Plan Review Notes
Plan Review Notes For Permit 20120712
Permit Number 20120712
Review Stop E
Sequence Number 1
Notes
Date Text
2021-02-19 16:23:24FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGES E-2.1A, E-2.1B, AND E-2.1C NEED TO SUBMIT AN
 ENLARGED PLANS OF ALL ELECTRICAL ROOMS.
  
 2) NEED TO SUBMIT A ONE LINE DIAGRAM SHOWING ALL
 SERVICES IN THIS BUILDING. 215.5
  
 3) FIRE PUMP SHOWS ONLY FPL AS A SOURCE OF POWER PER
 695.3 FPL IS NOT A RELIABLE SOURCE.
  
 4) PAGES E-7.1 AND E-7.3 NEED TO SHOW AIC CALCULATION.
  
 5) PAGES E-7.1 AND E-7.3 SHOW WHAT METHOD IS TO BE USED
 TO COMPLY WITH 240.87
  
 6) 230.2 ALLOWS FOR MORE THAN ONE SERVICE UNDER CERTAIN
 CONDITIONS PLEASE SHOW WHY WE HAVE SO MANY SERVICES
 THAT DO NOT MEET THE REQUIREMENTS OF THIS SECTION AND
 230.72.
  
 7) PAGES E-4.1 THRU E-4.3 UNIT PLANS NEEDS TO WITH FBC
 R314.3(4), AND R314.1 FOR INSTALLATION OF SMOKE ALARMS
 NEAR BATHROOMS AND COOKING APPLIANCES.
  
  
 BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, ACCESS
 CONTROL, CCTV, DAS, BDA, LIGHTNING PROTECTION,
 GENERATORS, COMMERCIAL HOODS SYSTEMS, WALK IN COOLERS,
 SIGNS, SITE LIGHTING AND SWIMMING POOLS, WHERE
 APPLICABLE ARE NOT INCLUDED IN THE SCOPE OF THIS PLAN
 REVIEW
  
  