Plan Review Notes
Plan Review Notes For Permit 20120803
Permit Number 20120803
Review Stop M
Sequence Number 1
Notes
Date Text
2021-01-29 07:43:301ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20120803
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: THE DEMO KITCHEN WILL NEED TO HAVE A
 SEPARATE PERMIT AND REVIEW FOR THE HOOD SYSTEM ALONG
 WITH AN AIR BALANCE REPORT. FBC M 508.1.2
  
 2) SHEET M2.1: PLEASE SHOW HOW THE LOUNGE/LOBBY WILL BE
 CONDITIONED. FBC 107.2.1
  
 3) SHEET M2.1.1: PLEASE SHOW VENTILATION FOR THE
 LOADING ZONE. FBC M TABLE 403.3.1.1
  
 4) SHEET M2.1.1: PLEASE SHOW HOW THE BIKE STORAGE WILL
 BE VENTILATED. FBC M TABLE 403.3.1.1
  
 5) PLEASE SHOW CONDENSATION DRAINAGE FOR THE MECHANICAL
 SYSTEMS AND WHERE THEY DRAIN. FBC M 307.2.1
  
 6) SHEET M2.2: PLEASE EXPLAIN WHY THE MECHANICAL CLOSET
 FOR AHU-1 DOES NOT HAVE RATED WALLS. FBC 107.2.1
  
 7) SHEET M2.1: IT APPEARS THAT AHU-7 IS LOCATED IN THE
 CORRIDOR WITHOUT A MECHANICAL CLOSET. HOW ARE YOU
 PROVIDING SEPARATION OF THE UNIT FROM THE CORRIDOR? FBC
 107.2.1
  
 8) SHEET M7.1: PLEASE PROVIDE OUTDOOR AIR AND
 VENTILATION CALCULATIONS FOR ALL SPACES IN THIS
 BUILDING. FBC M TABLE 403.3.1.1
  
 9) PLEASE PROVIDE DETAILS FOR THE AIR INTAKE AND
 EXHAUST TERMINATIONS FOR THE UNITS. FBC 107.2.1
  
 10) SHEETS M4.1, M4.2: PLEASE SHOW DRYER DUCT LENGTHS
 FOR EACH UNIT. IF THE DUCT EXTENDS BEYOND THE LENGTH
 ALLOWED BY THE CODE PLEASE PROVIDE THE MAKE MODEL AND
 ALLOWABLE DUCT LENGTHS OF THE DRYERS SPECIFIED. FBC M
 504.8.4.2
  
 11) SHEETS M4.1, M4.2: PLEASE SHOW THAT THE DRYER DUCT
 MEETS LENGTH IDENTIFICATION. FBC M 504.8.5
  
 12) SHEET M4.2: AHU-B FOR UNIT B AND UNIT B1-MOD
 INDICATES AHU-B IS SUPPLYING 840 CFM BUT SHEET M7.1
 INDICATES THAT AHU-B WILL ONLY SUPPLY 800 CFM. PLEASE
 CORRECT THIS. FBC EC C403
  
 13) SHEET M4.2: INDICATES THAT AHU-B IS SUPPLYING 860
 CFM BUT SHEET M7.1 INDICATES THAT AHU-B?S MAXIMUM
 SUPPLY IS 800 CFM. PLEASE CORRECT THIS. FBC EC C403
  
 14) PLEASE SHOW THAT THE PARKING GARAGE MEETS
 VENTILATION REQUIREMENTS OF FBC M 404
  
 15) THE PERMIT APPLICATION INDICATES WORK DESCRIPTION
 AS A 374 UNIT APARTMENT BUILDING BUT PAGE 22 OF 48 IN
 THE ENERGY GAUGE CALCULATIONS UNDER SPACES THE UNITS
 ARE LISTED AS SERVING ?GUEST ROOMS (HOTEL)? PLEASE BE
 CONSISTENT, IF THIS IS AN APARTMENT BUILDING THE ENERGY
 GAUGE SHOULD REFLECT THIS. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  