Plan Review Notes For Permit 20120712 |
Permit Number |
20120712 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-05-11 10:01:20 | NEW 8 STORY APT BUILDING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE PROVIDE THE FOLLOWING ACOUSTICAL TEST REPORTS | | . FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | 2) TOWNHOME BUILDING, PAVILION, POOL AND FENCING SHALL | | BE A SEPARATE PERMIT - PLEASE ACKNOWLEDGE THIS. | | | | ADDED REVIEW COMMENTS FOR 2 REVIEW = | | 3) PLEASE SHOW THE REQUIRED STAIR HANDRAILS AT THE | | GROUND FLOOR UNITS WITH EGRESS PER FBC 1011.11 - PLEASE | | SHOW STEP RISERS AND TREADS TO COMPLY WITH FBC | | 1011.5.2. | | 4) ACCESSIBLE PARKING SPACES SHALL BE A MINIMUM WIDTH | | OF 12' PER FBC A502.2 - DRAWING (A-2.5B/A-2.2B/A-2.3B) | | SHOW LESS THAN 12' WIDE. | | 5) PLEASE SHOW THE RAMP WIDTH ADDED TO THE (CO WORK) | | AREA IN THE COMMON FIRST FLOOR AREA.(A-5.9) FBC 1005.2 | | 6) ROOFING SYSTEMS, WINDOW, DOOR AND LOUVER PRODUCT | | APPROVALS AND ITEMS AS LISTED ON DRAWING LS-0.0 ARE TO | | BE DEFERRED. | | | | | | | | |
|