2021-05-15 04:24:571) SHT. P-2.0A - PROVIDE A MATCHLINE AT THE TOP OF PLAN
 FOR THE CONTINUATION OF THE GAS LIINE. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) SHT. P-2.0A SHOWS THE GAS LINE AS 3/4 INCH AND SHT.
 P-2.0B SHOWS THE GAS LIINE AS 1 INCH. CLARIFY.
 3) THE LAYOUT OF THE GAS LINE BETWEEN SHEETS P-2.0A &
 P-2.0B DO NOT CORRELATE WITH EACH OTHER. CLARIFY.
 4) SHT. P-2.0B - KEYNOTE #10 - LIST THE SPECIFIC CIVIL
 DRAWING FOR THE CONTINUATION OF THE GAS LINE. I COULD
 NOT FIND THE GAS LINE ON THE CIVIL DRAWINGS.
 5) SHT. P-6.9 - INDICATE ON THE PLAN WHICH SIZING TABLE
 FROM THE GAS CODE IS BEING UTILIZED FOR THE LOW
 PRESSURE SYSTEM. SHOW THE TYPE OF PIPING ON THE PLAN.
 6) THE INSTALLATION OF THE PRESSURE REGULATORS SHALL
 COMPLY WITH FBC-FUEL GAS SEC. 410.2 (1-7).
 7) A SEPARATE PERMIT WILL BE REQUIRED FOR THE GAS
 SYSTEM.
 8) SUBMIT COPIES OF THE MANUFACTURER'S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC- FUEL GAS CODE SEC. 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FBC-FUEL GAS
 CODE SEC.305.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  