Plan Review Notes
Plan Review Notes For Permit 20120712
Permit Number 20120712
Review Stop G
Sequence Number 2
Notes
Date Text
2021-07-21 14:53:311) SHTS. P-2.0A, P-2.0B & P-2.0C - THE GAS LINE APPEARS
 LIKE IT MAY BE RUNNING UNDER THE BUILDING IN CERTAIN
 AREAS. PE PIPE CAN ONLY BE INSTALLED OUTSIDE,
 UNDERGROUND. CLARIFY THIS ON THE AFOREMENTIONED
 SHEETS.FBC-FUEL GAS SEC.404.17.1. A YELLOW INSULATED
 COPPER TRACER WIRE OR OTHER APPROVED CONDUCTOR OR
 PRODUCT SHALL BE INSTALLED ADJACENT TO UNDERGROUND
 NONMETALLIC PIPING. FBC-FUEL GAS SECTION 404.17.3.
 2) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER
 FBC-FUEL GAS SEC. 301.3. THE SUBMITTED DOCUMENTS FOR
 THE TAVOOLA 4 FIRE TABLE DOES NOT SHOW IT IS LISTED OR
 LABELED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  