Plan Review Notes
Plan Review Notes For Permit 20120753
Permit Number 20120753
Review Stop E
Sequence Number 1
Notes
Date Text
2020-12-29 12:17:43CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) SHEET 2.0E MENTIONS RTU4 BEING THE ONLY NEW ROOF TOP
 UNIT. PLEASE SHOW LOCATION OF THIS UNIT, DISCONNECT,
 AND FEEDING THE UNIT. PLEASE SHOW GFI RECEPTACLE NEAR
 THIS UNIT TOO. FBC 107
 2) PANEL D CIRCUITS 5,7,9 FOR AN RTU SPECIFY 60 AMPS
 BREAKER WITH WIRE SIZE #8. IS THIS THE NEW RTU4? THE
 ORIGINAL MASTER PLANS (PERMIT 19120428) HAS SPECS FOR
 RTU4 (TRANE TSCO60) WITH A 40 AMPS BREAKER SIZE. PLEASE
 CORRECT DISCREPANCIES AND SPECIFY CORRECT BREAKER SIZE
 AND WIRE SIZE ON PANEL SCHEDULE D (#8 WIRE SIZE MIGHT
 BE TOO SMALL FOR A 60 AMPS BREAKER).
 3) TOTAL LOAD FOR PANEL D IS SHOWN AS 135035 VA WITH I=
 375 AMPS. PANEL IS ONLY 200 AMPS. LOADS ON PANEL
 SCHEDULE DO NOT SEEM TO TOTAL 135035 VA. PLEASE CLARIFY
 AND CORRECT.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER