2021-03-09 12:06:02 | 2ND REVIEW FBC-2017 RES. |
| PERMIT- 20120717 |
| 3/9/21 |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| PLAN REVIEW RESULTS: DENIED. |
| FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW |
| WITH NOTES ADDED FOR FURTHER CLARIFICATION |
| 1) FAILED. GAS RISER: THE RESUBMITTED GAS RISER IS NOT |
| LEGIBLE. THE PRINT AND DETAILS ARE TOO FAINT TO READ. |
| PLEASE RESUBMIT A CLEAR COPY WITH EMBOLDENED PRINT FOR |
| REVIEW AND FOR PUBLIC RECORD SCANNING- SECTION 107.2.1 |
| WPB. |
| A) PROVIDE THE SIZE OF THE PIPE FROM THE METER TO THE |
| 1ST AND 2ND TEES- G2413.4.1 FBC RES. |
| B) PROVIDE THE SIZE OF THE PIPE DROP FROM THE 2ND TEE |
| TO THE LOW PRESSURE REGULATOR, AND THE BRANCH PIPE |
| SIZES FROM THE REGULATOR TO THE WATER HEATER, DRYER AND |
| RANGE- G2413.4.1 & G2413.4.2. |
| C) PROVIDE THE TOTAL GAS LOAD OF THE SYSTEM AND THE |
| TOTAL DEVELOPED LENGTH FROM THE METER TO THE MOST |
| REMOTE OUTLET- G2413.1, G2413.2, & G2413.4.1. |
| 2) FAILED. THE TANKLESS WATER HEATER, BBQ, FIREPLACE, |
| AND POOL HEATER WERE NOT INCLUDED IN THE MASTER PERMIT- |
| 20071263. PLEASE PROVIDE THE FOLLOWING ITEMS: THE SPECS |
| FOR THE BBQ GRILL AND FIREPIT WERE NOT SUBMITTED. |
| PLEASE DO NOT SUBMIT ENTIRE INSTALLATION MANUALS- THOSE |
| CAN BE ONSITE. SUBMIT ONLY THE MANUFACTURER?S |
| SPECIFICATIONS SHEETS WHICH ARE TYPICALLY ONE OR TWO |
| DATA SHEETS THAT SHOW COMPLIANCE STANDARDS AND LISTING |
| NUMBERS, BTUH CAPACITIES AND INPUT PRESSURES. |
| A) FAILED. MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| HEATER, BBQ GRILL, FIREPLACE, AND POOL HEATER- |
| SECTIONS- G2408.1 & G2448.1. SEE NOTES UNDER ITEM 2 |
| ABOVE. |
| C) FAILED. ADJUST THE $2000.00 VALUE ON THE APPLICATION |
| TO INCLUDE THE COST OF THE NEW APPLIANCES- SECTION |
| 109.3 WPB. NO INCREASE IN VALUE OR DOCUMENTATION |
| PROVIDED. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |