2021-07-22 13:42:28 | 1) SHT. C2.4 - PLACE A NOTE ON THE PLAN THAT SEPARATE |
| PERMITS ARE REQUIRED FOR THE IRRIGATION, DOMMESTIC |
| WATER AND THE FIRE LINE BACKFLOWS PER THE CITY OF WEST |
| PALM BEACH CROSS-CONNECTION CONTROL MANUAL. 3RD |
| REQUEST. |
| 2) SHT. A-5.3 - DETAIL #C - THE REAR GRAB BAR AT THE |
| WATER CLOSETS IN THE MALE AND FEMALE TOILET ROOMS |
| APPEARS TO BE 24 INCHES IN LENGTH. THE MINIMUM SIZE OF |
| THE REAR GRAB BAR SHALL BE 36 INCHES PER ANSI |
| A117.1-1986 SEC.4.16.4 & FIGURE 29. |
| 3) SHT. A-5.3 - DETAILS #A & #C - THE LAVATORY IN THE |
| MEN'S RESTROOM APPEARS TO BE ENCROACHING INTO THE CLEAR |
| FLOOR SPACE OR THE WATER CLOSET. THE LAVATORY CANNOT |
| ENCROACH INTO THIS CLEAR FFLOOR SPACE. ANSI A117.1 SEC. |
| 4.16.2ND REQUEST. |
| 4) SHT. A-5.9 - DETAIL #C - THE DOOR CANNOT SWING INTO |
| THE CLEAR FLOOR SPACE FOR THE LAVATORY UNLESS |
| SUFFICIENT MANEUVERING SPACE WITHIN THE ROOM COMPLYING |
| WITH ANSI A117.1 FIGURE #3 IS PRROVIDED. SHOW THE |
| REQUIRED MANEUVERING SPACE WITHIN THE TOILET ROOM. |
| 5) SHT. A-5.3 - IDENTIFY THE LOCATION OF THE TOILET |
| ROOMS ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1. |
| THE PLUMBING FIXTURE COUNT LISTED ON SHT. A-5.9 SHALL |
| BE CALCULATED IN ACCORDANCE WITH FBC-PLUMBING |
| SEC.403.1.1.FOR CALCULATIONS INVOLVING MULTIPLE |
| OCCUPANCIES, THE FIXTURE REQUIREMENTS SHALL BE |
| EVALUATED FOR EACH OCCUPANCY BASED ON THE OCCUPANT LOAD |
| OF EACH OCCUPANCY AND THEN SUMMED AND ROUNDED UP TO THE |
| NEXT WHOLE NUMBER.2ND REQUEST. |
| 6) SHT. A-9.1 - SUBMIT A FLOOR FIRE STOPPING |
| PENETRATION DETAIL FOR PVC PIPE LARGER THAN 2 INCHES IN |
| DIAMETER.WPB AMEND. TO FBC SEC.107.3.5.1.1.2ND REQUEST. |
| 7) SHOW THE SANITARY LINE FOR THE DOG WASH ON THE |
| UNDERGROUND SANITARY RISER FOR THE FIRST LEVEL. THE |
| LINE IS SHOWN ON THE PLAN VIEW BUT I COULD NOT FIND IT |
| ON THE RISER.WPB AMEND. TO FBC SEC. 107.2.1. 2ND |
| REQUEST. |
| 8) SHT. P-2.1A - THE MATCHLINE P-2.1D REFERENCED ON THE |
| SHEET DOES NOT SEEM TO CORRELATE WITH SHT. P-2.1D. THE |
| 1 INCH WATER LINE IS NOT SHOWN ON P-2.1D. CLARIFY. |
| 9) THE CONCRETE GREASE INTERCEPTORS SHALL COMPLY WITH |
| CITY OF WEST PALM BEACH STANDARD DRAWING GS-7. CONTACT |
| THE CITY OF WEST PALM BEACH ENGINEERING DEPT. AT |
| 561-494-1079 OR 561-835-7423 FOR A COPY OF THE DRAWING. |
| THE SUBMITTED DETAILS DO NOT APPEAR TO COMPLY WITH THE |
| CITY STANDARD DRAWING GS-7. |
| 10) SHT. P-2.0A - A SAMPLING PORT IS REQUIRED ON THE |
| OUTLET OF GI-2. THE SAMPLING PORT ON THE INLET OF GI- 1 |
| IS NOT SERVING ANY PURPOSE. |
| 11) THE RESPONSE NARRATIVE FOR PLUMBING COMMENT 31 |
| REFERS TO SHT. P-2.04. THERE IS NO SUCH SHEET. CLARIFY. |
| 12) SHT. P-2.0B - THE PLAN SHOWS THE GI-3 INTERCEPTOR |
| AND LABELS IT AS A GREASE INTERCEPTOR YET THIS ITEM IS |
| LABELED AS OI-1 ON SHT. P-6.3. SHT. P-0.1 ALSO CALLS |
| THIS OUT AS AN OIL INTERCEPTOR AND A GREASE |
| INTERCEPTOR.CLARIFY. NOTE: A GREASE INTERCEPTOR CANNOT |
| BE UTILIZED AS AN OIL INTERCEPTOR. CLARIFY AS TO WHAT |
| THIS RECEPTACLE IS TO BE USED FOR. SHT. P-2.0B ALSO |
| CALLS THIS OUT AS GI-3. CLARIFY.SUBMIT A DETAIL OF THE |
| OIL INTERCEPTOR IF THAT IS WHAT IT IS. IF IT IS A |
| GREASE INTERCEPTOR, SUBMIT DETAILS OF THE INTERCEPTOR. |
| FBC SEC. 107.3.5.1.3. |
| 13) SHT. P-2.0B - THE PLANS SHOW 1 FLOOR DRAIN IN THE |
| FIRE PUMP ROOM BUT 2 ARE SHOWN ON THE RISER ON SHT. |
| P-6.3. CLARIFY. |
| 14) SHT. P-2.0B - THE FLOOR PLAN FOR THE FIRE PUMP ROOM |
| #M-0102 NEXT TO STAIR #3 DOES NOT CORRELATE WITH SHT. |
| P- 2.0B. CLARIFY. |
| 15) SHOW THE GREASE INTERCEPTORS AND OIL INTERCEPTOR ON |
| THE SANITARY RISERS. WPB AMEND. TO FBC SEC. |
| 107.3.5.1.3. |
| 16) SHOW THE WATER LINE FOR THE TRASH CHUTE FLUSHING |
| RING ON THE WATER RISER. WPB AMEND. TO FBC SEC. |
| 107.3.5.1.3. |
| 17) THE BACKFLOW PREVENTER CALLED OUT FOR THE FLUSHING |
| RING FOR THE TRASH CHUTE ON SHT. P-28B IS NOT APPROVED |
| FOR CONTINUOUS PRESSURE AND IF A CHEMICAL DISENFECTING |
| SYSTEM WILL BE ATTCHED TO THE WATER LINE, A REDUCED |
| PRESSURE ZONE BACKFLOW PREVENTER SHALL BE INSTALLED ON |
| THE WATER LINE.FBC-PLUMBING SEC.608.1 & TABLE 608.1. |
| 18) SHT. P-6.3 - INDICATE THE TERMINATION POINT OF THE |
| VENT FOR THE TOILET ROOM IN THE MAINTENANCE ROOM # |
| A-0101B. |
| 19) SHT. P-6.4 - THERE IS A NOTE ON TH 10 INCH |
| UNDERGROUND SANITARY THAT STATES " REFER TO P-6.4 FOR |
| CONTINUATION.' THERE IS NO CONTINUATION OF THIS LINE ON |
| P-6.4. CLARIFY. |
| 20) SHT.P-6.1 - RISER 5S - THE AIR ADMITTANCE VALVES ON |
| THE KITCHEN SINKS DO NOT COMPLY WITH FBC-PLUMBING |
| SECS.918.3.1. AIR ADMITTANCE VALVES SHALL VENT ONLY |
| FIXTURES THAT CONNECT TO A HORIZONTAL BRANCH |
| DRAIN.THESE AIR ADMITTANCE VALVES ARE LOCATED ON |
| FIXTURE DRAINS. REFER TO THE DEFINITIONS OF HORIZONTAL |
| BRANCH DRAINS AND FIXTURE DRAINS IN CHAPTER 2 OF THE |
| FBC-PLUMBING.IN ADDITION, THIS RISER IS CURRENTLY |
| DESIGNED AS A WASTE STACK IN ACCORDANCE WITH |
| FBC-PLUMBING SEC.913. THE AIR ADMITTANCE VALVES ARE NOT |
| EVEN REQUIRED. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |