Plan Review Notes For Permit 20120790 |
Permit Number |
20120790 |
|
Review Stop |
SIGNATURE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-04-23 15:52:52 | SAME COMMENTS AS REVIEW NO. 1 BY MR. MCDOUGAL. NEW | | ORIGINALS SUBMITTED DID NOT INCLUDE THE PRECAST PAD | | DRAWING SO THE DIGITAL SIGNATURE IS STILL MISSING. | | | | THE GENERATOR PAD DRAWING DOES NOT HAVE THE ENGINEER'S | | DIGITAL SIGNATURE. ELECTRONICALLY SUBMITTED DRAWINGS | | ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE | | ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED | | AND SEALED PAPER VERSION OF DRAWINGS. AFTER THE | | ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE | | CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT | | TO BE VERIFIED. THE ENGINEER'S ORIGINAL HANDWRITTEN | | SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. | | NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE | | ACCEPTABLE. FS 471 & 61G15 | | | | ELECTRICAL SIGNATURE IS GOOD JLEAHY |
|