Plan Review Notes For Permit 20120647 |
Permit Number |
20120647 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-04-15 08:27:08 | GUEST HOUSE REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | REVISED DRAWINGS | | 1) PLEASE SHOW THE WOOD SHINGLE ATTACHMENTS FOR WIND | | ZONE 5 WHICH IS A HIGHER WIND PRESSURE THEN FBC | | R703.6.3 ATTACHMENT. | | WOOD SHAKES OR SHINGLES SHALL BE INSTALLED ACCORDING TO | | THIS CHAPTER AND THE MANUFACTURER?S INSTRUCTIONS. WHERE | | WIND PRESSURES DETERMINED IN ACCORDANCE WITH TABLE | | R301.2(2) DO NOT EXCEED 30 PSF. | | 2) WINDOW SCHEDULE SHOWS A PRODUCT APPROVAL NUMBER | | (17-0918.11) WHICH IS NOT PROVIDED - PLEASE REVISE THE | | WINDOW SCHEDULE TO SHOW THE PRODUCT APPROVAL NUMBERS | | PROVIDED. | | | | |
|