2021-06-01 08:43:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PANEL "B" NEEDS TO HAVE A MAIN BREAKER, THERE ARE MORE
 THAN 6 CIRCUITS SO A MAIN IS REQUIRED
  
 230.71 MAXIMUM NUMBER OF DISCONNECTS. (A) GENERAL. THE
 SERVICE DISCONNECTING MEANS FOR EACH SERVICE PERMITTED
 BY 230.2, OR FOR EACH SET OF SERVICE-ENTRANCE
 CONDUCTORS PERMITTED BY 230.40, EXCEPTION NO. 1, 3, 4,
 OR 5, SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR
 SETS OF CIRCUIT BREAKERS, OR A COMBINATION OF NOT MORE
 THAN SIX SWITCHES AND SETS OF CIRCUIT BREAKERS, MOUNTED
 IN A SINGLE ENCLOSURE, IN A GROUP OF SEPARATE
 ENCLOSURES, OR IN OR ON A SWITCHBOARD OR IN SWITCHGEAR.
 THERE SHALL BE NOT MORE THAN SIX SETS OF DISCONNECTS
 PER SERVICE GROUPED IN ANY ONE LOCATION.