Plan Review Notes For Permit 20120790 |
Permit Number |
20120790 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-07 10:44:54 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM | | OPENINGS INTO A BUILDING. REVISE NOTE ON THE SURVEY. | | FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | 2) SEE SIGNATURE COMMENTS. | | | | |
|