Plan Review Notes
Plan Review Notes For Permit 20120712
Permit Number 20120712
Review Stop P
Sequence Number 4
Notes
Date Text
2021-07-22 13:42:281) SHT. C2.4 - PLACE A NOTE ON THE PLAN THAT SEPARATE
 PERMITS ARE REQUIRED FOR THE IRRIGATION, DOMMESTIC
 WATER AND THE FIRE LINE BACKFLOWS PER THE CITY OF WEST
 PALM BEACH CROSS-CONNECTION CONTROL MANUAL. 3RD
 REQUEST.
 2) SHT. A-5.3 - DETAIL #C - THE REAR GRAB BAR AT THE
 WATER CLOSETS IN THE MALE AND FEMALE TOILET ROOMS
 APPEARS TO BE 24 INCHES IN LENGTH. THE MINIMUM SIZE OF
 THE REAR GRAB BAR SHALL BE 36 INCHES PER ANSI
 A117.1-1986 SEC.4.16.4 & FIGURE 29.
 3) SHT. A-5.3 - DETAILS #A & #C - THE LAVATORY IN THE
 MEN'S RESTROOM APPEARS TO BE ENCROACHING INTO THE CLEAR
 FLOOR SPACE OR THE WATER CLOSET. THE LAVATORY CANNOT
 ENCROACH INTO THIS CLEAR FFLOOR SPACE. ANSI A117.1 SEC.
 4.16.2ND REQUEST.
 4) SHT. A-5.9 - DETAIL #C - THE DOOR CANNOT SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY UNLESS
 SUFFICIENT MANEUVERING SPACE WITHIN THE ROOM COMPLYING
 WITH ANSI A117.1 FIGURE #3 IS PRROVIDED. SHOW THE
 REQUIRED MANEUVERING SPACE WITHIN THE TOILET ROOM.
 5) SHT. A-5.3 - IDENTIFY THE LOCATION OF THE TOILET
 ROOMS ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 THE PLUMBING FIXTURE COUNT LISTED ON SHT. A-5.9 SHALL
 BE CALCULATED IN ACCORDANCE WITH FBC-PLUMBING
 SEC.403.1.1.FOR CALCULATIONS INVOLVING MULTIPLE
 OCCUPANCIES, THE FIXTURE REQUIREMENTS SHALL BE
 EVALUATED FOR EACH OCCUPANCY BASED ON THE OCCUPANT LOAD
 OF EACH OCCUPANCY AND THEN SUMMED AND ROUNDED UP TO THE
 NEXT WHOLE NUMBER.2ND REQUEST.
 6) SHT. A-9.1 - SUBMIT A FLOOR FIRE STOPPING
 PENETRATION DETAIL FOR PVC PIPE LARGER THAN 2 INCHES IN
 DIAMETER.WPB AMEND. TO FBC SEC.107.3.5.1.1.2ND REQUEST.
 7) SHOW THE SANITARY LINE FOR THE DOG WASH ON THE
 UNDERGROUND SANITARY RISER FOR THE FIRST LEVEL. THE
 LINE IS SHOWN ON THE PLAN VIEW BUT I COULD NOT FIND IT
 ON THE RISER.WPB AMEND. TO FBC SEC. 107.2.1. 2ND
 REQUEST.
 8) SHT. P-2.1A - THE MATCHLINE P-2.1D REFERENCED ON THE
 SHEET DOES NOT SEEM TO CORRELATE WITH SHT. P-2.1D. THE
 1 INCH WATER LINE IS NOT SHOWN ON P-2.1D. CLARIFY.
 9) THE CONCRETE GREASE INTERCEPTORS SHALL COMPLY WITH
 CITY OF WEST PALM BEACH STANDARD DRAWING GS-7. CONTACT
 THE CITY OF WEST PALM BEACH ENGINEERING DEPT. AT
 561-494-1079 OR 561-835-7423 FOR A COPY OF THE DRAWING.
 THE SUBMITTED DETAILS DO NOT APPEAR TO COMPLY WITH THE
 CITY STANDARD DRAWING GS-7.
 10) SHT. P-2.0A - A SAMPLING PORT IS REQUIRED ON THE
 OUTLET OF GI-2. THE SAMPLING PORT ON THE INLET OF GI- 1
 IS NOT SERVING ANY PURPOSE.
 11) THE RESPONSE NARRATIVE FOR PLUMBING COMMENT 31
 REFERS TO SHT. P-2.04. THERE IS NO SUCH SHEET. CLARIFY.
 12) SHT. P-2.0B - THE PLAN SHOWS THE GI-3 INTERCEPTOR
 AND LABELS IT AS A GREASE INTERCEPTOR YET THIS ITEM IS
 LABELED AS OI-1 ON SHT. P-6.3. SHT. P-0.1 ALSO CALLS
 THIS OUT AS AN OIL INTERCEPTOR AND A GREASE
 INTERCEPTOR.CLARIFY. NOTE: A GREASE INTERCEPTOR CANNOT
 BE UTILIZED AS AN OIL INTERCEPTOR. CLARIFY AS TO WHAT
 THIS RECEPTACLE IS TO BE USED FOR. SHT. P-2.0B ALSO
 CALLS THIS OUT AS GI-3. CLARIFY.SUBMIT A DETAIL OF THE
 OIL INTERCEPTOR IF THAT IS WHAT IT IS. IF IT IS A
 GREASE INTERCEPTOR, SUBMIT DETAILS OF THE INTERCEPTOR.
 FBC SEC. 107.3.5.1.3.
 13) SHT. P-2.0B - THE PLANS SHOW 1 FLOOR DRAIN IN THE
 FIRE PUMP ROOM BUT 2 ARE SHOWN ON THE RISER ON SHT.
 P-6.3. CLARIFY.
 14) SHT. P-2.0B - THE FLOOR PLAN FOR THE FIRE PUMP ROOM
 #M-0102 NEXT TO STAIR #3 DOES NOT CORRELATE WITH SHT.
 P- 2.0B. CLARIFY.
 15) SHOW THE GREASE INTERCEPTORS AND OIL INTERCEPTOR ON
 THE SANITARY RISERS. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 16) SHOW THE WATER LINE FOR THE TRASH CHUTE FLUSHING
 RING ON THE WATER RISER. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 17) THE BACKFLOW PREVENTER CALLED OUT FOR THE FLUSHING
 RING FOR THE TRASH CHUTE ON SHT. P-28B IS NOT APPROVED
 FOR CONTINUOUS PRESSURE AND IF A CHEMICAL DISENFECTING
 SYSTEM WILL BE ATTCHED TO THE WATER LINE, A REDUCED
 PRESSURE ZONE BACKFLOW PREVENTER SHALL BE INSTALLED ON
 THE WATER LINE.FBC-PLUMBING SEC.608.1 & TABLE 608.1.
 18) SHT. P-6.3 - INDICATE THE TERMINATION POINT OF THE
 VENT FOR THE TOILET ROOM IN THE MAINTENANCE ROOM #
 A-0101B.
 19) SHT. P-6.4 - THERE IS A NOTE ON TH 10 INCH
 UNDERGROUND SANITARY THAT STATES " REFER TO P-6.4 FOR
 CONTINUATION.' THERE IS NO CONTINUATION OF THIS LINE ON
 P-6.4. CLARIFY.
 20) SHT.P-6.1 - RISER 5S - THE AIR ADMITTANCE VALVES ON
 THE KITCHEN SINKS DO NOT COMPLY WITH FBC-PLUMBING
 SECS.918.3.1. AIR ADMITTANCE VALVES SHALL VENT ONLY
 FIXTURES THAT CONNECT TO A HORIZONTAL BRANCH
 DRAIN.THESE AIR ADMITTANCE VALVES ARE LOCATED ON
 FIXTURE DRAINS. REFER TO THE DEFINITIONS OF HORIZONTAL
 BRANCH DRAINS AND FIXTURE DRAINS IN CHAPTER 2 OF THE
 FBC-PLUMBING.IN ADDITION, THIS RISER IS CURRENTLY
 DESIGNED AS A WASTE STACK IN ACCORDANCE WITH
 FBC-PLUMBING SEC.913. THE AIR ADMITTANCE VALVES ARE NOT
 EVEN REQUIRED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  