Date |
Text |
2021-01-19 16:31:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET C 07 - THERE IS AN INDICATION OF A FDC ON THE |
| EAST SIDE OF A GATED FENCE AND A FIRE HYDRANT ON THE |
| WEST SIDE. |
| |
| THESE NEED TO BE ON THE SAME SIDE OF FENCE WITHIN 100' |
| OF EACH OTHER. |
| |
| PLEASE CORRECT AND SEE 1A BELOW. |
| |
| |
| 1A) SHEET C 07 - A PROJECT OF THIS SIZE IS RECOMMENDED |
| TO HAVE 2 FDC'S AND 2 FIRE HYDRANT FOR FIRE GROUND |
| OPERATIONAL TACTIC'S AND STRATEGIES . |
| |
| ONE SET IS RECOMMENDED TO BE ON THE WEST SIDE OF THE |
| GATED FENCE NEAR THE THE PARKING GARAGE WITH THE FDC |
| LOCATED ON THE SAME ISLAND AS THE FIRE HYDRANT. |
| |
| THE SECOND SET IS RECOMMENED TO BE ON THE EAST SIDE OF |
| GATED FENCE LOCATED AT THE ROUND ABOUT ALONG THE EAST |
| ORDER (SIMILAR SIDE AS THE PROPOSED HOTEL) |
| |
| PLEASE REVIEW AND CORRECT |
| |
| |
| 1B) SHEET C 07 & F 0.1 - THERE ARE INDICATIONS OF FIRE |
| LINE UNDERGROUND WORK INCLUDING FIRE HYDRANTS AND FDC |
| LINES. |
| |
| ALL FIRE LINE WORK SHALL BE INSTALLED UNDER SEPARATE |
| PERMITS AND SHOP DRAWINGS, INCLUDING MANUFACTURERS |
| SPECIFICATION SHEETS. |
| |
| PLEASE REVIEW AND CORRECT AND PROVIDE AN APPLICABLE |
| NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| 1C) C 07 & FP SHEETS - A WATER SUPPLY SHALL BE PROVIDED |
| PRIOR TO VERITICAL CONSTRUCTION AND FIRE PROTECTION |
| STANDPIPES PER NFPA 241 |
| |
| 7.5.8 HYDRANTS. |
| 7.5.8.1 FREE ACCESS FROM THE STREET TO FIRE HYDRANTS |
| AND TO |
| OUTSIDE CONNECTIONS FOR STANDPIPES, SPRINKLERS, OR |
| OTHER FIRE |
| EXTINGUISHING EQUIPMENT, WHETHER PERMANENT OR |
| TEMPORARY, |
| SHALL BE PROVIDED AND MAINTAINED AT ALL TIMES. |
| |
| 8.7.4.2 STANDPIPE INSTALLATIONS IN BUILDINGS UNDER |
| CONSTRUCTION. |
| WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IN |
| BUILDINGS UNDER CONSTRUCTION, A STANDPIPE SYSTEM, |
| EITHER TEMPORARY |
| OR PERMANENT IN NATURE, SHALL BE INSTALLED IN |
| ACCORDANCE |
| WITH 8.7.4.2.1 THROUGH 8.7.4.2.10. |
| |
| STANDPIPE CONNECTIONS, AT LEASET ONE FOR THE APT BLDG |
| AND ONE FOR THE GARAGE, WITH FDC'S SHALL BE INSTALLED |
| BEGINNING WITH THE 4 FLOOR |
| |
| PLEAE REVIEW AND PROVIDE AN APPLICABLE NOTE. |
| |
| |
| |
| |
| 2) SHEET LS 0.1 - THERE ARE INDICATIONS OF EXIT SIGNS |
| AT DOUBLE SWING CORRIDOR DOORS. THE EXIT SIGN IS |
| INDICATED AT THE CENTER OF THOSE DOORS. |
| |
| THE EXIT SIGN SHOULD BE LOCATED OVER THE CENTER OF THE |
| DOOR IN THE PATH OF EXIT TRAVEL. |
| |
| PER NFPA 101, CH 7 MEANS OF EGRESS |
| |
| 7.10.1.9 MOUNTING LOCATION. THE BOTTOM OF NEW EGRESS |
| MARKINGS SHALL BE LOCATED AT A VERTICAL DISTANCE OF NOT |
| MORE THAN 6 |
| FT 8 IN. (2030 MM) ABOVE THE TOP EDGE OF THE EGRESS |
| OPENING |
| INTENDED FOR DESIGNATION BY THAT MARKING. EGRESS |
| MARKINGS SHALL |
| BE LOCATED AT A HORIZONTAL DISTANCE OF NOT MORE THAN |
| THE REQUIRED |
| WIDTH OF THE EGRESS OPENING, AS MEASURED FROM THE EDGE |
| OF THE |
| EGRESS OPENING INTENDED FOR DESIGNATION BY THAT MARKING |
| TO THE |
| NEAREST EDGE OF THE MARKING. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 3) SHEET LS 0.2 - THERE ARE INDICATIONS OF EXIT SIGNS |
| ON EACH SIDE OF THE DOUBLE SWING CORRIDOR DOORS AT THE |
| SIDES OF THE BRIDGE. |
| |
| EXIT TRAVEL PATHS SHALL BE IN ONLY ONE DIRECTION UNLESS |
| THERE IS A HORIZONTAL EXIT OR ARE THESE SMOKE DOORS. |
| |
| IS IT INTENDED FOR THESE DOUBLE DOORS TO FUNCTION AS |
| HORIZONTAL EXITS. |
| |
| PLEASE REVIEW AND PROVIDE DETAILS, CORRECT AND MOVE THE |
| EXIT SIGNS OVER THE APPLICABLE DOOR. |
| |
| |
| |
| 4) SHEET LS .02 - THERE ARE INDICATIONS OF DIMENSIONS |
| BETWEEN THE STAIRWELLS; HOWEVER, THERE ARE NO |
| INDICATIONS OF HOW IT IS MEASURED. |
| |
| PER NFPA 14 |
| |
| 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A |
| NONSPRINKLERED |
| FLOOR OR STORY IS LOCATED IN EXCESS OF 150 FT (45.7 M) |
| OF TRAVEL |
| DISTANCE FROM A HOSE CONNECTION IN OR ADJACENT TO A |
| REQUIRED |
| EXIT OR THE MOST REMOTE PORTION OF A SPRINKLERED FLOOR |
| OR STORY |
| IS LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL |
| DISTANCE FROM A |
| HOSE CONNECTION IN OR ADJACENT TO A REQUIRED EXIT, |
| ADDITIONAL |
| HOSE CONNECTIONS SHALL BE PROVIDED, IN APPROVED |
| LOCATIONS, |
| WHERE REQUIRED BY THE LOCAL FIRE DEPARTMENT OR THE AHJ. |
| |
| THE MEAASUREMENT NEEDS TO BE FROM THE HOSE CONNECTION |
| TO THE MOST REMOTE PORTION WITHIN A LIVING UNIT OR |
| OTHER APPLICABLE REMOTE AREA. |
| |
| PLEASE REVIEW AND PROVIDE GREATER DETAILED |
| MEASURERMENTS AND CORRECT AS APPLICABLE. |
| |
| |
| 5) FP SHEETS - THERE ARE NO INDICATION OF FIRE |
| SPRINKLER PROTECTION WITHIN THE WASTE CHUTE. |
| |
| PER NFPA 101, CH 30 , NFPA 13 & 82 |
| |
| 30.5.4 WASTE CHUTES, INCINERATORS, AND LAUNDRY CHUTES. |
| WASTE CHUTES, INCINERATORS, AND LAUNDRY CHUTES SHALL |
| COMPLY WITH |
| THE PROVISIONS OF SECTION 9.5. |
| |
| 9.5.2 INSTALLATION AND MAINTENANCE. WASTE CHUTES, |
| LAUNDRY |
| CHUTES, AND INCINERATORS SHALL BE INSTALLED AND |
| MAINTAINED IN |
| ACCORDANCE WITH NFPA 82, STANDARD ON INCINERATORS AND |
| WASTE |
| AND LINEN HANDLING SYSTEMS AND EQUIPMENT, UNLESS SUCH |
| INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| WHICH SHALL BE |
| PERMITTED TO BE CONTINUED IN SERVICE. |
| |
| 22.15.2.2.1 GRAVITY WASTE OR LINEN CHUTES. [82:5.2] |
| 22.15.2.2.1.1 GRAVITY CHUTES SHALL BE PROTECTED |
| INTERNALLY BY |
| AUTOMATIC SPRINKLERS UNLESS THEY ARE LINED IN |
| ACCORDANCE WITH |
| 5.2.2.6.1 IN NFPA 82. [82:5.2.2.6.2; 82:5.2.6.1.1] |
| 22.15.2.2.1.2 THIS PROTECTION REQUIRES THAT A SPRINKLER |
| BE INSTALLED |
| AT OR ABOVE THE TOP SERVICE OPENING OF THE CHUTE. |
| [82:5.2.6.1.2] |
| |
| PLEASE REVIEW AND CORRECT AND PROVIDE AN APPLICABLE |
| NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| 6) SHEET F 2.1 THRU 2.7 - THERE ARE NO INDICATIONS OF |
| FIRE SPRINKLER PROTECTION WITHIN THE PARKING GARAGE. |
| |
| IS THE PARKING GARAGE PROPOSED TO BE OPEN OR CLOSED? |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.5.7 OPEN PARKING STRUCTURES COMPLYING WITH NFPA |
| 88A, |
| STANDARD FOR PARKING STRUCTURES, THAT ARE CONTIGUOUS |
| WITH APARTMENT |
| BUILDINGS SHALL BE EXEMPT FROM THE SPRINKLER |
| REQUIREMENTS OF 30.3.5.1. |
| |
| PER NFPA 88A |
| |
| 5.5 OPENING REQUIREMENTS FOR OPEN PARKING STRUCTURES. |
| 5.5.1 EACH PARKING LEVEL SHALL HAVE WALL OPENINGS OPEN |
| TO THE |
| ATMOSPHERE, FOR AN AREA OF NOT LESS THAN 0.4 M2 FOR |
| EACH LINEAR |
| METER (1.4 FT2 FOR EACH LINEAR FOOT) OF ITS EXTERIOR |
| PERIMETER. |
| 5.5.2 SUCH OPENINGS SHALL BE DISTRIBUTED OVER 40 |
| PERCENT OF |
| THE BUILDING PERIMETER OR UNIFORMLY OVER TWO OPPOSING |
| SIDES. |
| 5.5.3 INTERIOR WALL LINES AND COLUMN LINES SHALL BE AT |
| LEAST 20 PERCENT |
| OPEN, WITH OPENINGS DISTRIBUTED TO PROVIDE VENTILATION. |
| |
| |
| PLEASE REVIEW AND PROVIDE APPLICABLE SPECIFIC DETAILS |
| OR CORRECT. BE SURE TO INCLUDE SPECIFIC FIRE SEPARATION |
| DETAILS BETWEEN THE GARAGE AND APARTMENT BUILDING PER |
| NFPA 101, CH 6 OCCUPANCY CLASSIFICATIONS. |
| |
| |
| 7) THERE ARE NO INDICATIONS OF 2 - WAY EMERGENCY RADIO |
| COMMUNICATIONS. |
| |
| PER NFPA 1 & 72 |
| |
| NFPA 1 |
| |
| 11.10* TWO-WAY RADIO COMMUNICATION ENHANCEMENT SYSTEMS. |
| 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| RADIO SIGNAL |
| STRENGTH FOR FIRE DEPARTMENT COMMUNICATIONS SHALL BE |
| MAINTAINED AT A |
| LEVEL DETERMINED BY THE AHJ. |
| 11.10.2 WHERE REQUIRED BY THE AHJ, TWO-WAY RADIO |
| COMMUNICATION |
| ENHANCEMENT SYSTEMS SHALL COMPLY WITH NFPA 72. |
| |
| NFPA 72 |
| |
| 24.5.2* TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT |
| SYSTEMS. |
| |
| 24.5.2.1.2 APPROVAL AND PERMIT. PLANS SHALL BE |
| SUBMITTED FOR |
| APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF |
| SUCCESSFUL |
| ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED |
| FOR THE |
| PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED |
| BY |
| THE AUTHORITY HAVING JURISDICTION. |
| 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE |
| PROVIDED |
| THROUGHOUT THE BUILDING AS A PERCENTAGE OF FLOOR AREA |
| AS SPECIFIED |
| IN 24.5.2.2.1 THROUGH 24.5.2.2.3. |
| 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE |
| FIRE COMMAND |
| CENTER(S), THE FIRE PUMP ROOM(S), EXIT STAIRS, EXIT |
| PASSAGEWAYS, |
| ELEVATOR LOBBIES, STANDPIPE CABINETS, SPRINKLER |
| SECTIONAL |
| VALVE LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE |
| AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH |
| 99 PERCENT |
| FLOOR AREA RADIO COVERAGE. |
| 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING |
| AREAS |
| SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA RADIO |
| COVERAGE. |
| 24.5.2.2.3 AMPLIFICATION COMPONENTS. BUILDINGS AND |
| STRUCTURES |
| THAT CANNOT SUPPORT THE REQUIRED LEVEL OF RADIO |
| COVERAGE |
| SHALL BE EQUIPPED WITH A RADIATING CABLE SYSTEM OR A |
| DISTRIBUTED |
| ANTENNA SYSTEM (DAS) WITH FCC-CERTIFIED SIGNAL |
| BOOSTERS, |
| OR BOTH, OR WITH A SYSTEM THAT IS OTHERWISE APPROVED, |
| IN ORDER |
| TO ACHIEVE THE REQUIRED ADEQUATE RADIO COVERAGE. |
| 24.5.2.3 SIGNAL STRENGTH. |
| 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH |
| OF |
| ?95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE |
| AUTHORITY |
| HAVING JURISDICTION, SHALL BE PROVIDED THROUGHOUT THE |
| COVERAGE |
| AREA. |
| 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH |
| OF ?95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH |
| AS REQUIRED |
| BY THE AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED |
| FROM THE COVERAGE AREA. |
| 24.5.2.3.3 ISOLATION. IF A DONOR ANTENNA EXISTS, |
| ISOLATION SHALL |
| BE MAINTAINED BETWEEN THE DONOR ANTENNA AND ALL INSIDE |
| ANTENNAS |
| AND SHALL BE A MINIMUM OF 15 DB ABOVE THE SIGNAL |
| BOOSTER GAIN UNDER ALL OPERATING CONDITIONS. |
| |
| ALL BDA WORK SHALL BE INSTALLED UNDER SEPARATE PERMIT |
| AND SHOP DRAWINGS. |
| |
| PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE AND |
| A NOTE OF ACKNOWLEDGEMENT TO PROVIDE |
| |
| |
| 8) ROOF FP SHEETS - THERE ARE NO INDICATIONS OF FIRE |
| SPRINKLER PROTECTION WITHIN THE CONCEALED ROOF SPACES. |
| |
| PER NFPA 72 |
| |
| 8.15.1 CONCEALED SPACES. |
| 8.15.1.1 CONCEALED SPACES REQUIRING SPRINKLER |
| PROTECTION. |
| CONCEALED SPACES OF EXPOSED COMBUSTIBLE CONSTRUCTION |
| SHALL |
| BE PROTECTED BY SPRINKLERS EXCEPT IN CONCEALED SPACES |
| WHERE |
| SPRINKLERS ARE NOT REQUIRED TO BE INSTALLED BY |
| 8.15.1.2.1 |
| THROUGH 8.15.1.2.18 AND 8.15.6. |
| |
| PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE AND |
| A NOTE OF ACKNOWLEDGEMENT TO PROVIDE |
| |
| |
| |
| 9) FIRE ALARM/ELECTICAL SHEETS- ALL FIRE ALARM WORK |
| SHALL BE INSTALLED UNDER SEPARATE PERMIT AND SHOP |
| DRAWINGS. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGEMENT. |
| |
| |
| 9A) FIRE ALARM/ELECTICAL SHEETS- THERE ARE INDICATIONS |
| OF PULL STATIONS THROUGHOUT THE OCCUPANCY. |
| |
| TO REDUCE THE POTENTIAL FOR ACCIDENTAL/INTENTIONAL |
| FALSE ALARMS THE NUMBER OF PULL STATIONS CAN BE |
| REDUCE/ELIMINATED WHERE NOT REQUIRED BY THE CODE. |
| |
| PER NFPA 101 CH 30 & CH 9 |
| |
| 30.3.4.2 INITIATION. |
| |
| 30.3.4.2.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH 30.3.5, |
| REQUIRED FIRE ALARM SYSTEMS SHALL BE INITIATED UPON |
| OPERATION OF |
| THE AUTOMATIC SPRINKLER SYSTEM. |
| |
| 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE |
| DETECTION OR |
| WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM |
| SYSTEM IN |
| ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN |
| ONE MANUAL |
| FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY |
| HAVING |
| JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE |
| ALARM SIGNAL. |
| |
| PULL STATION ON UPPER FLOORS CAN BE REMOVED. |
| |
| PULL STATIONS ON THE 1ST FLOOR CAN BE REDUCED. |
| |
| PLEASE REVIEW AND REDUCE LOCATIONS IN CONSULTATION WITH |
| OF OFFICE OF THE FIRE MARSHAL AND PROVIDE A NOTE OF |
| ACKNOWLEDGEMENT UNLESS THE OWNER/EOR SPECIFCALLY |
| REQUEST THESE LOCATIONS. |
| |
| |
| |
| 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |