2021-08-16 08:53:29PROVISOS:
 1. LIGHTING POLES ALONG ROSEMAY AVENUE SHALL MATCH THE
 DOUBLE HEAD POLES BEING INSTALLED BY THE CITY ON EAST
 SIDE OF ROSEMARY, AND THE POLES AND FIXTURES ALONG 2ND
 AND 3RD SHALL MATCH THE DMP CITY STANDARD (MANUFACTURER
 AND DESIGN). SPECS BEING PROVIDED TO APPLICANT. ALL
 POLES ARE PURCHASE AND INSTALLATION ARE THE
 RESPONSIBILITY OF THE DEVELOPER.
 2. PHOTOMETRICS ALONG ROSEMARY SHALL BE COMPLETED TO
 ENSURE COMPLIANCE WITH MIN 06 FOOTCANDLE AT ONE FOOT
 ABOVE THE SIDEWALK AT THE CURB SIDE.
 3. SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSS THE
 TWO PARKING GARAGE ENTRANCES.
 4.PLEASE DISCUSS WITH ENG. DEPARTMENT THE POSSIBILITY
 TO REGRADE ON-STREET PARKING TO DRAIN TOWARDS THE
 CENTER OR ROAD, AND RELOCATE THE GUTTER BETWEEN
 ON-STREET PARKING AND ROAD. THE GOAL IS TO ALLOW THE
 BULB OUTS AS A CONTINUOUS CURB.
 5. A MECHANICAL EQUIPMENT SCREENING PLAN SHALL BE
 SUBMITTED FOR APPROVAL BY THE ZONIND DIVISION BEFORE
 CONSTRUCTION STARTS. PARAPET WALL SHALLBE AS TALL AS
 ANY ROOF TOP MECHANICAL EQUIPMENT. EQUIPMENT SHALL BE
 GROUP TO MINIMIZE THE AREA WHERE EQUIPMENT IS LOCATED
 AND SCREEN SHALL BE PROVIDED AROUND THE EQUIPMENT AT
 THE MINIMUM CLEARANCE REQUIRED BY MANUFACTURER.
 6. PROJECT NEED TO TRANSFER 1,359 SF OF ADDITIONAL TDRS
 TO THE SITE TO ACHIEVE THE FINAL GROSS BUILDING AREA.