2021-10-07 08:11:36 | 1ST REVIEW FBC-2017 GAS |
| PERMIT-20120803 |
| 10/7/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THERE IS GAS ON PLAN PAGE P-8.3 INDICATING THAT |
| THERE WILL BE 12 GAS TANKLESS WATERHEATERS. PLEASE |
| INDICATE ON THE PLANS WHERE THESE WILL BE LOCATED? WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 2) ON PLAN PAGE P-8.1 THERE IS A GAS DIAGRAM SHOWN, |
| PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS |
| THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC |
| FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS |
| RES SECS. G2413.4.1, G2413.4.2. |
| 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 4) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC. |
| 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| 5) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS |
| SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) |
| THROUGH 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC. |
| G2413. |
| 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2 OR 2017 |
| FBC FUEL GAS RES. SEC. G2413.2. |
| 7) SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| 8) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| 9) INDICATE ON THE PLAN SHOWING THE LOCATION OF THE |
| TANKLESS WATER HEATERS AND THE LOCATION AND DISTANCE OF |
| ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| HEATERS. THE LOCATION OF THE WATER HEATERS SHALL COMPLY |
| WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 10) REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| 11) SUBMIT A COPY OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM 2017 FBC FUEL GAS SEC. 402.3 OR 2017 FBC FUEL |
| GAS RES. SEC. G2413.3 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |