Plan Review Notes
Plan Review Notes For Permit 20120647
Permit Number 20120647
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-18 09:35:3212/18/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE ON PLUMBING ISOMETRIC RISER DIAGRAM
 WHERE THE WASHING MACHINE WILL BE CONNECTED TO, IF IT
 IS TO THE OUTSIDE, IT WILL NEED TO BE A VENT TO THE
 OUTSIDE, IF IT IS TO THE EXISTING SYSTEM INSIDE ( AN
 AIR ADMITTANCE VALVE MAY BE USED). THE TWO DRAINAGE
 LINES, KS AND W/M, ARE NOT SIZED FOR THE HORIZONTAL
 DRAIN ( W/M REQUIRES A 3? STACK PER MOST MANUFACTURERS
 SPECIFICATION AND PLUMBING CODE 2017 FBC SEC. P 406.2
 WASTE CONNECTION).
  
 NOTE: FOR THE NEW PLUMBING INFORMATION PROVIDE, THIS
 MAY CHANGE WHEN DUE TO STRUCTURE. THESE CHANGES CAN BE
 REVISED BEFORE FINAL PLUMBING PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING.
  
 2. A LICENSED CONTRACTOR MUST REQUIRE A SUB PLUMBING
 PERMIT FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO
 THE FBC SEC. 105.1.
  
 3. THESE ARE MULTI-FAMILY DWELLINGS, AND THE WATER
 USERS WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM.
  
 4. ON SHEET A-1, IT SAYS THE WATER HEATER IS EXISTING,
 AND IT IS GOING TO BE REPLACED WITH A TANK-LESS. THERE
 IS NO INDICATION IF IT OR WAS ELECTRICAL OR GAS. ON
 SHEET E-1, THERE IS AN IN-STA HOT IGNITOR, SO IS THIS
 FOR THE KITCHEN SINK OR THE SOURCE OF HEATING THE
 WATER? PLEASE CLARIFY.
  
 5. THE SHEET MP-1 SHOWS A GAS TANK-LESS WATER HEATER
 THAT MAY CLARIFY THE COMMENT ABOVE, BUT IT SAYS
 EXISTING GAS TANK WATER HEATER. THE CITY OF WEST PALM
 BEACH HAS NO RECORD OF A GAS PERMIT FOR THIS STRUCTURE,
 AND THE CITY OF WEST PALM BEACH WILL NEED A FULL GAS
 EVALUATION ALONG WITH A SUB GAS PERMIT WILL BE REQUIRED
 AT OWNER EXPENSE. YOU MAY HAVE A GAS REVIEW DONE AT
 THIS TIME FOR THE SUB GAS PERMIT, BUT ALL INFORMATION
 HAS TO BE SUBMITTED FOR A REVIEW. YOU MAY CHOOSE TO DO
 A REVIEW FOR THE GAS LATER BY A LICENSED CONTRACTOR, SO
 PLACE A NOTE ON THE PLANS, PLEASE.
  
 NOTE: GAS UNIT VENTING AND PLACEMENT TO DOORS OR
 WINDOWS MAY WORK BETTER OUTSIDE THE STRUCTURE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved