Plan Review Notes For Permit 20120647 |
Permit Number |
20120647 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-06-01 08:43:55 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PANEL "B" NEEDS TO HAVE A MAIN BREAKER, THERE ARE MORE | | THAN 6 CIRCUITS SO A MAIN IS REQUIRED | | | | 230.71 MAXIMUM NUMBER OF DISCONNECTS. (A) GENERAL. THE | | SERVICE DISCONNECTING MEANS FOR EACH SERVICE PERMITTED | | BY 230.2, OR FOR EACH SET OF SERVICE-ENTRANCE | | CONDUCTORS PERMITTED BY 230.40, EXCEPTION NO. 1, 3, 4, | | OR 5, SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR | | SETS OF CIRCUIT BREAKERS, OR A COMBINATION OF NOT MORE | | THAN SIX SWITCHES AND SETS OF CIRCUIT BREAKERS, MOUNTED | | IN A SINGLE ENCLOSURE, IN A GROUP OF SEPARATE | | ENCLOSURES, OR IN OR ON A SWITCHBOARD OR IN SWITCHGEAR. | | THERE SHALL BE NOT MORE THAN SIX SETS OF DISCONNECTS | | PER SERVICE GROUPED IN ANY ONE LOCATION. |
|