2021-01-12 08:21:20PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE FOLLOWING COMMENT WAS NOT ADDRESSED. PLEASE CORRECT
 THE SPANS FOR THE OPENINGS ON THE INSTALLATION SCHEDULE
 FOR THE ARMOR SCREEN.
  
 1) THE SPAN FOR THE ARMOR SCREEN IS SPECIFIED AS 80"
 FOR ALL OF THE OPENINGS IN THE STORM PANEL SCHEDULE.
 THE SPAN FOR THE FABRIC SCREENS IS THE CENTER TO CENTER
 DISTANCE BETWEEN THE GROMMETS (ANCHORS) ON EACH SIDE OF
 THE OPENING. PLEASE CORRECT.
  
  