Plan Review Notes
Plan Review Notes For Permit 20120712
Permit Number 20120712
Review Stop P
Sequence Number 2
Notes
Date Text
2021-05-13 13:46:461) SHT. C2.4 - PLACE A NOTE ON THE PLAN THAT SEPARATE
 PERMITS ARE REQUIRED FOR THE IRRIGATION, DOMESTIC WATER
 AND THE THE FIRE LINE BACKFLOWS PER THE CITY OF WEST
 PALM BEACH CROSS-CONNECTION CONTROL MANUAL. 2ND
 REQUEST.
 2) THE PLUMBING FIXTURE COUNT LISTED ON SHT. A-5.9 IS
 VAGUE. WHAT OCCUPANCY ARE YOU BASING THESE FIXTURE
 REQUIREMENTS ON? THE FIXTURE REQUIREMENTS SHALL BE
 EVALUATED FOR EACH SEPARATE OCCUPANCY BASED ON THE
 OCCUPANT LOAD AND THEN SUMMED AND ROUNDED UP TO THE
 NEXT WHOLE NUMBER. FBC-PLUMBING SEC. 403.1.1. THERE ARE
 NO DRINKING FOUNTAINS LISTED IN THE FIXTURE
 CALCULATIONS AND THEY WILL BE REQUIRED BASED ON THE
 OCCUPANCIES.
 3) SHT. LS-0.0 - SUBMIT A FIRE STOPPING PENETRATION
 DETAIL FOR PVC PIPE LARGER THAN 2 INCHES IN DIAMETER.
 WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A-5.3 - DETAIL "A" - POOL PAVILION RESTROOMS -
 THE HANDICAP ACCESSIBLE WATER CLOSETS ARE STILL SHOWN
 AS BEING 1 FOOT 8 INCHES FROM THE ADJACENT WALL TO THE
 CENTERLINE OF THE WATER CLOSETS.COMPLY WITH ANSI
 A117.1-1986 SEC.4.16. 2ND REQUEST.
 5) SHTS. A-2.1, A-5.2, & A-5.9 - THE DOOR IN ONE OF THE
 WOMEN'S ACCESSIBLE TOILET ROOMS IN RESTROOM #A-0126
 CANNOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 THE WATER CLOSET. COMPLY WITH ANSI A117.1 SEC.4.22.2.
 6) SUBMIT A WATER AND SANITARY RISER FOR THE DOG WASH
 BASIN. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. A-5.3 - THE LAVATORY APPEARS TO BE ENCROACHING
 INTO THE CLEAR FLOOR SPACE FOR THE WATER CLOSET.
 CLEARLY DEFINE THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET. COMPLY WITH ANSI A117.1-1986 SEC.4.16.
 8) SHT A-5.3 - FIXTURE MOUNTING HEIGHTS - THERE ARE
 THREE DIFFERENT DIMENSIONS SHOWN TO THE BOTTOM OF THE
 LAVATORY. CLARIFY.
 9) SHT. A-5.5 - CLARIFY THE WALL SUBSTRATE AND FINISH
 AROUND THE MOP SINK. THE WALL FINISH SHALL COMPLY WITH
 FBC-BUILDING SEC. 1210.2.2. DRYWALL WITH EPOXY PAINT
 DOES NOT COMPLY.THERE IS NO NOTE ON SHT. A-5.7 AS
 STATED IN THE RESPONSE NARRATIVE. CLARIFY. 2ND
 REQQUEST.
 10) SHT. A-5.7 - THERE IS A NOTE ON THE LOWER RIGHT
 CORNER OF THE PLANS THAT REFERS TO I.D. CONSTRUCTION
 DOCUMENTS FOR ALL FINISHES. THERE ARE NO SUCH PLANS IN
 THIS SUBMITTAL. CLARIFY. 2ND REQUEST. THIS NOTE APPEARS
 IN MULTIPLE PLACES ON PLUMBING FIXTURE ELEVATION
 DETAILS.
 11) SHT. A-5.7 - DETAILS #1 & #2 - THERE IS NO GRAB BAR
 SHOWN ON THE SIDE WALL ADJACENT TO THE WATER CLOSET.
 COMPLY WITH ANSI A117.1-1986 SEC.4.16.4.2ND REQUEST.
 12) SHT. A-5.9 - DETAIL #3 - THE MAXIMUM HEIGHT OF THE
 URINAL SHALL BE 17 INCHES PER ANSI A 117.1-1986 SEC.
 4.18.2.
 13) SHT. A-5.9 - DETAIL "B" - TOILET ROOMS #A-0125 &
 A-0126 - THE LENGTH OF THE CLEAR FLOOR SPACE FOR THE
 WATER CLOSETS SHALL BE A MINIMUM OF 56 INCHES AND THE
 PLAN SHOWS 54 INCHES. REVISE THE HATCHED AREAS SHOWING
 THE CLEAR FLOOR SPACES. ANSI A117.1 SEC.4.16.2. CHECK
 THE LENGTHS OF THE CLEAR FLOOR SPACES FOR THE WATER
 CLOSETS IN ALL COMMON AREA TOILET AREAS FOR COMPLIANCE.
 14) SHT. A-5.10 - FIXTURE MOUNTING HEIGHTS - THERE IS
 NOTE UNDER THIS HEADING THAT STATES " REFER TO SHT.
 A-10.1 FOR ADDITIONAL INFORMATION." SHT. A-10.1 IS
 ENLARGED DWELLING UNIT FLOOR PLANS. CLARIFY.
 15) SHT. A-10.1 - SHOW THE DEPTH OF THE LAVATORIES
 ADJACENT TO THE WATER CLOSETS IN THE ADAPTABLE
 BATHROOMS. THE LAVATORIES SHALL HAVE A MAXIMUM DEPTH OF
 24 INCHES PER THE FAIR HOUSING ACT DESIGN MANUAL PAGE
 7.43. 2ND REQUEST.
 16) SHT. A- 10.2 - SHOW THE LENGTH OF THE SHOWER WALL
 ADJACENT TO THE WATER CLOSET IN THE B1 UNIT, TYPE "A"
 BATH. THE WALL LENGTH SHALL NOT EXCEED 24 INCHES. FHA
 DESIGN MANUAL PAGE 7.44.
 17) SHT. A-10.2 - UNIT B3 - THE DOOR TO THE LAUNDRY
 ROOM SHALL PROVIDE A 32 INCH CLEAR OPENING AS IT IS
 INTENDED FOR USER PASSAGE. FHA DESIGN MANUAL PAGE 7.19.
 2ND REQUEST.
 18) SINCE THE TOWNHOUSES DO NOT HAVE TO COMPLY WITH THE
 REQUIREMENTS OF THE FAIR HOUSING ACT, WHY ARE ALL THE
 CLEAR FLOOR SPACES SHOWN ON THESE PLANS? ACCESSIBILITY
 REQUIREMENTS FOR TOWNHOUSES ARE IN THE
 FBC-ACCESSIBILITY SEC. 233.3.6 AND FL. STATUTE 553.504
 (2).
 19) SHT. A-10.4 - SUBMIT A GRAB BAR REINFORCEMENT
 DETAIL FOR THE ADAPTABLE SHOWERS. COMPLY WITH FHA
 DESIGN MANUAL PAGE 7.56. 2ND REQUEST.
 20) SUBMIT A WATER RISER DIAGRAM FOR THE MAIN WATER
 PIPING FROM THE STREET INTO THE BUILDING AND INCLUDE
 THE WATER SYSTEM MAINS AND BRANCH LINES ON THE SYSTEM.
 INCLUDE ALL BRANCHES TO HOSE BIBBS, FUTURE CONNECTIONS
 AND THE INLET AND OUTLET PIPING FOR THE BOOSTER PUMP.
 21) SHT. P-2.1A & P-2.1B - KEYNOTE #4 CALLS OUT "4 INCH
 STORM PIPE DOWN" BUT THE KEYNOTE ON THE PLAN POINTS TO
 A WATER LINE. CLARIFY.
 22) SHT. P-2.1A - PROVIDE A MATCH LINE AT THE TOP OF
 THE SHEET TO SHOW THE CONTINUATION OF THE 1 INCH WATER
 LINE.WPB AMEND. TO FBC SEC. 107.2.1.
 23) SHT. P-2.1B - FOOTNOTES #2 & #3 REFER TO SANITARY
 PIPING BUT THE KEYNOTES ARE ON THE WATER SYSTEM.
 CLARIFY.
 24) THE WATER SUPPLY VALVES FOR THE FOR THE STACKED
 WASHER/DRYER UNITS SHALL BE PROVIDED WITH ACCES PER
 FBC-PLUMBING SEC. 606.3. IF THE VALVES ARE LOCATED
 BEHIND THE WASHER/DRYER UNITS THEY WILL NOT BE
 ACCESSIBLE UNLESS THERE IS A REMOVABLE ACESS PANEL ON
 THE UNIT. IF THE VALVES ARE LOCATED ON THE WALL
 ADJACENT TO THE UNITS, THEY MAY ALSO NOT BE ACCESSIBLE
 BECAUSE OF THE SIZE OF THE UNITS. CLEARLY SHOW THE
 LOCATION OF THE VALVES AND THE REQUIRED ACCESS. 2ND
 REQUEST.
 25) SHT. P-2.0A - RISER 1S IS NOT TAGGED ON THE RISER
 ON SHT. P-6.3. (SEE UNIT A1).
 26) SHT. P-2.0A SHOWS A 3 INCH SANITARY LINE TO THE
 SINK AT GRILLE AREA BUT THIS LINE IS NOT SHOWN ON THE
 RISER DIAGRAM ON SHT. P-6.3. CLARIFY.
 27) SHT.P-2.0A - RISER 5S IN UNIT A3 BY THE MATCHLINE
 IS LABELED AS RISER 6S ON SHT. P6.3. CLARIFY.
 28) SHT. P-2.0B - UNIT B1 MOD- THE SANITARY RISER IN
 THE BATHROOM IS LABELED AS 6S BUT LABELED AS 5S ON SHT.
 P-6.3. CLARIFY.
 29) SHT. P-2.0B - FIXTURE OI-1- IS THIS UNIT SUPPOSED
 TO BE AN "OIL INTERCEPTOR" OR A "GREASE INTERCEPTOR".
 IT IS CALLED OUT AS AN OIL INTERCEPTOR ON SHT. P-0.1
 BUT A SCHIER GB-50 IS A GREASE INTERCEPTOR. CLARIFY.
 OIL INTERCEPTORS SHALL COMPLY WITH FBC-PLUMBING
 SEC.1003.4.2.
 30) SHT. P-2.0B - KEYNOTE #4 CALLS OUT A 2 INCH DRY
 VENT BUT THE PLAN SHOWS A 3 INCH SANITARY LINE WITH 35
 DFU'S. SHT. P-6.03 ALSO SHOWS A 3 INCH SANITARY
 LINE.CLARIFY.
 31) SUBMIT DETAILS OF THE PRECAST GREASE
 INTERCEPTORS.THE CONCRETE GREASE INTERCEPTORS SHALL
 COMPLY WITH CITY STANDARD DRAWING GS-7. CONTACT THE
 CITY OF WPB ENGINEERING DEPT. AT 561-835-7423 FOR A
 COPY OF THE DRAWING. WPB AMEND. TO FBC SEC. 107.2.1.A
 SAMPLING PORT IS REQUIRED ON THE OUTLET OF EACH GREASE
 INTERCEPTOR AND THE OIL INTERCEPTOR.
 32) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTORS AND OIL INTERCEPTOR PER FBC-PLUMBING
 SEC.1003.2.
 33 SHT. P-4.1- UNIT A3 - KEYNOTE #9 CALLS OUT AN AIR
 ADMITTANCE VALVE BUT THE AAV IS NOT SHOWN ON THE RISER
 1S. THE RESPONSE NARRATIVE FOR PREVIOUS COMMENT #71
 REFERS TO THE REQUIRED RELIEF VENT BUT THERE IS NO
 RELIEF VENT ON RISER 1S.CLARIFY. COMPLY WITH
 FBC-PLUMBING SEC.918.
 34) SHT. P-4.2 - UNIT B1-MOD SHOWS THE AIR ADMITTANCE
 VALVE LOCATED IN THE WALL NEXT TO THE WATER CLOSET.
 CLARIFY.
 35) SHT. P-6.0 - CLARIFY THE PIPE SIZES ON THE WATER
 RISER.THE PIPE SIZES ARE EXTREMELY DIFFICULT TO READ.
 36) P-6.0 - THE URINAL IN THE MEN'S RESTROOM CANNOT
 DISCHARGE INTO THE HORIZONTAL WET VENT PER FBC-PLUMBING
 SEC.912.1.THE URINAL SHALL CONNECT TO THE HORIZONTAL
 DRAIN DOWNSTREAM OF THE FLOOR DRAIN.
 37) INDICATE ON THE TRASH CHUTE DETAILS (SHT. A-8.5) IF
 THE TRASH CHUTE WILL BE EQUIPPED WITH A FLUSHING RING
 AT THE TOP OF THE CHUTE. IF SO, SUBMIT A DETAIL FOR THE
 WATER CONNECTION. IF A CHEMICAL SOLUTION WILL BE
 CONNECTED TO THE SYSTEM, A BACKFLOW DEVICE SHALL BE
 REQUIRED ON THE WATER CONNECTION.
 38) SHT. P-6.2 - THE TOP OF RISER AND THE VENT APPEAR
 TO BE CUT OFF. CLARIFY.
 39) SHT. P-6.3 - SECTIONS OF THE SANITARY RISER ARE
 MISSING ON THE LEFT SIDE OF THE DRAWING.
 40) SHT.P-8.1 - SUB-METER SPECIFICATIONS - THE ENTIRE
 METER HOUSING AND LID SHALL BE CONSTRUCTED OF BRASS IN
 ORDER TO BE LOCATED INSIDE THE RETURN AIR CLOSETS. THE
 SUBMETERS SHALL COMPLY WITH THE FBC-MECH. SECS. 602.2.1
 & 602.2.1.7.
 41) A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTORS AND THE OIL INTERCEPTOR.
 42) A SAMPLING PORT IS REQUIRED ON THE OUTLET OF EACH
 GREASE INTERCEPTOR AND THE OIL INTERCEPTOR.
 43) SHTS. P-2.0B & P-2.0C - THE KEYNOTES LISTED THAT
 REFER TO THE PLUMBING SYSTEM ARE NOT SHOWN ON THE
 PLANS. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW