Plan Review Notes
Plan Review Notes For Permit 20120797
Permit Number 20120797
Review Stop HIST
Sequence Number 3
Notes
Date Text
2021-04-08 12:04:14THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 ORDER DETAIL QUOTE UNIT #1 ?
 REVISE #2 TO BE A STANDARD SINGLE-HUNG.
 REVISE #4 TO BE A STANDARD SINGLE-HUNG.
 REVISE #5, #6, AND #7 TO BE A STANDARD SINGLE-HUNG. NO
 MUNTINS ARE REQUIRED.
 UNABLE TO DETERMINE #9. INSUFFICIENT INFORMATION
 PROVIDED.
 UNABLE TO DETERMINE #10. INSUFFICIENT INFORMATION
 PROVIDED.
  
 PICTURE OF PROPOSED GLASS INSERT DOOR -
 REVISE OPENING #1 AND #8 TO BE A MULTIPLE PANEL DOOR.
 IF GLASS IS DESIRED TOP 1/4 OR 1/2 ONLY.
  
 ORDER FOR ENTRANCE DOOR WITH LOW PROFILE MUNTINS DOES
 NOT SPECIFICALLY INDICATE A LOW-PROFILE MUNTIN PROFILE
 OR ANY OTHER MUNTIN PROFILE PATTERN.
  
 PHOTOGRAPHS OF THE EXISTING OPENINGS ? EVERY OPENING
 MUST BE LABELED AND CLEARLY VISIBLE. SUPPLY IN COLOR.
  
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE. CONFIRM THAT
 THESE CONDITIONS WILL BE COMPLIED WITH. NOTE, IF THE
 EXISTING MULLION IS NOT FLUSH WITH THE EXTERIOR WINDOW
 FRAME CASING, THE NEW MULLION MUST REPLICATE THIS
 APPEARANCE.
  
 1. ALL REPLACEMENT WINDOWS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS) AND
 MATCH THE LOCATION/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS.
 2. THE EXISTING MULLION SHALL REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT.
 3. ALL STREET OR SIDEWALK FACING GLASS SHALL BE CLEAR.
 ALL NON-STREET FACING GLASS SHALL BE CLEAR OR CLEAR
 WITH LOW-E COATING. NO TINT. OBSCURED TEXTURED GLASS
 MAY BE USED ON NON-STREET FACING BATHROOMS ONLY.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  
  