2021-01-29 07:43:30 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-20120803 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2020 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M2.1: THE DEMO KITCHEN WILL NEED TO HAVE A |
| SEPARATE PERMIT AND REVIEW FOR THE HOOD SYSTEM ALONG |
| WITH AN AIR BALANCE REPORT. FBC M 508.1.2 |
| |
| 2) SHEET M2.1: PLEASE SHOW HOW THE LOUNGE/LOBBY WILL BE |
| CONDITIONED. FBC 107.2.1 |
| |
| 3) SHEET M2.1.1: PLEASE SHOW VENTILATION FOR THE |
| LOADING ZONE. FBC M TABLE 403.3.1.1 |
| |
| 4) SHEET M2.1.1: PLEASE SHOW HOW THE BIKE STORAGE WILL |
| BE VENTILATED. FBC M TABLE 403.3.1.1 |
| |
| 5) PLEASE SHOW CONDENSATION DRAINAGE FOR THE MECHANICAL |
| SYSTEMS AND WHERE THEY DRAIN. FBC M 307.2.1 |
| |
| 6) SHEET M2.2: PLEASE EXPLAIN WHY THE MECHANICAL CLOSET |
| FOR AHU-1 DOES NOT HAVE RATED WALLS. FBC 107.2.1 |
| |
| 7) SHEET M2.1: IT APPEARS THAT AHU-7 IS LOCATED IN THE |
| CORRIDOR WITHOUT A MECHANICAL CLOSET. HOW ARE YOU |
| PROVIDING SEPARATION OF THE UNIT FROM THE CORRIDOR? FBC |
| 107.2.1 |
| |
| 8) SHEET M7.1: PLEASE PROVIDE OUTDOOR AIR AND |
| VENTILATION CALCULATIONS FOR ALL SPACES IN THIS |
| BUILDING. FBC M TABLE 403.3.1.1 |
| |
| 9) PLEASE PROVIDE DETAILS FOR THE AIR INTAKE AND |
| EXHAUST TERMINATIONS FOR THE UNITS. FBC 107.2.1 |
| |
| 10) SHEETS M4.1, M4.2: PLEASE SHOW DRYER DUCT LENGTHS |
| FOR EACH UNIT. IF THE DUCT EXTENDS BEYOND THE LENGTH |
| ALLOWED BY THE CODE PLEASE PROVIDE THE MAKE MODEL AND |
| ALLOWABLE DUCT LENGTHS OF THE DRYERS SPECIFIED. FBC M |
| 504.8.4.2 |
| |
| 11) SHEETS M4.1, M4.2: PLEASE SHOW THAT THE DRYER DUCT |
| MEETS LENGTH IDENTIFICATION. FBC M 504.8.5 |
| |
| 12) SHEET M4.2: AHU-B FOR UNIT B AND UNIT B1-MOD |
| INDICATES AHU-B IS SUPPLYING 840 CFM BUT SHEET M7.1 |
| INDICATES THAT AHU-B WILL ONLY SUPPLY 800 CFM. PLEASE |
| CORRECT THIS. FBC EC C403 |
| |
| 13) SHEET M4.2: INDICATES THAT AHU-B IS SUPPLYING 860 |
| CFM BUT SHEET M7.1 INDICATES THAT AHU-B?S MAXIMUM |
| SUPPLY IS 800 CFM. PLEASE CORRECT THIS. FBC EC C403 |
| |
| 14) PLEASE SHOW THAT THE PARKING GARAGE MEETS |
| VENTILATION REQUIREMENTS OF FBC M 404 |
| |
| 15) THE PERMIT APPLICATION INDICATES WORK DESCRIPTION |
| AS A 374 UNIT APARTMENT BUILDING BUT PAGE 22 OF 48 IN |
| THE ENERGY GAUGE CALCULATIONS UNDER SPACES THE UNITS |
| ARE LISTED AS SERVING ?GUEST ROOMS (HOTEL)? PLEASE BE |
| CONSISTENT, IF THIS IS AN APARTMENT BUILDING THE ENERGY |
| GAUGE SHOULD REFLECT THIS. FBC 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |