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND
 OUTDOORS TO THE OPEN AIR.
  
 19- WATER METERS : THERE IS NO INFORMATION ON THE SPECS
 SHOWING THE FLAME SPREAD INDEX AND SMOKE-DEVELOPED
 INDEX OF THE UNIT. IT MUST COMPLY WITH T SEC.602.2.1 OF
 THE MECHANICAL CODE AND COMPLY WITH THE TESTING
 CRITERIA IN ASTM E84 OR UL 723.
  
 20- ON PLAN PAGE A5.4 DETAIL 1 THE 5 FOOT WATER CLOSET
 CLEAR FLOOR SPACE SHALL NOT HAVE ANY OTHER PLUMBING
 FIXTURES INSIDE OF THAT 5 FOOT CLEAR FLOOR SPACE. THE
 URINAL SHALL BE RELOCATED. PLEASE SHOW THE CLEAR FLOOR
 SPACE FOR ALL OF THE ACCESSIBLE PLUMBING FIXTURES IN
 THE MEN'S AND WOMEN'S RESTROOMS.
  
 21- ON PLAN PAGE A5.4 DETAIL 2,3,4,5,8,9,10,11,12,14
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 22- ON PLAN PAGE A5.4 DETAIL 1 & 2 BOTH DETAILS
 INDICATE "POOL ACCESS/ PAVILLION LEVEL 1. PLEASE
 CLARIFY WHICH DETAIL IS FOR THE POOL ACCESS PAVILLION
 AND WHICH DETAIL IS FOR THE RESTROOM.
  
 23. PER FBCACC 2017 603.3 MIRRORS. A SINGLE FULL-LENGTH
 MIRROR CAN ACCOMMODATE A GREATER NUMBER OF PEOPLE,
 INCLUDING CHILDREN. IN ORDER FOR MIRRORS TO BE USABLE
 BY PEOPLE WHO ARE AMBULATORY AND PEOPLE WHO USE
 WHEELCHAIRS, THE TOP EDGE OF MIRRORS SHOULD BE 74
 INCHES (1880 MM) MINIMUM FROM THE FLOOR OR GROUND
  
 24- GRAB BARS ON A5.4 THE SIDE WALL GRAB BAR SHALL BE
 42 INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES
 (305 MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54
 INCHES (1370 MM) MINIMUM FROM THE REAR WALL. THE REAR
 WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 INCHES (610
 MM) MINIMUM ON THE OTHER SIDE.
  
 25. ON PAGE A5.4 TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9
 INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM
 AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR
 AND SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS
 SHALL NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT
 DOES NOT ALLOW CONTINUOUS PAPER FLOW.
  
 26. ON PAGE A5.4 IF SOAP AND TOWEL DISPENSERS ARE
 PROVIDED, THEY MUST BE LOCATED WITHIN THE REACH RANGES
 SPECIFIED IN 308. LOCATE SOAP AND TOWEL DISPENSERS SO
 THAT THEY ARE CONVENIENTLY USABLE BY A PERSON AT THE
 ACCESSIBLE LAVATORY.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  