2021-02-09 15:43:39 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY BN, BU, PX |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1) NEED TO SHOW A ONLINE DIAGRAM OF THE SERVICES AND |
| HOW THIS WILL WORK IN THE BUILDING. |
| |
| 2) I DON'T SEE AN EMERGENCY SYSTEM? LIGHTS, FIRE PUMP, |
| ELEVATORS??? |
| |
| 3) PLEASE PROVIDE AN ELECTRICAL ROOM LAYOUT FOR EACH |
| ELECTRICAL ROOM. |
| |
| 4) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE |
| ALARM SYSTEM. PAGE E-5.2 |
| |
| 5) MOST SERVICE MAINS WILL BE REQUIRED TO COMPLY WITH |
| 240.87 PLEASE INDICATE HOW THIS WILL BE ACOMPLISHED. |
| |
| 6) NEED TO SHOW FAULT CURRENT CALCULATIONS FOR THE |
| MAINS AND SUB PANELS PER 110.9, 110.10 PAGES E-5.1, |
| E-5.2, AND NOTED ON THE PLAN FOR THE SIGNAGE NEEDED PER |
| 110.24. |
| |
| 7) HOW ARE THE GOUPING OF THE SERVICE MAINS THAT DON'T |
| MEET EXCEPTIONS HP1A, HP3B, AMENITY, FIRE PUMP. |
| |
| 8) FIRE PUMP SHOWS ONLY FPL FPL IS NOT A RELIABLE |
| SOURCE OF POWER PER 695.3 |
| |
| 9) GARAGE CIRCUITS SHALL COME FROM ONE SOURCE ONLY |
| CAN'T TELL IF ALL CIRCUITS COME FROM SAME SOURCE PAGES |
| E-2.1--E-2.6 |
| |
| 10) IF YOU ARE SUPPLYING SHUNT TRIPS TO THE FIRE COMAND |
| CENTER HOW ARE THE OTHER NON-SHUNTED SREVICES GOING TO |
| COMPLY WITH A SAFE SYSTEM? |
| |
| 11) SMOKE ALARMS IN UNITS NEED TO BE ADJUSTED TO MEET |
| THE REQUIREMENTS OF NFPA 72 WITH REFERENCE TO LOCATION |
| TO BATHROOMS, AND KITCHEN COOKING APPLIANCES. |
| |
| 12) SIGNAGE AND DIRECTORIES NEEDED TO BE INSTALLED FOR |
| THE SERVICE LOCATIONS THROUGHOUT THE BUILDING WILL NEED |
| TO BE SUBMITTED FOR REVIEW BY THE FIRE DEPTARTMENT. |
| PLEASE INSERT A PAGE INTO THE ELECTRICAL DRAWINGS FOR |
| REVIEW. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6713 |