2020-12-29 12:17:43 | CODES IN EFFECT |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| REVIEW STATUS: FAILED. |
| |
| 1) SHEET 2.0E MENTIONS RTU4 BEING THE ONLY NEW ROOF TOP |
| UNIT. PLEASE SHOW LOCATION OF THIS UNIT, DISCONNECT, |
| AND FEEDING THE UNIT. PLEASE SHOW GFI RECEPTACLE NEAR |
| THIS UNIT TOO. FBC 107 |
| 2) PANEL D CIRCUITS 5,7,9 FOR AN RTU SPECIFY 60 AMPS |
| BREAKER WITH WIRE SIZE #8. IS THIS THE NEW RTU4? THE |
| ORIGINAL MASTER PLANS (PERMIT 19120428) HAS SPECS FOR |
| RTU4 (TRANE TSCO60) WITH A 40 AMPS BREAKER SIZE. PLEASE |
| CORRECT DISCREPANCIES AND SPECIFY CORRECT BREAKER SIZE |
| AND WIRE SIZE ON PANEL SCHEDULE D (#8 WIRE SIZE MIGHT |
| BE TOO SMALL FOR A 60 AMPS BREAKER). |
| 3) TOTAL LOAD FOR PANEL D IS SHOWN AS 135035 VA WITH I= |
| 375 AMPS. PANEL IS ONLY 200 AMPS. LOADS ON PANEL |
| SCHEDULE DO NOT SEEM TO TOTAL 135035 VA. PLEASE CLARIFY |
| AND CORRECT. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |