2021-02-19 13:58:001ST REVIEW FBC-2020 MECHANICAL
 PERMIT- 20120712
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION CODE
 FBC FG- FLORIDA FUEL GAS CODE
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) THIS IS A MULTIFAMILY APARTMENT BUILDING PLEASE
 EXPLAIN THE USE OF ?GUEST ROOMS (HOTEL) IN THE ENERGY
 CALCULATIONS. FBC M TABLE 403.3.1.1
  
 2) PLEASE PROVIDE VENTILATION CALCULATIONS FOR EACH
 DWELLING UNIT. FBC M 401.2
  
 3) THE DUCTWORK COMING OUT OF THE RATED SHAFT IN THE
 CORRIDORS SHOULD BE PROTECTED BY A FSD BUT THE SYMBOL
 THAT IS IN THE LOCATION DOES NOT APPEAR ON SHEET M-0.1.
 PLEASE IDENTIFY THE CORRECT DAMPER FOR THE DUCTWORK
 PENETRATING THE RATED SHAFT. FBC M 607
  
 4) PLEASE IDENTIFY THE RTU FOR THE DUCTWORK PENETRATING
 THE SHAFTS IN THE CORRIDORS AT EACH FLOOR. FBC 107.2.1
  
 5) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH
 SPACE IN THESE BUILDINGS. FBC M 403.3.1.1
  
 6) PLEASE PROVIDE A COMPLETE OUTDOOR AIR CALCULATION
 FOR THE RETAIL TENANT SPACE. FBC TABLE 403.3.1.1
  
 7) PLEASE PROVIDE THE CFM?S SUPPLIED BY THE REGISTER IN
 THE CORRIDOR CLOSE TO THE A1 UNITS ON THE LEFT SIDE OF
 THE PAGE. FBC 107.2.1
  
 8) TYPICAL UNIT SHEETS: PLEASE PROVIDE THE MAKE AND
 MODEL OF THE SPECIFIC DRYER USED IN EACH UNIT. FBC M
 504.8.4.2
  
 9) TYPICAL UNITS SHEETS: PLEASE PROVIDE THE DRYER DUCT
 LENGTHS INCLUDING THE 45 AND 90 DEGREE ELBOWS. FBC M
 504.8.5
  
 10) TYPICAL UNITS SHEETS: PLEASE VERIFY THE EXHAUST IS
 A MINIMUM OF 3? FROM ANY OPERABLE OPENING INTO THE
 UNITS. FBC M 501.3.1 (3)
  
 11) TYPICAL UNITS SHEETS: DOES NOTE (8) REFER TO THE
 MECHANICAL CLOSET DOORS? IF SO EITHER LABEL EACH DOOR
 OR ADD THE WORDS TO NOTE 8 THAT THIS IS THE MECHANICAL
 CLOSET DOOR AS SOME DOORS DO NOT HAVE THE FOOTNOTE 8
 LABELED ON THE UNIT DRAWINGS. FBC 107.2.1
  
 12) SHEET M-4.2: UNIT B1 IS SUPPLYING 860 CFM OF AIR TO
 THE UNIT BUT SHEET M-7.1 INDICATES THAT AHU-B ONLY
 SUPPLIES 800 CFM OF SUPPLY AIR. PLEASE CORRECT THIS.
 FBC 107.2.1
  
 13) SHEET M-4.2: UNIT B3; PLEASE SHOW CFM OF SUPPLY AIR
 TO CLOSET, THE CFM?S HAVE NOT BEEN INCLUDED IN THIS
 VERSION. FBC 107.2.1
  
 14) SHEET M-4.2: UNIT B3; THE SUPPLY AIR IS 830 CFM,
 AHU-B ONLY SUPPLIES 800 CFM. PLEASE CORRECT THIS. FBC
 107.2.1
  
 15) SHEET M-4.3: THE UNIT-C TH INDICATES AHU-C IS
 SUPPLYING 1210 CFM OF AIR. SHEET M-7.1 INDICATES AHU-C
 ONLY SUPPLIES 1050 CFM. PLEASE CORRECT. FBC 107.2.1
  
 16) SHEET M-5.2: AHU-3 IS SUPPLYING 2135 CFM OF AIR BUT
 SHEET M-7.1 INDICATES AHU-3 ONLY SUPPLIES 1900 CFM.
 PLEASE CORRECT. FBC 107.2.1
  
 17) SHEET M-7.1: RTU-3 INDICATES A MAX. OF SUPPLY AIR
 IS 2,450 CFM. THE TOTAL OF SUPPLY AIR FOR EACH FLOOR IS
 2,800CFM. PLEASE CORRECT THIS. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  