Plan Review Notes
Plan Review Notes For Permit 20120712
Permit Number 20120712
Review Stop P-GREASE
Sequence Number 1
Notes
Date Text
2021-07-22 15:00:211) THE CONCRETE GREASE INTERCEPTORS SHALL COMPLY WITH
 CITY OF WEST PALM BEACH STANDARD DRAWING GS-7. CONTACT
 THE CITY OF WEST PALM BEACH ENGINEERING DEPT. AT
 561-494-1079 OR 561-835-7423 FOR A COPY OF THE DRAWING.
 THE SUBMITTED DETAILS DO NOT APPEAR TO COMPLY WITH THE
 CITY STANDARD DRAWING GS-7.
 2) SHT. P-2.0A - A SAMPLING PORT IS REQUIRED ON THE
 OUTLET OF GI-2. THE SAMPLING PORT ON THE INLET OF GI- 1
 IS NOT SERVING ANY PURPOSE.
 3) SHT. P-2.0B - THE PLAN SHOWS THE GI-3 INTERCEPTOR
 AND LABELS IT AS A GREASE INTERCEPTOR YET THIS ITEM IS
 LABELED AS OI-1 ON SHT. P-6.3. SHT. P-0.1 ALSO CALLS
 THIS OUT AS AN OIL INTERCEPTOR AND A GREASE
 INTERCEPTOR.CLARIFY. NOTE: A GREASE INTERCEPTOR CANNOT
 BE UTILIZED AS AN OIL INTERCEPTOR. CLARIFY AS TO WHAT
 THIS RECEPTACLE IS TO BE USED FOR. SHT. P-2.0B ALSO
 CALLS THIS OUT AS GI-3. CLARIFY.SUBMIT A DETAIL OF THE
 OIL INTERCEPTOR IF THAT IS WHAT IT IS. IF IT IS A
 GREASE INTERCEPTOR, SUBMIT DETAILS OF THE INTERCEPTOR.
 FBC SEC. 107.3.5.1.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  