Plan Review Notes
Plan Review Notes For Permit 20120712
Permit Number 20120712
Review Stop P
Sequence Number 1
Notes
Date Text
2021-03-15 11:04:331) SHT. C2.4 - PLACE A NOTE ON THE PLAN THAT SEPARATE
 PERMITS ARE REQUIRED FOR THE IRRIGATION, DOMESTIC
 WATER, AND FIRE LINE BACKFLOWS PER THE CITY OF WEST
 PALM BEACH CROSS-CONNECTION CONTROL MANUAL.
 2) SUBMIT A PLUMBING FIXTURE COUNT SCHEDULE FOR THE
 MINIMUM NUMBER OF REQUIRED SANITARY FACILITIES REQUIRED
 FOR EACH OCCUPANCY TYPE AT THE POOL, AREA FITNESS
 CENTER, PAVILION/GAMING/WET BAR, MULTIPURPOSE
 LAWN/AMPHITHEATER,FIRE PIT AREA, AND ALL OTHER COMMON
 AREAS LOCATED ON LEVEL ONE. COMPLY WITH FBC-PLUMBING
 TABLE 403.1.
 3) SHT. LS-0.0 - NOTE #2 (A) REFERS TO SHT P-6.1 FOR
 LISTED UL ASSEMBLIES FOR THROUGH PENETRATION FIRE STOP
 SYSTEMS. THERE IS NO FIRE STOP INFORMATION ON SHT.
 P-6.1. CLARIFY.
 4) SHTS. A-2.1, A-5.2, & A-5.9 - THE DOOR IN THE MEN'S
 TOILET ROOM #A-0125 CANNOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR THE LAVATORY. COMPLY WITH
 FBC-ACCESS. SEC.603.2.3. SEE EXCEPTION #2. SHOW THE 30
 INCH MINIMUM BY 48 INCH MINIMUM CLEAR FLOOR SPACE
 LOCATED BEYOND THE THE ARC OF THE DOOR ON THE PLANS.
 5) SHTS. A-2.1, A-5.2, & A-5.9 - THE DOOR IN ONE OF THE
 WOMEN'S TOILET ROOMS #A-0126 CANNOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR THE WATER CLOSET. COMPLY
 WITH FBC-ACCESS. SEC.603.2.3. SEE EXCEPTION #2. SHOW
 THE 30 INCH MINIMUM BY 48 INCH MINIMUM CLEAR FLOOR
 SPACE LOCATED BEYOND THE THE ARC OF THE DOOR ON THE
 PLANS.
 6) SHT. A-5.2 & A=5.10 - THE SINK IN THE HOSPITALITY
 AREA (A-0109) AND LOUNGE AREA ( A-0121) SHALL COMPLY
 WITH ANSI A117.1 - 1986.
 7) THE SINK
 8) SHT. SP-1 SHOWS A DOG PARK.INDICATE ON THE PLAN IF
 THERE ARE ANY PLUMBING FIXTURES LOCATED IN THIS AREA
 AND IF SO, SUPPLY A WATER AND SANITARY RISER. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3. THERE IS ALSO A SQUARE
 MARKED "TX." CLARIFY WAHT THIS ITEM IS AND IT'S USE.
 THE PLAN STATES "SEE CIVIL" BUT THERE IS NO INFORMATION
 ON THE CIVIL DRAWINGS. CLARIFY.
 9) SHTS. A-4.1 & A-4.2 - SHOW THE DEPTH OF THE
 LAVATORIES ADJACENT TO THE WATER CLOSETS IN THE
 ADAPTABLE BATHROOMS. THE LAVATORIES SHALL HAVE A
 MAXIMUM DEPTH OF 24 INCHES PER THE FAIR HOUSING ACT
 DESIGN MANUAL PAGE 7.43.
 10) SHT. A-4 - UNITS B1 & B1-MOD - SHOW THE LENGTH OF
 THE TUB AND SHOWER WALL NEXT TO THE WATER CLOSET. THE
 WALL LENGTH SHALL NOT EXCEED 24 INCHES PER THE FHA
 DESIGN MANUAL PAGE 7.44.
 11) SHT. A-5.3 - MEN'S RESTROOM A-0130B - THE URINAL
 CANNOT BE LOCATED INSIDE THE CLEAR FLOOR SPACE FOR THE
 URINAL. ANSI A117.1 - 1986 SEC.4.16, FIGURE 28.
 12) SHT. A-5.3 - FIXTURE MOUNTING HEIGHTS SHOWS A GRAB
 BAR IN THE VERTICAL POSITION. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION. THERE IS NO
 EXCEPTION IN THE ANSI STANDARD FOR VERTICAL GRAB BARS.
 ANSI A117.1-1986 SEC.4.16.4.
 13) SHT. A-5.3 - POOL RESTROOM ELEVATION DRAWINGS - THE
 HEIGHT OF THE GRAB BARS IS MEASURED TO THE BOTTOM OF
 THE GRAB BAR. SEC. 4.16.4 & FIGURE 29 (A) (B) OF ANSI
 A117.1-1986 REQUIRE THE GRAB BARS TO BE MEASURED TO THE
 CENTERLINE OF THE GRAB BAR.CLARIFY.
 14) SHT. A-5.3 - POOL RESTROOM ELEVATION DRAWINGS -
 SHOW THE LOCATION OF THE GRAB BARS FROM THE SIDE WALL
 AND REAR WALL OF THE WATER CLOSET ON THE DRAWINGS AND
 SHOW THE LENGTH OF THE GRAB BARS PER ANSI A117.1 SEC.
 4.16.4.
 15) SHT. A-5.3 - THE PLAN SHOWS THE CENTERLINE OF THE
 WATER CLOSET 1 FOOT 8 INCHES FROM THE SIDE WALL TO THE
 CENTERLINE OF THE WATER CLOSET. THE WATER CLOSET SHALL
 BE LOCATED 18 INCHES TO THE CENTERLINE FROM THE SIDE
 WALL. ANSI A117.1 SEC.4.16.2. SHOW THE DIMENSION FROM
 THE FINISHED SURFACE OF THE WALL.
 16) SHT. A-5.3 - FIXTURE MOUNTING HEIGHTS - THE GRAB
 BARS ARE SHOWN MEASURED TO THE CENTERLINE OF THE GRAB
 BARS BUT THE NOTE STATES "TOP OF GRIPPING SURFACE." THE
 GRAB BARS SHALL BE MEESURED TO THE CENTERLINE PER ANSI
 A117.1 SEC.4.16.4. REMOVE THE NOTE.
 17) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE CLEAR
 FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES IN
 THE COMMON AREA TOILET ROOMS AND TOILET STALLS. COMPLY
 WITH ANSI A117.1. SECS. 4.15 THOUGH 4.21.
 18) SHT. A-5.5 - CLARIFY THE WALL SUBSTRATE AND FINISH
 AROUND THE MOP SINK. THE FINISH SCHEDULE NOTES "1 COAT
 PRIMER AND 2 COATS PAINT". THE WALL FFINISH SHALL
 COMPLY WITH FBC-BUILDING SEC. 1210.2.2.DRYWALL AND
 EPOXY PAINT DOES NOT COMPLY.NOTE #16 REFERS TO INTERIOR
 DESIGNER'S DRAWINGS BUT THERE ARE NO SUCH DRAWINGS IN
 THIS SUBMITTAL. CLARIFY.
 19) SHT. A-5.7. - MAINTENANCE RESTROOM DETAILS #1 & #2
 APPEAR TO SHOW THE GRAB BARS MEASURED TO THE BOTTOM OF
 THE GRAB BAR. GRAB BARS SHALL BE MEASURED TO THE
 CENTERLINE OF THE GRAB BAR PER ANSI A117.1 SEC.4.16.4.
 20) SHT. A-5.7 - DETAILS #1 & #2 - THERE IS NO GRAB BAR
 SHOWN ON THE SIDE ADJACENT TO THE WATER CLOSET.
 CLARIFY. COMPLY WITH ANSI A117.1 SEC.4.16.4.
 21) SHT. A-5.7 - SHOW THE WIDTH OF THE TOILET ROOM.
 THERE IS NO DIMENSION SHOWN ON THE PLAN. WPB AMEND. TO
 FBC SEC. 107.2.1.
 22) SHT. A-5.9 - AMENITY RESTROOMS - DETAILS #1,2,6,7,8
 & 9 APPEAR TO SHOW THE GRAB BARS MEASURED TO THE BOTTOM
 OF THE GRAB BAR. GRAB BARS SHALL BE MEASURED TO THE
 CENTERLINE PER ANSI A117.1 SEC.4.16.4. RFERENCE IS ALSO
 MADE TO I.D. DRAWINGS BUT THERE ARE NO I.D. DRAWINGS IN
 THIS SUBMITTAL.
 23) SHT. A-5.9 - AMENITY RESTROOMS - THERE ARE
 ADDITIONAL ELEVATION DETAILS SHOWING THE GRAB BARS
 MEASURED TO THE TOP OF THE GRIPPING SURFACE WITH NOTES
 STATING SUCH. GRAB BARS SHALL BE MEASURED TO THE
 CENTERLINE PER ANSI A117.1 SEC.4.16.4.REMOVE THE NOTE
 REFERRING TO THE TOP OF THE GRIPPING SURFACE.
 24) SHT. A-5.9 - SHOW THE LOCATION OF THE GRAB BARS
 FROM THE SIDE WALL AND REAR WALL OF THE WATER CLOSET ON
 THE DRAWINGS AND SHOW THE LENGTH OF THE GRAB BARS PER
 ANSI A117.1 SEC. 4.16.4.25)
 25) SHT. A-5.9 - A VERTICAL GRAB BAR IS SHOWN ON THE
 SIDE WALL NEXT TO THE WATER CLOSET IN THE ELEVATION
 DETAILS ON THE BOTTOM RIGHT SIDE OF THE PLAN.GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION. THERE IS
 NO EXCEPTION IN THE ANSI STANDARD FOR VERTICAL GRAB
 BARS. ANSI A117.1-1986 SEC.4.16.4
 26) SHT. A-5.9 - HANDICAP MOUNTING HEIGHT DETAILS - THE
 REAR GRAB BAR AT THE WATER CLOSET SHOWS A DIMENSION OF
 3 FEET YET IT ALSO SHOWS 24 INCHES TO ONE SIDE OF THE
 WATER CLOSET AND 18 INCHES ON THE OTHER SIDE OF THE
 WATER CLOSET WHICH EQUALS 42 INCHES OVERALL. CLARIFY.
 27) SHT. A-5.10 - SHOW THE CLEAR FLOOR SPACE DIMENSIONS
 ON THE FLOOR PLAN. COMPLY WITH ANSI A117.1 SECS.
 4.16.2, 4.18 AND 4.19. SHOW THE CLEAR FLOOR SPACE FOR
 THE URINAL ON THE PLANS.
 28) SHT. A-5.10 - THE RESTROOM ELEVATION DETAILS APPEAR
 TO SHOW THE GRAB BAR MEASUREMENT MEASURED TO THE BOTTOM
 OF THE GRAB BAR. GRAB BARS SHALL BE MEASURED TO THE
 CENTERLINE OF THE GRAB BAR PER ANSI A117.1 SEC. 4.16.4.
 29) SHT. A-5.10 - THE URINAL SHALL BE LOCATED WITH THE
 RIM AT A MAXIMUM HEIGHT OF 17 INCHES ABOVE THE FLOOR
 PER ANSI A117.1 SEC.4.18.2.
 30) SHT. A-5.10 - DELETE THE VERTICAL GRAB BAR FROM THE
 ELEVATION DETAILS. GRAB BARS SHALL BE INSTALLED IN THE
 HORIZONTAL POSITION. THERE IS NO EXCEPTION IN THE ANSI
 STANDARD FOR VERTICAL GRAB BARS. ANSI A117.1-1986
 SEC.4.16.4.
 31) SHT. A-5.10 - HANDICAP MOUNTING HEIGHT DETAILS (AT
 TOP OF DRAWING)- THE REAR GRAB BAR AT THE WATER CLOSET
 SHOWS A DIMENSION OF 3 FEET YET IT ALSO SHOWS 24 INCHES
 TO ONE SIDE OF THE WATER CLOSET AND 18 INCHES ON THE
 OTHER SIDE OF THE WATER CLOSET WHICH EQUALS 42 INCHES
 OVERALL. CLARIFY.
 B) THE GRAB BAR MEASUREMENT IS SHOWN TO THE TOP OF THE
 GRIPPING SURFACE. GRAB BARS SHALL BE MEASURED TO THE
 CENTERLINE OF THE BAR PER ANSI A117.1 SEC. 4.16.4 &
 FIGURE #29..REMOVE THE NOTE REFERRING TO THE TOP OF THE
 GRIPPING SURFACE. NOTE: THE MOUNTING DETAILS AT THE
 BOTTOM OF THE DRAWING APPEAR TO SSHOW THE GRAB BAR
 MEASUREMMENT TO THE BOTTOM OF THE GRAB BAR. DETAILS AT
 THE BOTOM OF THE DRAWING REFER TO ID DRAWINGS. THERE
 ARE NO SUCH DRAWINGS IN THIS SUBMITTAL. CLARIFY
 32) SHT. A-5.10 - HANDICAP MOUNTING HEIGHTS - SHOW THE
 LOCATION OF THE GRAB BAR ADJACENT TO THE WATER CLOSET.
 COMPLY WITH ANSI A117.1 SEC.4.16.4 & FIGURE #29.
 33) SHT. A-5.10 - THE SINK AND FAUCET IN THE LOUNGE
 SHALL COMPLY WITH ANSI A117.1 SEC. 4.19.2.2, 4.19.3,
 4.19.5. SHOW THE CLEAR FLOOR SPACE ON THE PLAN WITH THE
 DIMESIONS. ALSO, INDICATE ON THE PLAN THAT THE LOUNGE
 IS LOCATED ON THE 8TH FLOOR.WPB AMEND. TO FBC SEC.
 107.2.1.
 34) SHT. A-8.5 - DETAIL #15 - SUBMIT MANUFACTURER'S
 DETAILS/ INSTALLATION INSTRUCTIONS FOR THE FLUID
 APPLIED SHOWER PAN MATERIAL. THE MATERIAL SHALL COMPLY
 WITH FBC-PLUMBING SEC.417.5.2.6.
 35) SHT. A-8.5 - DETAIL #15 REFERS TO DETAIL #8 ON SHT.
 A-8.3. DETAIL #8 ON A-8.3 IS FOR A WINDOW SILL DETAIL.
 CLARIFY.
 36) SHT. A-9.1 - DETAIL #1 - PLACE THE APPROVED LISTED
 ASSEMBLY SYSTEM NUMBER ON THE DETAIL. WPB AMEND. TO FBC
 SEC. 107.2.1.
 37) SHT. A-10.1 - UNIT A3 - WHICH DESIGN SPECIFICATION
 ( A OR B) OF THE FHA GUIDELINES APPLIES TO THIS UNIT? I
 CANNOT FIND ANY INFORMATION.CLARIFY.
 38) SHT. A-10.2 - UNITS B1 & B1 MOD - THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET IN THE HALL BATH APPEARS TO
 BE IMPINGED UPON BY THE BATHROOM FRAMED DOOR OPENING.
 CLARIFY.
 39) SHT. A-10.2 - UNIT B3 - HALL BATH - SHOW THE
 REQUIRED 30 INCH BY 48 INCH CLEAR FLOOR SPACE OUTSIDE
 THE SWING OF THE DOOR AS IT IS CLOSED AS REQUIRED BY
 THE FHA DESIGN MANUAL PAGE 7.39.
 40) SHT. A-10.2 - UNIT B3 - THE DOOR TO THE LAUNDRY
 ROOM SHALL PROVIDE A 32 INCH CLEAR OPENING AS IT
 INTENDED FOR USER PASSAGE. FHA DESIGN MANUAL PAGE 7.19.
 41) SHT A-10.2 - UNIT B3 - THE PLAN CALLS OUT TYPE A
 BATH FOR THE MASTER AND TYPE B BATH FOR THE HALL BATH.
 IF TYPE A, ALL BATHROOMS SHALL COMPLY FOR TYPE A SO YOU
 CANNOT HAVE A TYPE A AND TYPE B TOGETHER. CLARIFY.
 42) SHT. A-10.3 - CLARIFY THE ACCESSIBILITY
 REQUIREMENTS FOR THE TOWNHOMES. MY UNDERSTANDING OF THE
 FAIR HOUSING ACT REQUIREMENTS DO NOT MANDATE COMPLIANCE
 FOR MULTISTORY TOWNHOMES. TO BE A COVERED UNIT, ALL OF
 THE FINISHED LIVING SPACE MUST BE ON THE SAME FLOOR
 EXCEPT WHEN THEY ARE LOCATED IN BUILDINGS WHICH HAVE
 ONE OR MORE ELEVATORS, IN WHICH CASE, THE PRIMARY ENTRY
 IS COVERED. FHA DESIGN MANUAL PAGE 7.
 43) SHT. A-10.4 - THE FAIR HOUSING DETAILS AT THE LOWER
 RIGHT OF THE PLAN SHOW THE DEPTH OF THE LAVATORIES AS
 25 INCHES. THE MAXIMUM DEPTH OF THE LAVATORIES SHALL BE
 24 INCHES PER THE FHA DESIGN MANUAL PAGES 7.43 & 7.44.
 44) SHT. A-10.4 - EQUIPMENT MOUNTING DETAILS - THERE IS
 A NOTE THAT REFERS TO THE 2014 F.A.C. SEC. 308. THE
 2017 CODE IS THE CODE IN EFFECT. THESE ITEMS MAY FALL
 UNDER THE ANSI A117.1 STANDAED.
 45) SHT. A-10.4 - TUB GRAB BAR REINFORCEMENT DETAILS -
 IDENTIFY THE FOOT AND HEAD OF THE TUB FOR THE DETAILS
 SHOWING THE 24 INCH WIDE REINFORCEMENT. COMPLY WITH FHA
 DESIGN MANUAL PAGES 6.8 & 6.9.
 46) SHT. A-10.4 - SUBMIT A GRAB BAR REINFORCEMENT
 DETAIL FOR THE SHOWERS. FHA DESIGN MANUAL PAGE 7.56.
 47) SHT. A-10.5 - THE COMMON AREAS SHALL COMPLY WITH
 ANSI A117.1 PER THE FHA DESIGN MANUAL REQUIREMENT #2,
 PAGE 2.5. PLACE A NOTE ON THE PLAN REFERENCING THE ANSI
 STANNDARD AND REMOVE REFERENCE TO THE FLORIDA BUILDING
 CODE - ACCESSIBILITY.. THE PLANS REFERENCE THE 2014
 FBC-ACCESS. WHICH IS NOT APPLICABLE.
 48) SHT. A-10.5 - THE ELEVATION DETAILS FOR THE WATER
 CLOSETS SHOW THE GRAB BARS MEASURED TO THE CENTERLINE
 OF THE GRAB BAR BUT THE TEXT STATES " TOP OF GRIPPING
 SURFACE." THE ANSI STANDARD SHOWS GRAB BARS MEASURED TO
 THE CENTERLINE. CLARIFY.
 49) SHT. A-5.9 - WOMEN'S RESTROOM #A-0126 - TOILET ROOM
 ENLARGEMENT PLAN - THERE ARE TWO HANDICAP ACCESSIBLE
 TOILET ROOMS SHOWN BUT ONE OF THE TOILET ROOMS DOES NOT
 HAVE A LAVATORY WITHIN THE TOILET ROOM. CLARIFY. ALSO,
 THE DOOR CANNOT SWING INTO THE CLEA FLOOR SPACE FOR THE
 WATER CLOSET PER FBC-ACCESS. SEC.603.2.3.( SEE
 EXCEPTION #2 - SHOW THE CLEAR FLOOR SPACE AND THE
 DIMENSIONS).
 50) SHT. A-5.9 - MEN'S TOILET ROOM #A-0125 - THE DOOR
 CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY. FBC-ACCESS. SEC.603.2.3.( SEE EXCEPTION #2 -
 SHOW THE CLEAR FLOOR SPACE AND THE DIMENSIONS).
 51) SUBMIT A DETAIL OF THE DOMESTIC BOOSTER PUMP
 SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
 52) SUBMIT A SANITARY RISER DIAGRAM OF THE COMPLETE
 UNDERGROUND SANITARY COLLECTION SYSTEM WITH ALL
 VERTICAL RISER LINES IDENTIFIED WITH RISER TAGS. SHOW
 THE SLOPE OF THE SANITARY LINES. COMPLY WITH
 FBC-PLUMBING TABLE 710.1 (1). WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 53) SHT. P-2.0A - KEYNOTE #6 REFERS TO A DETAIL BUT
 THERE IS NO SPECIFIC DETAIL REFERENCED. ( DRAWING #,
 DETAIL #). CLARIFY.
 54) SHT. P-2.0A - IDENTIFY ALL RISERS WITH RISER TAGS,
 INCLUDING THE VENTS/DRY VENTS. WPB AMEND. TO FBC SEC.
 107.2.1.
 55) THE WATER SUPPLY VALVES FOR THE STACKED
 WASHER/DRYER UNITS SHALL BE PROVIDED WITH ACCESS PER
 FBC-PLUMBING SEC. 606.3.
 56) SUBMIT A COMPLETE RAIN WATER RISER AND UNDERGROUND
 COLLECTION SYSTEM.ALL VERTICAL RISSER LINES SHALL BE
 IDENTIFIED WITH RISER TAGS. THE SIZING OF THE SYSTEM
 SHALL INCLUDE THE AREA OF ALL VERTICAL WALLS THAT
 DIVERT RAINWATER TO THE ROOF IN ACCORDANCE WITH
 FBC-PLUMBING SEC.1106.4, WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 57) SHT. P-2.0A & P-2.B - THE MATCH LINES NOTED ON THE
 PLANS APPEAR TO BE INCORRECT. CLARIFY.
 58) SHT.P-2.0B - IDENTIFY FIXTURE OI-1 CONNECTED TO THE
 FLOOR DRAINS.THIS FIXTURE IS NOT LISTED ON THE PLUMBING
 FIXTURE SCHEDULE AND SUBMIT A DETAIL FOR THIS ITEM.WPB
 AMEND. TO FBC SEC. 107.2.1.
 59) SHT. P-2.0B - IDENTIFY THE SANITARY AND VENT RISERS
 WITH RISER TAGS. WPB AMEND. TO FBC SEC. 107.2.1.
 58) SHT. P-2.0B - THE MATCH LINES AT THE TOP OF THE
 PAGE APPEAR TO BE INCORRECT. SHT. P-2.0B SHOWS SANITARY
 LINES AND SHT. P-2.0C SHOWS WATER LINES. CLARIFY.
 60) SHT. P-2.0C - PROVIDE A MATCHLINE ON THE RIGHT SIDE
 OF THE PLAN FOR THE CONTINUATION OF THE 6 INCH SANITARY
 LINE WITH 152 DFU'S EXITING UNIT B3.
 61) SHT. P-2.1A - IDENTIFY ALL THE STORM RISERS WITH
 RISER TAGS. WPB AMEND. TO FBC SEC. 107.2.1.
 62) DRAWING SERIES P-2.1 THROUGH P-2.8 - PLACE A RISER
 TAG ON THE 2 INCH VENT LINE AS REFERENCED IN KEYNOTE #1
 AND TAG THE RAIN WATER RISERS ON THE APPLICABLE
 DRAWINGS. WPB AMEND. TO FBC SEC. 107.2.1.
 63) SHT. P-2.1C - KEYNOTE #4 STATES "4 INCH STORM PIPE
 DOWN" BUT THE ARROW IS POINTING TO A WATER BRANCH LINE.
 CLARIFY.
 64) SHT. P-2.1D - KEYNOTE #5 - LIST THE SPECIFIC
 DRAWING NUMBER IN THE FOOTNOTE FOR THE CONTINUATION OF
 THE WATER AND SANITARY LINES.WPB AMEND. TO FBC SEC.
 107.2.1.
 65) SHTS. P-2.2C, P-2.3B & P-2.3C- SUBMIT THE
 APPLICABLE KEYNOTE LEGEND FOR THESE PLANS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 66) SHT. P-2.8A - UNITS A2 - THERE ARE TWO RISERS SHOWN
 AT THE WASHING MACHINE BUT THERE IS NO RISER TAG ON ONE
 OF THE RISERS. CLARIFY.
 67) SHT. P-2.8A - UNITS A2 - THERE IS A RISER TAG 4/S
 BEHIND THE WATER CLOSET BUT NO RISER IS SHOWN. CLARIFY.
 68) SHT. P-5.1 - KEYNOTE #3 - STATE THE SPECIFIC
 DRAWING NUMBER FOR THE CONTINUATION OF THE WATER
 LINE.WPB AMEND. TO FBC SEC. 107.2.1.
 69) SHTS. P-4.1 7 P-4.2 - KEYNOTE 39 REFERS TO AIR
 ADMITTANCE VALVES BUT NOTHING IS SHOWN ON THE PLANS.
 CLARIFY. NOTE: WHERE THE HORIZONTAL BRANCH IS LOCATED
 MORE THAN 4 BRANCH INTERVALS FROM THE TOP OF THE STACK,
 THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF
 VENT THAT SHALL CONNECT TO A VENT STACK OR STACK VENT,
 OR EXTEND OUTDOOR TO THE OPEN AIR PER FBC-PLUMBING
 SEC.918.3.1.
 70) SHT.P-5.1 - THE FLOOR DRAIN IN THE PAVILION EXCEEDS
 THE DISTANCE TO A VENT PER FBC-PLUMBING SEC.909.1 7
 TABLE 909.1.
 71) SHT. P-5.1 SHOWS AN AIR ADMITTANCE VALVE ON THE
 SINK.THE USE OF AN AIR ADMITTANCE MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, IT SHALL OMPLY
 WITH FBC-PLUMBING SEC.918.3.1.WHERE THE HORIZONTAL
 BRANCH IS LOCATED MORE THAN 4 BRANCH INTERVALS FROM THE
 TOP OF THE STACK, THE HORIZONTAL BRANCH SHALL BE
 PROVIDED WITH A RELIEF VENT THAT SHALL CONNECT TO A
 VENT STACK OR STACK VENT, OR EXTEND OUTDOOR TO THE OPEN
 AIR PER FBC-PLUMBING SEC.918.3.1.
 72) SHT. P-5.1 - PROVIDE A SANITARY AND WATER RISER
 DIAGRAM FOR THE TOILET ROOMS AND SINK AT THE POOL DECK.
 WPB AMEND. TO FBC SEC. 107.2.1.
 73) THERE IS A FIRE PIT SHOWN ON SHT. A-2.1A. IS THIS
 FFIRE PIT GAS? IF SO, SUBMIT A GAS RISER DIAGRAM FOR
 ANY AND ALL GAS PIPING THAT WILL BE INSTALLED IN THIS
 BUILDING.WPB AMEND. TO FBC SEC. 107.3.5.1.5. ALSO,
 SUBMIT COMBUSTION AIR CALCCULATIONS FOR ANY
 EQUIPMENT/APPLIANCES LOCATED ON THE INTERIOR OF THE
 STRUCTURE.
 74) SHT.P-5.2 - THE WATER CLOSETS IN THE WOMEN'S
 RESTROOM ARE NOT PROPERLY VENTED. THE VENT SHALL BE
 LOCATED BETWEEN THE TWO WATER CLOSETS.FBC-PLUMBING SEC.
 901.2,
 75) SHT. P-6.1 - RISER #4/S - TRAPS ARE MISSING ON THE
 SHOWERS.
 76) SHT. P-6.1 - RISER #5/S - THE RISER DECREASES IN
 PIPE SIZE FROM 3 INCHES TO 2 1/2 INCHES IN THE
 DIRECTION OF FLOW AT THE BOTTOM OF THE STACK.
 FBC-PLUMBING SEC. 704.2. CLARIFY.
 77) SHT. P-6.1 - RISER #8/S - SIZE THE RISER.
 78) SHT. P-6.2 - RISER#10/S - SHOWS A 3 INCH STACK AND
 A 2 INCH VTR. THE VENT THROUGH THE ROOF SHALL BE 3
 INCHES PER FBC-PLUMBING SEC.913.3.
 79) SHT. P-8.1 - WATER HEATER DETAIL - INICATE ON THE
 DETAIL THE TYPE OF PIPE MATERIAL TO BE USED FOR THE PAN
 DRAIN AND THE THERMAL INSULATION ON THE HOT WATER
 LINE.THE PAN DRAIN MATERIAL SHALL COMPLY WITH THE
 FBC-MECH. SECS.602.2.1 & 602.2.1.7.
 80) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 SUBMETERS BEING INSTALLED. IF THEY ARE BEING INSTALLED
 IN THE MECHANICAL CLOSET, THEY SHALL COMPLY WITH
 FBC-MECH. SECS. 602.2.1 & 602.2.1.7.
 81) INDICATE ON THE PLANS (SHT. A-8.5) IF THE TRASH
 CHUTE WILL BE EQUIPPED WITH A FLUSHING RING AT THE TOP
 OF THE CHUTE. IF SO, SUBMIT A DETAIL FOR THE WATER
 CONNECTION. IF A CHEMICAL SOLUTION WILL BE CONNECTED TO
 THE SYSTEM, A BACKFLOW DEVICE SHALL BE REQUIRED.
 FBC-PLUMBING SEC.608.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  