2021-02-22 13:57:35 | NEW 8 STORY APT BUILDING |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE SHOW THE PROTECTED OPENING CALCULATIONS FOR |
| THE NORTH EAST CORNER OF THE APT BUILDING PER FBC 705.8 |
| 2) PLEASE SHOW THE TRASH CHUTE (ROOM OR COMPARTMENT) |
| WALL AND DOOR FIRE RATING FROM THE CORRIDORS PER FBC |
| 713.13.3 CHUTE ACCESS ROOMS. |
| ACCESS OPENINGS FOR WASTE OR LINEN CHUTES SHALL BE |
| LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS |
| THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE |
| WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| IN ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO |
| THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING |
| PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS |
| THAN 3/4 HOUR. DOORS SHALL BE SELF- OR |
| AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN |
| ACCORDANCE WITH SECTION 716.5.9.3. |
| 3) DRAWING S-3.1 SHOW BEAM ELEVATION USING NGVD OTHER |
| DRAWINGS USE NAVD ELEVATIONS - PLEASE CLARIFY. |
| 4) DRAWING A-3.10 SHOWS THE GARAGE FLOOR ELEVATION AT |
| 50' 6" AND THE PARAPET HEIGHT AT 53' - DOES NOT MEET |
| THE REQUIRED GUARD HEIGHT PER FBC 1015.3 |
| 5) DRAWING A-5.1 SHOULD SHOW A GUARD RAIL AT SECTION |
| "B" - FBC 1015 |
| 6) PLEASE PROVIDE A HANDRAIL DETAIL FOR THE RAMPS FBC |
| 1012.8 |
| 7) PLEASE SHOW THE POOL AREA AND THE OUTSIDE A3 |
| PAVILION/MULTI PURPOSE LAWN EXIT GATE WIDTHS FBC |
| 1010.1.1 AND OPENING HARDWARE TO COMPLY WITH FBC |
| 1010.1.9.1 - 1010.1.10 PANIC AND FIRE EXIT HARDWARE. |
| DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING |
| ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN |
| A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A |
| LATCH OR LOCK OTHER THAN PANIC HARDWARE OR FIRE EXIT |
| HARDWARE. |
| 8) PLEASE SHOW THE DISCERNIBLE PATH THROUGH THE OUTDOOR |
| FITNESS GYM AREA FROM THE OUTDOOR PAVILION/COURT YARD |
| AREA FBC 1016.2 EGRESS THROUGH INTERVENING SPACES. (2.) |
| EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH |
| ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE |
| SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE |
| ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H |
| OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS |
| TRAVEL TO AN EXIT. |
| 9) APT UNIT B3 SHOWN ON DRAWING A-10.2 - BATH TYPE "B" |
| PLEASE SHOW THE 30X48 DOOR SWING CLEAR FLOOR SPACE FBC |
| ACCESSIBILITY FHA REQUIREMENT NUMBER 7 USEABLE |
| BATHROOMS - (I)WHERE THE DOOR SWINGS INTO THE BATHROOM, |
| THERE IS A CLEAR SPACE (APPROXIMATELY 2?6" BY 4?0") |
| WITHIN THE ROOM TO POSITION A WHEELCHAIR OR OTHER |
| MOBILITY AID CLEAR OF THE PATH OF THE DOOR AS IT IS |
| CLOSED AND TO PERMIT USE OF FIXTURES. THIS CLEAR SPACE |
| CAN INCLUDE ANY KNEESPACE AND TOESPACE AVAILABLE BELOW |
| BATHROOM FIXTURES. |
| 10) APT. UNIT B1 SHOWN ON DRAWING A-10.2 - THE SHOWER |
| DOOR SHOULD BE ON THE OPPOSITE SIDE TO ALLOW THE SHOWER |
| CONTROLS TO BE REACHED FROM OUTSIDE THE SHOWER FBC |
| ACCESSIBILITY FHA REQUIREMENT NUMBER 7 USEABLE |
| BATHROOMS (VII)STALL SHOWERS IN THE BATHROOM MAY BE OF |
| ANY SIZE OR CONFIGURATION. A MINIMUM CLEAR FLOOR SPACE |
| 2'6" WIDE BY 4'0" SHOULD BE AVAILABLE OUTSIDE THE |
| STALL. (SEE FIGURE FHAG-7(D).) |
| 11) ALL UNIT DOORS - PLEASE SHOW THE REQUIRED |
| MANEUVERING SPACE (18" BESIDE THE DOOR) TO EXIT THE |
| UNIT OR ROOM. FBC ACCESSIBILITY FHA REQUIREMENT ANSI |
| 4.13.6 |
| 12) PLEASE PROVIDE AN ORIGINAL SIGNED AND SEALED COPY |
| OF THE SOIL REPORT. |
| 13) PLEASE PROVIDE COMPLETE COPIES OF THE EXTERIOR |
| WINDOWS, DOORS, LOUVERS ETC AS LISTED ON THE DRAWINGS. |
| 14) PLEASE PROVIDE COMPLETE COPIES OF THE ROOFING |
| SYSTEM PRODUCT APPROVALS. |
| 15) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD OR |
| BE LISTED ON THE DRAWINGS. |
| 16) PLEASE PROVIDE THE FOLLOWING ACOUSTICAL TEST |
| REPORTS |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |
| 17) PLEASE PROVIDE THE REQUIRED THRESHOLD INSPECTION |
| FORMS AND DOCUMENTS DESCRIBED IN "GUIDELINES AND |
| POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL |
| INSPECTORS AND RESIDENT INSPECTORS". PLEASE E MAIL |
| ([email protected]) FOR A COPY OF THE GUIDELINES. |
| 18) TOWNHOUSE BUILDING, PAVILION, POOL AND FENCING |
| SHALL BE A SEPARATE PERMIT - PLEASE ACKNOWLEDGE THIS. |
| 19) PLEASE USE A DIFFERENT LANGUAGE FOR THE TOWNHOUSE |
| BUILDING - TOWNHOUSE AS DEFINED IN THE FBC - [A] |
| TOWNHOUSE. A SINGLE-FAMILY DWELLING UNIT NOT EXCEEDING |
| THREE STORIES IN HEIGHT CONSTRUCTED IN A GROUP OF TWO |
| OR MORE ATTACHED UNITS WITH PROPERTY LINES SEPARATING |
| SUCH UNITS IN WHICH EACH UNIT EXTENDS FROM THE |
| FOUNDATION TO ROOF AND WITH A YARD OR PUBLIC WAY ON NOT |
| LESS THAN TWO SIDES. |
| 20) LIFE SAFETY PLAN SHOWS THE SAME SQUARE FOOTAGE FOR |
| FLOOR 3 AND 4 - NOT CORRECT 4TH FLOOR AND ABOVE SHOULD |
| BE LESS - PLEASE SHOW THE CORRECT SQUARE FOOTAGE FOR |
| EACH FLOOR. SHOW THE GARAGE SQUARE FOOTAGE FOR EACH |
| FLOOR SEPARATELY. |
| 21) PLEASE CLEARLY SHOW THE REQUIRED POOL BARRIER AND |
| ALL COMPONENTS GATES, LOCKS, HARDWARE, DOOR OPERATION |
| FROM BUILDING ETC TO COMPLY WITH FBC 454.1.3.1.9 |
| 22) ROOFING SYSTEMS, WINDOW, DOOR AND LOUVER PRODUCT |
| APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS |
| TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - |
| 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| APPROVED BY THE BUILDING OFFICIAL. |
| |
| |
| |
| |